초고층 및 지하연계 복합건축물 재난관리에 관한 특별법 시행규칙
287847 · 2026-07-01
National Fire Agency ( Prevention Policy Division ), 044-205-7446
Chapter 1 General Provisions
Article 1 (Purpose) The purpose of this rule is to prescribe matters delegated by the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings and the Enforcement Decree of the same Act , as well as matters necessary for the implementation thereof.
Article 1-2 (Underground-linked complex buildings) Regarding the method for calculating the number of occupants on the ground floor of a building pursuant to the proviso of Article 2, Paragraph 2 of the Enforcement Decree of the Special Act on Disaster Management of Super High -rise and Underground-linked Complex Buildings (hereinafter referred to as the “Decree”), the method for calculating the number of occupants pursuant to Item 1, Subparagraphs (a) and (b) of Annex 1-2 of the Rules on Standards for Evacuation, Fire Protection, and Structures of Buildings shall apply mutatis mutandis.
[This Article Newly Inserted Feb. 14, 2025]
Chapter 2 Prevention and Preparation
Article 1-3 (Application and Notification of Prior Disaster Impact Assessment) ① In Article 5, Paragraph 2 of the Enforcement Decree, the term “application for assessment prescribed by the Ordinance of the Ministry of the Interior and Safety”refers to the application for prior disaster impact assessment in Form No. 1 of the Attached Form .
② When the Mayor of a Special City, Integrated Special City, Metropolitan City, Special Self-Governing City, or Governor of a Province or Special Self-Governing Province (hereinafter referred to as “Mayor/Governor”) notifies the results of a prior disaster impact assessment pursuant to Article 6, Paragraph 3 of the “ Special Act on Disaster Management of Super High-Rise and Underground-Linked Complex Buildings” (hereinafter referred to as the “Act”) , they shall use the Notification of Prior Disaster Impact Assessment Results in the form of Annex 1-2 . <Amended July 1, 2026>
[This Article Newly Inserted Feb. 14, 2025]
Article 1-4 (Application for Re-evaluation and Notification) ① In Article 5-2, Paragraph 1 of the Enforcement Decree, the term “application for re-evaluation prescribed by the Ordinance of the Ministry of the Interior and Safety”refers to the application for re-evaluation of the prior disaster impact assessment in Form No. 1-3 of the Appendix .
② When a mayor or provincial governor notifies the results of a reassessment pursuant to Article 5-2, Paragraph 2 of the Enforcement Decree , they shall use the Notification of Results of Reassessment of Pre-disaster Impact Assessment in Form No. 1-2 of the Appendix .
[This Article Newly Inserted Feb. 14, 2025]
Article 2 (Duties of the General Disaster Manager) The term “matters prescribed by the Ordinance of the Ministry of the Interior and Safety” in Article 12, Paragraph 1, Item 10 of the Act refers to the following matters:
1. Matters concerning the maintenance, management, inspection, repair, etc. of buildings and facilities pursuant to Article 3 of the Act (hereinafter referred to as “super high-rise buildings, etc.”)
2. Matters concerning the implementation of integrated safety inspections pursuant to Article 13 of the Act
3. Matters concerning the establishment and implementation of publicity plans pursuant to Article 15 of the Act
4. Matters concerning the establishment and implementation of plans for crime prevention, security, and terrorism preparedness and response
[Wholly Amended Feb. 14, 2025]
Article 3 (Appointment and Registration of General Disaster Manager) ①A managing entity of a super high-rise building, etc., that intends to register the appointment of a general disaster manager pursuant to Article 13-3, Paragraph 3 of the Enforcement Decree shall submit an application for registration of the appointment of a general disaster manager in the form of Annex 1-4, along with documents classified according to the following subparagraphs, to the Mayor of a Special Self-Governing City or the Governor of a Special Self-Governing Province (excluding the Governor of a Special Self-Governing Province where there are local government entities, such as cities and counties, within its jurisdiction; hereinafter the same applies in Paragraphs 2 and 3) or the Mayor, County Head, or District Head (referring to the head of an autonomous district; hereinafter the same applies).
1. In cases where the appointed Chief Disaster Manager falls under Article 13-3, Paragraph 1, Subparagraph 1 of the Enforcement Decree: Copy of Architect License
2. In cases where the appointed General Disaster Manager falls under Article 13-3, Paragraph 1, Subparagraph 3 of the Enforcement Decree : a copy of the Fire Facility Management Certificate, the Fire Safety Manager Qualification Handbook, or documents proving relevant experience.
