Rules on Building Facility Standards, etc.

289011 · 2026-08-24

Article 1 (Purpose) The purpose of this Rule is to prescribe matters necessary for technical standards, etc. regarding the installation of building facilities pursuant to Articles 49, 62, 64, 67, and 68 of the Building Act and Articles 87, 89, 90, and 91-3 of the Enforcement Decree of the same Act. <Revised 1996.2.9, 1999.5.11, 2006.2.13, 2008.7.10, 2009.12.31, 2010.11.5, 2011.11.30, 2013.2.22, 2013.9.2, 2015.7.9, 2020.4.9> Article 2 (Buildings Requiring Cooperation from Related Professional Engineers) In the part other than each subparagraph of Article 91-3, Paragraph 2 of the Enforcement Decree of the Building Act (hereinafter referred to as the "Decree"), the term "buildings prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" refers to the buildings listed in each of the following subparagraphs. <Amended May 11, 1999; Feb. 13, 2006; Mar. 14, 2008; Mar. 23, 2013; Sep. 2, 2013; Apr. 9, 2020> 1. A building used for a refrigeration/freezing facility, a constant temperature and humidity facility (referring to a facility equipped with special equipment to maintain constant temperature and humidity), or a special cleanroom facility (referring to a facility equipped with special equipment to remove bacteria or dust, etc.) where the total floor area used for such purpose is 500 square meters or more 2. Apartments and row houses pursuant to Subparagraphs (a) and (b) of Item 2 of Annex 1 of the Enforcement Decree 3. A building falling under any of the following subparagraphs, wherein the total floor area used for the relevant purpose is 500 square meters or more A. Bathhouses pursuant to Subparagraph 3, Item C of Annex 1 of the Enforcement Decree B. Water play facilities pursuant to Subparagraph A of Item 13 of Annex 1 of the Enforcement Decree (limited to cases where installed indoors) and swimming pools pursuant to Subparagraph C of the same item (limited to cases where installed indoors) 4. A building falling under any of the following subparagraphs, wherein the total floor area used for the relevant purpose is 2,000 square meters or more A. Dormitories pursuant to Subparagraph 2(d) of Annex 1 of the Enforcement Decree B. Medical facilities pursuant to Item 9 of Annex 1 of the Enforcement Decree C. Youth hostels pursuant to Item 12, Subparagraph C of Annex 1 of the Enforcement Decree D. Accommodation facilities pursuant to Item 15 of Annex 1 of the Enforcement Decree 5. A building falling under any of the following subparagraphs, wherein the total floor area used for the relevant purpose is 3,000 square meters or more A. Sales facilities pursuant to Item 7 of Annex 1 of the Enforcement Decree B. Research institute pursuant to Item 10, Subparagraph E of Annex 1 of the Enforcement Decree C. Business facilities pursuant to Item 14 of Annex 1 of the Enforcement Decree 6. A building falling under any of the following subparagraphs, wherein the total floor area used for the relevant purpose is 10,000 square meters or more A. Cultural and assembly facilities corresponding to Items A through D of Subparagraph 5 of Annex 1 of the Enforcement Decree B. Religious facilities pursuant to Item 6 of Annex 1 of the Enforcement Decree C. Educational and research facilities pursuant to Item 10 of Annex 1 of the Enforcement Decree (excluding research institutes) D. Funeral homes pursuant to Item 28 of Annex 1 of the Enforcement Decree [Wholly Revised 1996.2.9] Article 3 (Matters of Cooperation by Related Expert Technicians) ① In cases where electrical, elevator, lightning rod, gas, water supply, drainage, ventilation, heating, fire extinguishing, smoke exhaust, and waste disposal facilities are installed in a building pursuant to Article 91-3, Paragraph 2 of the Enforcement Decree, an architect shall oversee the design of the said building, and a Professional Engineer in Architectural Electrical Equipment, Professional Engineer in Power Transmission and Distribution, Professional Engineer in Architectural Mechanical Equipment, Professional Engineer in Air Conditioning and Refrigeration, or Professional Engineer in Gas (hereinafter referred to as "Professional Engineer") registered under the Professional Engineers Act shall design the said building facilities in cooperation with the architect. <Amended 2008.7.10, 2010.11.5, 2017.5.2> ② In cases where building facilities have been installed in a building pursuant to Article 91-3, Paragraph 2 of the Enforcement Decree, a Professional Engineer in the relevant field shall verify the installation status and submit a Confirmation of Building Facilities Installation in the form of Annex 1 to the building owner and the construction supervisor. <Amended 2008.7.10, 2010.11.5> [Wholly Revised 1996.2.9] Article 4 [Former Article 4 moved to Article 12 <2015.7.9>] Article 5 (Installation Standards for Passenger Elevators) Pursuant to Article 64, Paragraph 1 of the Building Act (hereinafter referred to as the "Act"), the installation standards for passenger elevators installed in buildings shall be as set forth in Attached Table 1-2. However, in the case of adding one floor to a building where a passenger elevator is already installed, the elevator shaft of the passenger elevator may not be installed by extending it. <Amended Jan. 17, 2001; Feb. 13, 2006; Jul. 10, 2008; Jul. 9, 2015> [Wholly Revised 1999.5.11] Article 6 (Structure of Elevators) The structure of elevators, escalators, and emergency elevators installed in buildings pursuant to Article 64 of the Act shall be in accordance with the provisions of the Elevator Safety Management Act. <Amended Feb. 13, 2006; Jul. 10, 2008; Nov. 5, 2010; Aug. 7, 2024> [Wholly Revised 1996.2.9] Delete Article 7 <1996.2.9> Article 8 Deleted <1996.2.9> Article 9 (Buildings Where Emergency Elevators May Not Be Installed) The term "buildings prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" in the proviso to Article 64, Paragraph 2 of the Act refers to the buildings listed in each of the following subparagraphs. <Amended Feb. 9, 1996; May 11, 1999; May 12, 2006; March 14, 2008; July 10, 2008; March 23, 2013; December 4, 2017> 1. A building with a height exceeding 31 meters where each floor is used for purposes other than living rooms 2. Buildings with a height exceeding 31 meters where the total floor area of ​​each story is 500 square meters or less 3. A building with a height exceeding 31 meters and four or fewer stories, partitioned into fire compartments (referring to fire compartments pursuant to the main text of Article 46, Paragraph 1 of the Enforcement Decree; hereinafter the same applies) for every 200 square meters or less of the total floor area of ​​each said story (500 square meters or less if the finishing of the parts of walls and ceilings facing the interior is made of non-combustible materials). Article 10 (Structure of Landings and Shafts of Emergency Elevators) The structure of landings and shafts of emergency elevators pursuant to Article 64, Paragraph 2 of the Act shall comply with the standards set forth in each of the following subparagraphs. <Amended Feb. 9, 1996; May 11, 1999; Aug. 31, 2002; Feb. 13, 2006; July 10, 2008; Aug. 7, 2024> 1. Deleted <1996.2.9> 2. Structure of Emergency Elevator Landing A. The part of the elevator landing, excluding windows, doorways, and other openings, shall be partitioned from other parts of the building by fire-resistant floors and walls. However, in the case of multi-unit dwellings, if the part shared between the elevator landing and the vestibule of the special escape staircase (referring to the special escape staircase pursuant to Article 9 of the "Rules on Standards for Escape and Fire Protection Structures of Buildings," hereinafter the same) is partitioned separately from the stairwell of the special escape staircase, the elevator landing may be shared with the vestibule of the special escape staircase. B. Elevator landings shall be connected to the interior of each floor, and 60-minute+ fire doors or 60-minute fire doors shall be installed at their entrances (excluding entrances to elevator shafts). However, 60-minute+ fire doors or 60-minute fire doors may not be installed on evacuation floors. c. Install windows that can be opened toward a balcony or the outside, or smoke exhaust facilities in accordance with the provisions of Article 14, Paragraph 2. D. Finishing materials (including substrates for finishing) for parts of walls and ceilings that face the interior shall be made of non-combustible materials. E. There shall be windows that allow natural light, or lighting facilities powered by a backup power source shall be installed. F. The floor area of ​​the landing shall be at least 6 square meters per emergency elevator. However, this shall not apply if the landing is installed outdoors. d. The distance from the entrance of the elevator landing on the evacuation floor (or the entrance of the elevator shaft in cases where there is no elevator landing) to a road or open space (referring to a park, plaza, or other similar place that does not hinder access to the site for evacuation and firefighting) shall be 30 meters or less. A. Place a sign indicating that the elevator is an emergency elevator in a conspicuous place near the platform entrance. 