3. In cases where the appointed Chief Disaster Manager falls under Article 13-3, Paragraph 1 , Subparagraph 4 or 5 of the Enforcement Decree: Documents proving practical experience in disaster and safety management
4. In cases where the appointed Chief Disaster Manager falls under Article 13-3, Paragraph 1, Subparagraph 6 of the Enforcement Decree : a copy of the Housing Manager license, and documents proving practical experience in disaster and safety management.
② The Mayor of a Special Self-Governing City, the Governor of a Special Self-Governing Province, or the Mayor, County Head, or District Head who has received an application pursuant to Paragraph 1 shall verify the national technical qualification certificate of the appointed General Disaster Manager through the joint use of administrative information pursuant to Article 36, Paragraph 1 of the Electronic Government Act if the appointed General Disaster Manager falls under any of the following subparagraphs. However, if the applicant does not consent to the verification, a copy thereof must be submitted.
1. Cases falling under Article 13-3, Paragraph 1, Subparagraph 2 of the Enforcement Decree
2. Among persons falling under Article 13-3, Paragraph 1, Subparagraph 3 of the Enforcement Decree, cases corresponding to Subparagraph 1, Item (b) 1) (applicable only to persons with the qualification of a Professional Firefighter), 2) and 3) of Annex 4 of the Enforcement Decree of the Act on the Prevention of Fire and Safety Management
3. Cases falling under Article 13-3, Paragraph 1 , Subparagraph 4 or 5 of the Enforcement Decree
③ The mayor of a special self-governing city, the governor of a special self-governing province, or the mayor, county head, or district head who has received an application pursuant to Paragraph 1 shall issue a certificate of appointment of a general disaster manager in the form of Annex 2 if they recognize that the appointed general disaster manager has the qualifications corresponding to any of the subparagraphs of Paragraph 1 of Article 13-3 of the Enforcement Decree.
④ When the Mayor of a Special Self-Governing City or the Governor of a Special Self-Governing Province (excluding the Governor of a Special Self-Governing Province where there are local government entities, such as cities and counties, within their jurisdiction) or the Mayor, County Head, or District Head has issued a Certificate of Registration for the Appointment of a General Disaster Manager pursuant to Paragraph 3, they shall record and manage the fact in the Register of Registration for the Appointment of General Disaster Managers in the Form of Annex 3 , and shall notify the contents regarding the appointment of the General Disaster Manager to the emergency rescue agencies pursuant to Article 3, Subparagraph 7 of the Framework Act on Disaster and Safety Management (excluding the Korea Coast Guard, regional Korea Coast Guard offices, and Korea Coast Guard stations; hereinafter referred to as “emergency rescue agencies” in Article 12, Paragraph 2, Subparagraph 5 ) and the Mayor of a Special City, the Mayor of a Consolidated Special City, the Mayor of a Metropolitan City, the Governor of a Province, or the Governor of a Special Self-Governing Province. <Amended July 1, 2026>
[Wholly Amended Feb. 14, 2025]
Article 4 (Education for Chief Disaster Managers) ① A Chief Disaster Manager shall receive education including the matters set forth in each of the following subparagraphs within six months from the date of appointment as Chief Disaster Manager, and shall thereafter receive refresher education at least once every two years. <Amended Nov. 19, 2014; Jul. 26, 2017; Feb. 14, 2025>
1. General Disaster Management
2. Key Contents of the Act and Subordinate Regulations
3. Matters concerning the establishment of disaster prevention and damage mitigation plans
4. Matters concerning education and training regarding disasters, terrorism, etc. conducted for relevant persons, regular employees, and residents
5. Matters concerning the installation and operation of the Integrated Disaster Control Room
6. Matters concerning the establishment of an integrated disaster management system
7. Matters concerning the installation and operation of evacuation safety zones
8. Matters concerning the management, etc. of hazardous and dangerous substances
9. Other matters deemed necessary by the Commissioner of the National Fire Agency
② The education under Paragraph 1 shall be conducted by the Commissioner of the National Fire Agency or by an institution designated by the Commissioner . <Amended Nov. 19, 2014; Jul. 26, 2017>
③ The Commissioner of the National Fire Agency shall determine and publicly announce the necessary detailed matters concerning the schedule, content, and methods, etc., of the education pursuant to Paragraph 1. In this case, the Commissioner shall notify the managing entity of the super high-rise building, etc. of the details thereof (including the contents of the public announcement that are amended). <Amended Nov. 19, 2014; Jul. 26, 2017>
Article 4-2 Deleted <February 14, 2025>
Article 5 (Implementation of Integrated Safety Inspection, etc.) ① If the managing entity of a super high-rise building, etc.wishes to request an integrated safety inspection pursuant to Article 13, Paragraph 1 of the Act, it shall submit the Application for Integrated Safety Inspection of Super High-Rise and Underground-Connected Complex Buildings (Form No. 4) to the Mayor, County Head, or District Head at least 30 days prior to the desired date of the integrated safety inspection. <Amended Feb. 14, 2025>
② The Governor of a City or Province or the Mayor, County Head, or District Head who receives an application pursuant to Paragraph 1 shall consult with relevant agencies regarding the timing, etc., of the integrated safety inspection and notify the applicant of whether or not the integrated safety inspection will be conducted within 14 days from the date of receipt of the application. <Amended Feb. 14, 2025>
③ Any relevant agency that has received a request for consultation regarding integrated safety inspections from a City/Provincial Governor or a Mayor/County Head/District Head pursuant to Paragraph 2 shall submit the reasons to the City/Provincial Governor or the Mayor/County Head/District Head if it is unable to comply with the integrated safety inspection. <Amended Feb. 14, 2025>
Article 6 (Education and Training, etc.) ① The managing entity of a super high-rise building, etc. shall provide education and training to persons with interest, permanent employees, and residents in accordance with the classifications in each of the following subparagraphs pursuant to Article 14, Paragraph 1 of the Act.
1. Education and training for related parties and regular employees
a. Matters concerning the reporting, notification, and dissemination of disaster occurrence situations
B. Matters concerning the guidance of evacuation for tenants, users, residents, etc. (including persons with disabilities and the elderly)
C. Matters concerning on-site control and disaster response and recovery
D. Matters concerning duties in the event of a disaster, response and action guidelines for each type of disaster
E. Matters concerning the prevention and mitigation of secondary damage
F. Matters concerning the handover of the situation regarding dispatch to external agencies
G. Matters concerning terrorism prevention and response activities
2. Education and training for residents, etc.
a. Matters concerning the location of evacuation safety zones
B. Matters concerning evacuation procedures, etc. to the evacuation floor (referring to a floor with an exit leading directly to the ground and an evacuation safety zone; hereinafter the same applies).
C. Measures for damage mitigation
D. Matters concerning terrorism prevention and response activities (applicable only to tenants)
② The managing entity of a super high-rise building, etc., shall conduct education and training pursuant to Paragraph 1 at least once a year.
③ The managing entity of a super high-rise building, etc. shall formulate an education and training plan for the following year (hereinafter referred to as the “Education and Training Plan for Permanent Employees, etc.”) with the types, content, timing, frequency, and subjects of participation of the education and training pursuant to Paragraph 1 as its main contents, and submit it to the Mayor of a Special Self-Governing City, the Governor of a Special Self-Governing Province (excluding the Governor of a Special Self-Governing Province where there are local government entities such as Cities or Counties within its jurisdiction; the same shall apply in Paragraphs 6 and 7 below) or the Mayor, County Head, or District Head by December 15 of each year; and the Mayor, County Head, or District Head shall submit the Education and Training Plan for Permanent Employees, etc. to the Mayor of a Special City, the Mayor of a Consolidated Special City, the Mayor of a Metropolitan City, the Governor of a Province, or the Governor of a Special Self-Governing Province by December 30 of the same year. <Amended Feb. 14, 2025; July 1, 2026>
④ The Mayor or Provincial Governor shall submit the education and training plan for permanent employees, etc. received pursuant to Paragraph 3 to the Commissioner of the National Fire Agency by January 10 of the following year. <Newly added Feb. 14, 2025>
⑤ If the education and training plan for permanent employees, etc., includes training on firefighting, evacuation, etc., pursuant to the latter part of Article 14, Paragraph 1 of the Act , and education necessary for fire safety management, the managing entity of a super high-rise building, etc., shall consult with the head of the competent fire station regarding the content, timing, method, and subjects, etc., of the education and training at least 14 days prior to the scheduled date of the education and training. <Amended Feb. 14, 2025>
⑥ When the managing entity of a super high-rise building, etc. has conducted the education and training pursuant to Paragraph 1, it shall submit the Report on the Results of the Education and Training on Disasters and Terrorism, etc., in the form of Annex 4-2 , to the Mayor of a Special Self-Governing City, the Governor of a Special Self-Governing Province, or the Mayor, County Head, or District Head within 10 days from the date of the education and training, and shall retain it for one year. <Amended June 1, 2015; Feb. 14, 2025>