3. Structure of the Emergency Elevator Shaft a. The elevator shaft shall be partitioned from other parts of the building by a fire-resistant structure. B. The elevator shafts extending from each floor to the evacuation floor shall be installed as a single connected structure. [Title Revised 1996.2.9] Article 11 (Standards for Ventilation Equipment, etc., for Multi-unit Housing and Multi-use Facilities) ① Houses or buildings falling under any of the following subparagraphs that are newly constructed or remodeled pursuant to the provisions of Article 87, Paragraph 2 of the Enforcement Decree (hereinafter referred to as "newly constructed multi-unit housing, etc.") shall be equipped with natural ventilation facilities or mechanical ventilation facilities to ensure ventilation of at least 0.5 times per hour. <Amended Sep. 2, 2013; Dec. 27, 2013; Apr. 9, 2020> 1. Multi-unit housing with 30 or more households 2. A building where housing is constructed as part of the same structure as non-residential facilities, and the housing consists of 30 or more units ② In cases where natural ventilation facilities are installed in newly constructed multi-unit dwellings, etc., deliberation by the Local Architectural Committee pursuant to Article 4 of the Act shall be obtained regarding whether the natural ventilation facilities satisfy the ventilation frequency requirements under Paragraph 1. However, this shall not apply in cases where natural ventilation facilities that have undergone performance testing in accordance with the Ventilation Performance Test Method for Natural Ventilation Facilities (KSF 2921) of the Korean Industrial Standard under the Industrial Standardization Act (hereinafter referred to as "Korean Industrial Standard") are installed in newly constructed multi-unit dwellings, etc., for an installation length exceeding that of the natural ventilation facilities specified in Annex 1-3. <Amended 2009.12.31, 2010.11.5, 2015.7.9> ③ When installing natural ventilation facilities or mechanical ventilation facilities in newly constructed multi-unit dwellings, etc., they shall comply with the standards of Annex 1-4 or Annex 1-5. <Amended Jul. 10, 2008, Dec. 31, 2009> ④ The Mayor of a Special City, Metropolitan City, Special Self-Governing City, or Special Self-Governing Province, or the Mayor, County Head, or District Head (referring to the District Head of an autonomous district; hereinafter referred to as the "Licensing Authority") may recommend the installation of natural ventilation facilities or mechanical ventilation facilities to ensure ventilation of at least 0.5 times per hour for multi-unit dwellings with fewer than 30 households, buildings where housing is constructed within the same structure as non-housing facilities and the housing consists of fewer than 30 households, and single-family dwellings. <Newly Added Apr. 9, 2020> ⑤ In the case of constructing a new multi-use facility, the multi-use facilities requiring the installation of mechanical ventilation equipment and the required ventilation volume for each facility are as set forth in Attached Table 1-6, and the structure and installation of the mechanical ventilation equipment to be installed must comply with the standards of each of the following subparagraphs. <Amended 2008.7.10, 2009.12.31, 2010.11.5, 2020.4.9> 1. The capacity standards for mechanical ventilation systems in multi-use facilities shall, in principle, be calculated based on the ventilation volume per facility user. 2. Mechanical ventilation equipment shall ensure the distribution of air supplied to multi-use facilities is as even as possible to minimize variations in indoor airflow. 3. Blowers installed in air supply systems, air exhaust systems, or air intakes, exhausts, etc., shall not be structured in such a way that their blowing capacity is reduced by external airflow. 