⑦ The Mayor of a Special Self-Governing City, the Governor of a Special Self-Governing Province, or the Mayor, County Head, or District Head shall notify the head of the competent fire station within 10 days from the date of receiving the report on the results of education and training regarding disasters and terrorism, etc., from the managing entity pursuant to Paragraph 6. <Amended June 1, 2015; Feb. 14, 2025>
⑧ The Commissioner of the National Fire Agency or the Mayor or Provincial Governor may provide necessary support to the managing entity of a super high-rise building, etc., for conducting education and training pursuant to Paragraph 1. <Amended Nov. 19, 2014; Jul. 26, 2017; Feb. 14, 2025>
⑨ The managing entity of super high-rise buildings, etc., shall provide the equipment and teaching materials, etc. necessary for the education and training under Paragraph 1. <Amended Feb. 14, 2025>
Article 7 (Standards for Installation of Integrated Disaster Prevention Rooms) ① The managing entity of a super high-rise building, etc., shall install and operate an integrated disaster prevention room that meets the standards of each of the following subparagraphs in accordance with Article 16, Paragraph 1 of the Act . <Amended Oct. 6, 2016>
1. Number of comprehensive disaster control rooms: 1. However, the managing entity of a super high-rise building, etc. with 100 stories or more [excluding multi-unit housing pursuant to Article 2, Paragraph 2, Subparagraph 2 of the Building Act (excluding cases where facilities other than housing and housing are constructed as the same building under a building permit pursuant to Article 11 of the same Act; hereinafter referred to as “multi-unit housing”)] shall install an additional comprehensive disaster control room or establish a supplementary comprehensive disaster management system in another comprehensive disaster control room within the relevant area in preparation for the event that the comprehensive disaster control room loses its function, so that disaster management operations are not interrupted.
2. Location of the Integrated Disaster Control Room
a. 1st floor or evacuation floor. However, in the case of a super high-rise building, etc., where a special evacuation staircase pursuant to Article 35 of the Enforcement Decree of the Building Act (hereinafter referred to as “special evacuation staircase”) is installed and a general disaster prevention room is to be installed within 5 meters of the entrance to the special evacuation staircase, it may be installed on the 2nd floor or basement 1st floor, and in the case of a multi-unit dwelling, it may be installed within the management office.
B. Places with easy access to emergency elevators, evacuation elevators, and special evacuation staircases
C. A place capable of serving as a base for disaster information collection and provision, and for disaster prevention activities
D. Places easily accessible to the fire brigade
E. Places with a low risk of damage due to fire, flooding, etc.
3. Structure and Area of the Integrated Disaster Control Room
a. It shall be installed as a fire compartment from other parts. However, for monitoring other control rooms, etc., a built-in window of less than 4 square meters made of wired glass with a thickness of 7 millimeters or more (including laminated glass with a thickness of 16.3 millimeters or more or double-pane glass with a thickness of 28 millimeters or more) may be installed.
B. Install a fire-compartmented annex room and a comprehensive disaster prevention control room for the standby and rest of personnel pursuant to Paragraph 2.
c. The area shall be 20 square meters or more.
D. Installation of facilities and equipment necessary for disaster and safety management, crime prevention and security, and terrorism prevention shall be carried out in such a manner that there is no hindrance to the disaster and safety management activities of personnel or the command activities of firefighters in the event of a disaster.
E. Entrance doors shall be equipped with access restriction and control devices.
4. Equipment, etc. of the Integrated Disaster Control Room
a. Lighting facilities (including backup power) and water supply and drainage facilities
B. Equipment for automatically or manually switching the supply of commercial power and backup power
C. Supply and exhaust facilities and cooling and heating facilities
D. Power supply status verification system
E. Monitoring and control system for air conditioning, heating and cooling, fire fighting, and elevator facilities
B. Data Storage System
d. Seismometers and wind direction and speed meters (limited to super high-rise buildings)
Ah. Fire extinguishing equipment storage cabinet and uninterruptible power supply
Z. Closed-circuit television (CCTV) for evacuation safety zones, evacuation elevator landings, and surveillance of terrorism, etc., and for crime prevention and security.
② The managing entity of a super high-rise building, etc., shall ensure that at least three personnel necessary for disaster and safety management are stationed in the comprehensive disaster control room.
③ The managing entity of super high-rise buildings, etc. shall frequently inspect the facilities and equipment of the comprehensive disaster control room to ensure that the functions of the comprehensive disaster control room always operate normally, and shall keep records of the results.
Article 8 (Facilities, etc. in Evacuation Safety Zones) In Article 14, Paragraph 4 of the Enforcement Decree, the term “facilities, etc. prescribed by the Ordinance of the Ministry of the Interior and Safety” refers to the equipment set forth in each of the following subparagraphs. <Amended Mar. 23, 2013; Nov. 19, 2014; Jul. 26, 2017; Jul. 13, 2021; Feb. 14, 2025>
1. Emergency equipment capable of performing cardiopulmonary resuscitation, such as automated external defibrillators (AEDs).
2. Gas masks in quantities according to the classification of each of the following items
a. Evacuation safety zones installed in super high-rise buildings: At least one-tenth of the number of occupants on the floor above the evacuation safety zone (referring to the number of occupants calculated in accordance with Annex 1-2 of the "Rules on Standards for Evacuation, Fire Protection, and Structures of Buildings")
B. Evacuation safety zones installed in underground-connected complex buildings: At least one-tenth of the occupancy capacity of the floor where the evacuation safety zone is installed ( referring to the occupancy capacity calculated in accordance with the remarks in Annex 2 of the Enforcement Decree).
Article 9 (Management of Hazardous and Dangerous Substances, etc.) ① When hazardous and dangerous substances are removed from or brought into a super high-rise building, etc., the managing entity of such building, etc.shall record and manage the matters of each of the following subparagraphs in the hazardous and dangerous substances management ledger in the form of Annex 5 .
1. Purpose of Export/Import
2. Type, quantity, use, and place of purchase of hazardous and dangerous substances
3. Carriers and managers of hazardous and dangerous substances
4. Types of Vehicles Transporting Hazardous and Dangerous Substances
② The managing entity of super high-rise buildings, etc., shall establish and operate a database regarding information on the export and import of hazardous and dangerous substances pursuant to Paragraph 1.
③ The managing entity of super high-rise buildings, etc., shall install separate access roads and exits for vehicles transporting hazardous and dangerous substances or control entry and exit times for the efficient management of hazardous and dangerous substances.
Article 10 (Provision of Design Documents, etc.) In Article 20 of the Act , the term “design documents prescribed by the Ordinance of the Ministry of the Interior and Safety” refers to the design documents set forth in each of the following subparagraphs. <Amended Mar. 23, 2013; Nov. 19, 2014; Feb. 10, 2017; Jul. 26, 2017; Dec. 1, 2022>
1. Design documents in Annex 2 of the Enforcement Rules of the Building Act [excluding architectural plans and specifications]
2. Design documents under each item of Article 3, Paragraph 2, Subparagraph 2 of the Enforcement Rules of the Act on the Installation and Management of Firefighting Facilities
Article 10-2 (Order for Measures) ① When the Commissioner of the Fire Department, the Governor of a City or Province, or the Mayor, County Head, or District Head issues an order for measures pursuant to Article 20-2, Paragraph 1 of the Act, they shall do so in writing, specifying matters requiring supplementation, repair, or modification, the period for compliance with the order, etc.
② When the Commissioner of the Fire Department, the governor of a city or province, or the mayor, county head, or district head determines the period for compliance with an order pursuant to Paragraph 1, they shall determine it within the range of one year, taking into consideration the period for supplementation, repair, or modification.
③ A management entity that has received a measure order with a compliance period of 60 days or more pursuant to Paragraph 1 shall prepare an improvement plan and submit it to the Commissioner of the Fire Department, the Governor of a City or Province, or the Mayor, County Head, or District Head within 30 days from the date of receiving the order.
④ If a managing entity that has received a measure order pursuant to Paragraph 1 is unable to comply with the measure order within the compliance period due to natural disasters or other unavoidable circumstances, it may apply for an extension of the compliance period to the Commissioner of the Fire Department, the Governor of a City or Province, or the Mayor, County Head, or District Head by attaching documents proving the reason for the extension to the application for extension of the compliance period in Form No. 6 attached hereto, no later than 5 days before the end of the period.
⑤ The Commissioner of the Fire Department, the Governor of a City or Province, or the Mayor, County Head, or District Head who receives an application for an extension of the period for compliance with an order pursuant to Paragraph 4 shall decide whether to approve the extension and notify the managing entity of the result in accordance with Form No. 7 attached .
[This Article Newly Inserted Feb. 14, 2025]
Chapter 3 Disaster Response and Support
Article 11 (Establishment and Operation of Disaster Response and Support System) ① Governors of Cities and Provinces and Mayors, County Governors, and District Heads shall establish and operate a disaster response and support system that includes the contents of each of the following subparagraphs pursuant to Article 21, Paragraph 1 of the Act . <Amended Feb. 14, 2025>
1. Disaster Prevention and Damage Mitigation Measures for Super High-Rise Buildings, etc.
2. Emergency communication network system with the overall disaster manager and comprehensive disaster control center of super high-rise buildings, etc., fire departments, relevant agencies, and the initial response team pursuant to Article 22, Paragraph 1 of the Act (hereinafter referred to as the “initial response team”), etc.
3. Current Status of Locations of Evacuation Safety Zones and List of Equipment, etc.
4. Building register of super high-rise buildings, etc. and design documents under each subparagraph of Article 10
5. Floor Use, Occupancy, and Risk Factors of Super High-Rise Buildings, etc.
6. Status of Composition and Operation of the Initial Response Team
7. Establishment of a direct telephone line with fire departments for emergency rescue and fire suppression
8. Other matters deemed necessary by the Mayor, Governor, or District Head
② The Governor of a City or Province and the Mayor, County Governor, or District Head shall inspect the status of each subparagraph of Paragraph 1 at least once every six months and manage any changes thereto. <Amended Feb. 14, 2025>
③ The Commissioner of the National Fire Agency shall inspect the appropriateness, etc. of the disaster response and support system under Paragraph 1 at least once a year, and provide guidance to the management entities of super high-rise buildings, etc. and relevant agencies, etc. <Amended Nov. 19, 2014; Jul. 26, 2017>
Article 12 (Composition and Operation of Initial Response Team, etc.) ① The initial response team shall be composed of five or more persons with relevant knowledge residing in the relevant super high-rise building, etc. However, in the case of multi-unit housing, it may be composed of three or more persons with relevant knowledge.
② The initial response team shall perform the following roles.
1. Identifying the current status, including the location of the disaster, reporting it, and disseminating information to relevant areas.
2. Guiding the evacuation and escape of residents, tenants, etc.
3. Initial Disaster Response
4. Rescue and First Aid
5. Provision of disaster information to emergency rescue agencies
6. Other matters necessary for disaster prevention and damage mitigation
③ The overall disaster manager shall provide education and training to the initial response team, including the contents of each of the following subparagraphs, at least once a year. In this case, the education and training for the initial response team may be conducted together with the education and training pursuant to Article 6, Paragraph 1 .
1. How to identify the location of a disaster
2. Methods for reporting disasters and disseminating information to relevant areas, etc.
3. Initial Response and Physical Protection Methods
4. Evacuation guidance methods for residents and tenants on each floor
5. Emergency First Aid Methods
6. How to operate fire fighting and evacuation facilities
7. Method for blocking heat sources of equipment and appliances that use fire
8. Emergency First Aid Procedures for Dangerous Goods
9. Guiding the scene and providing information upon the arrival of the fire department, etc.
10. Safety Protection Methods
11. Other matters necessary for initial disaster response
④ The initial response team must be equipped with the necessary equipment for guiding residents, etc. to evacuate, rescue and emergency measures, and blocking heat sources such as fire-using facilities and equipment.
ADDENDA <Ministry of the Interior and Safety Decree No. 286, Mar. 9, 2012>
Article 1 (Enforcement Date) This Rule shall enter into force on March 9, 2012. However, Article 8, subparagraph 2, item (a) shall enter into force on March 17, 2012.
Article 2 (Special Provisions Concerning Installation Standards for Comprehensive Disaster Control Rooms in Existing High-Rise Buildings, etc.) Notwithstanding Article 7, Paragraph 1, for high-rise buildings, etc. that have received approval for use or inspection for use, etc., or are in the process of applying for approval for use or inspection for use, etc., at the time of enforcement of this Rule, if facilities, etc., pursuant to Subparagraph 4 of Paragraph 1 of the same Article are provided in a place used as a comprehensive disaster control room, it shall be deemed to have been installed in accordance with the installation standards for comprehensive disaster control rooms pursuant to the same Paragraph.
Article 3 (Transitional Measures Concerning the Designation of General Disaster Managers for Existing High-Rise Buildings, etc.) Notwithstanding Article 3, Paragraph 1, for existing high-rise buildings, etc. that have received approval for use or inspection of use at the time of enforcement of this Rule, the managing entity of high-rise buildings, etc. shall designate a general disaster manager within 30 days from the date of enforcement of this Rule.
ADDENDA <Ministry of Security and Public Administration Decree No. 3, Mar. 23, 2013> (Enforcement Rule for the Organization of the National Fire Agency and its Affiliated Agencies)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation.
Article 2 omitted
Article 3 (Amendment of Other Laws) ① through ⑪ Omitted
12 The Enforcement Rules of the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings are partially amended as follows.
In the part other than the subparagraphs of Article 2, Paragraph 1, the part other than the subparagraphs of Article 8, and the part other than the subparagraphs of Article 10, “Ordinance of the Ministry of Public Administration and Security” shall be changed to “Ordinance of the Ministry of Safety and Security”.
ADDENDA <Prime Minister's Decree No. 1105, Nov. 19, 2014> (Enforcement Rule for the Organization of the Ministry of Public Safety and Security and Its Affiliated Agencies)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation. However, among the Ministerial Ordinances amended pursuant to Article 6 of the Addenda, the parts amending Prime Ministerial Ordinances or Ministerial Ordinances that were promulgated prior to the enforcement of this Rule but whose effective date has not yet arrived shall enter into force on the respective effective dates of the said Prime Ministerial Ordinances or Ministerial Ordinances.
Articles 2 through 5 omitted
Article 6 (Amendment of Other Laws) ① through ㉛ Omitted
㉜ The Enforcement Rules of the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings are partially amended as follows.
In the part other than the subparagraphs of Article 2, Paragraph 1, the part other than the subparagraphs of Article 8, and the part other than the subparagraphs of Article 10, “Ordinance of the Ministry of Public Administration and Security” shall each be changed to “Ordinance of the Prime Minister.”
In Article 4, Paragraph 1, Subparagraph 9; Paragraph 2 of the same article; the first and second parts of Paragraph 3 of the same article; Paragraphs 3 and 7 of Article 6; and Paragraph 3 of Article 11, the term “Commissioner of the National Fire Agency” shall be replaced with “Minister of Public Safety and Security”.
omitted from ㉝ to ㊶
ADDENDA <Prime Minister's Decree No. 1166, June 1, 2015>
This rule shall take effect from the date of its promulgation.
ADDENDA <Prime Minister's Decree No. 1324, Oct. 6, 2016>
This rule shall enter into force on the date of its promulgation. However, the amended provisions of Article 4-2 shall enter into force on January 28, 2017.
ADDENDA <Prime Minister's Decree No. 1369, Feb. 10, 2017> (Enforcement Rule of the Act on Prevention of Fire, Installation and Maintenance of Firefighting Facilities and Safety Management)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation.
Articles 2 and 3 omitted
Article 4 (Amendment of Other Laws) The Enforcement Rules of the Special Act on Disaster Management of Super High-Rise and Underground-Connected Complex Buildings are partially amended as follows:
In Article 10, subparagraph 2, “「Enforcement Rules of the Act on Installation, Maintenance and Safety Management of Firefighting Facilities」” shall be changed to “「Enforcement Rules of the Act on Fire Prevention, Installation, Maintenance and Safety Management of Firefighting Facilities」”.
ADDENDA <Ministry of the Interior and Safety Decree No. 2, July 26, 2017> (Enforcement Rule for the Organization of the National Fire Agency and its Affiliated Agencies)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation. However, among the Decrees of the Prime Minister amended pursuant to Article 3 of the Addenda, the parts amending Decrees of the Prime Minister that were promulgated prior to the enforcement of this Decree but whose enforcement date has not yet arrived shall enter into force on the respective enforcement dates of those Decrees.
Article 2 omitted
Article 3 (Amendment of Other Laws) ① through ⑮ Omitted
16. The Enforcement Rules of the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings are partially amended as follows.
In the part other than the subparagraphs of Article 2, Paragraph 1, the part other than the subparagraphs of Article 8, and the part other than the subparagraphs of Article 10, “Prime Minister’s Decree” shall be changed to “Ministry of the Interior and Safety Decree”.
In Article 4, Paragraph 1, Subparagraph 9; Paragraph 2 of the same article; the first and second parts of Paragraph 3 of the same article; Article 6, Paragraphs 3 and 7; and Article 11, Paragraph 3, “Minister of Public Safety and Security” shall be changed to “Commissioner of the Fire Department”.
11 omitted
ADDENDA <Ministry of the Interior and Safety Decree No. 268, July 13, 2021> (Ministry of the Interior and Safety Decree on the Partial Amendment of 13 Laws for the Reorganization of Difficult Legal Terms)
This rule shall take effect from the date of its promulgation.
ADDENDA <Ministry of the Interior and Safety Decree No. 360, Dec. 1, 2022> (Enforcement Rule of the Act on Installation and Management of Firefighting Facilities)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation. <Proviso Omitted>
Articles 2 through 5 omitted
Article 6 (Amendment of Other Laws) ① through ⑤ Omitted
⑥ The Enforcement Rules of the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings are partially amended as follows.
In Article 10, subparagraph 2, “Article 4, paragraph 2, subparagraph 2 of the Enforcement Rules of the Act on Fire Prevention, Installation and Maintenance of Firefighting Facilities and Safety Management” shall be changed to “Article 3, paragraph 2, subparagraph 2 of the Enforcement Rules of the Act on Installation and Management of Firefighting Facilities”.
Article 7 omitted
ADDENDA <Ministry of the Interior and Safety Decree No. 361, Dec. 1, 2022> (Enforcement Rule of the Act on the Prevention of Fire and Safety Management)
Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation.
Articles 2 through 7 omitted
Article 8 (Amendment of Other Laws) ① through ⑧ Omitted
⑨ The Enforcement Rules of the Special Act on Disaster Management of High-Rise and Underground-Connected Complex Buildings are partially amended as follows.
In Article 2, Paragraph 2, Subparagraph 2, “Article 23, Paragraph 1 of the Enforcement Decree of the Act on Installation, Maintenance and Safety Management of Firefighting Facilities” shall be changed to “Subparagraph 1 of Annex 4 of the Enforcement Decree of the Act on Prevention of Fire and Safety Management of Firefighting Facilities”.
In Article 3, Paragraph 3, “Article 23, Paragraph 1, Subparagraph 1 (excluding fire facility managers), Subparagraphs 2 and 3 of the Enforcement Decree of the Act on Installation, Maintenance and Safety Management of Firefighting Facilities” shall be changed to “Subparagraph 1, Item B of Annex 4 of the Enforcement Decree of the Act on Prevention of Fire and Safety Management (excluding fire facility managers), Subparagraphs 2 and 3)”.
Article 9 omitted
ADDENDA <Ministry of the Interior and Safety Decree No. 547, Feb. 14, 2025>
This rule will take effect on February 14, 2025.
ADDENDA <Ministry of the Interior and Safety Decree No. 628, July 1, 2026> (Ministry of the Interior and Safety Decree on the Partial Amendment of 22 Laws under the Jurisdiction of the National Fire Agency Pursuant to the Establishment of Integrated Special Cities)
This rule shall take effect on July 1, 2026.
[Attachment Form No. 1] Application for Preliminary Disaster Impact Assessment
[Attachment Form No. 1-2] Notification of Preliminary Disaster Impact Assessment (Re-assessment) Results
[Attachment Form No. 1-3] Application for Re-evaluation of Preliminary Disaster Impact Assessment
[Attachment Form No. 1-4] Application for Registration of Appointment of General Disaster Manager
[Attachment Form No. 2] Certificate of Registration for Appointment of Chief Disaster Manager
[Attachment Form No. 3] Register of Appointed Chief Disaster Managers
[Attachment Form No. 4] Application for Integrated Safety Inspection of Super High-Rise and Underground-Connected Complex Buildings
[Attachment Form No. 4-2] Results of Education and Training on Disasters and Terrorism, etc.
[Attachment Form No. 5] Hazardous and Dangerous Substances Management Register
[Attachment Form No. 6] Application for Extension of Compliance Period for Action Order
[Attachment Form No. 7] Notification of Result of Extension of Compliance Period for Action Order