4. An air supply system supplying outside air or an air intake into which outside air is introduced shall be equipped with an air filter or dust collector, etc., that meets all of the requirements of each of the following subparagraphs a. The performance for removing or filtering particulate and gaseous pollutants shall be above a certain level. B. It shall have a structure that facilitates easy maintenance, such as cleaning and replacement of filtration devices, etc. c. In the case of air filters, the particle capture rate according to the Korean Industrial Standard (KS B 6141) shall be 60 percent or higher when measured by the counting method. 5. The air exhaust system and exhaust ports shall be installed in a location where the exhausted air does not directly enter the air supply system and air intake ports. 6. In determining the efficiency and performance, etc., of equipment, devices, apparatus, and products constituting mechanical ventilation systems, matters not specified in this Rule shall conform to the Korean Industrial Standards for the relevant items. [This Article Newly Established 2006.2.13] Article 11-2 (Safety Standards for Ventilation Openings) ① Pursuant to Article 87, Paragraph 2 of the Enforcement Decree, ventilation openings [referring to openings in a building structure for supply and exhaust air attached to the ventilation facilities of a building; hereinafter the same applies] shall be installed at a height of at least 2 meters from the floor to ensure the safety of pedestrians and building users. However, exceptions shall be made in any of the following cases: <Amended Aug. 27, 2021> 1. Cases where ventilation openings are installed in a structure that prevents people from stepping on them, such as by installing them on a wall. In this case, the exhaust ventilation opening must be installed so that the exhausted air does not come into direct contact with pedestrians and building users. 2. In cases where access is blocked using safety fences or landscaping, etc. ② All ventilation openings shall be equipped with fall prevention facilities, such as covers and cover ledges, having a strength equal to or greater than that prescribed and notified by the Minister of Land, Infrastructure and Transport. [This Article Newly Established 2015.7.9] Article 12 (Installation Standards for Ondol) ① In cases where ondol is installed in a building pursuant to Article 87, Paragraph 2 of the Enforcement Decree, it shall comply with the standards of Annex 1-7 in order to efficiently manage thermal energy structurally and prevent the risk of fire. <Amended July 9, 2015> ② A person installing an ondol in a building pursuant to Paragraph 1 shall submit a Confirmation of Ondol Installation in the form of Annex 2 to the construction supervisor after the completion of the installation. However, this shall not apply in cases where a Confirmation of Building Equipment Installation pursuant to Article 3, Paragraph 2 has been submitted, or where the construction supervisor has directly verified the installation of the ondol. <Amended 2010.11.5, 2015.7.9> [This Article Newly Established 2008.7.10] [Moved from Article 4 <2015.7.9>] Article 13 (Individual Heating Facilities, etc.) ① In cases where the heating facilities of multi-unit dwellings and officetels are installed using an individual heating system pursuant to the provisions of Article 87, Paragraph 2 of the Enforcement Decree, they shall comply with the standards of each of the following subparagraphs. <Amended Feb. 9, 1996; May 11, 1999; Jan. 17, 2001; Dec. 4, 2017> 1. The boiler shall be installed outside the living room, and the boundary wall between the boiler installation site and the living room shall be partitioned with a fire-resistant wall, excluding the entrance. 2. A ventilation window with an area of ​​at least 0.5 square meters shall be installed at the top of the boiler room, and air intake and exhaust vents with a diameter of at least 10 centimeters shall be installed at the top and bottom of the boiler room, respectively, so as to remain constantly open and exposed to the outside air. However, this shall not apply to electric boilers. 3. Delete<1999.5.11> 4. The doorway between the boiler room and the living room shall be designed so that boiler gas cannot enter the living room when the doorway is closed. 5. When installing an oil boiler, install the oil storage facility in a location other than the boiler room. 6. In the case of officetels, heating compartments shall be divided into fire compartments 7. The boiler flue shall be of a refractory structure and installed as a common flue. ② Notwithstanding the provisions of Paragraph 1, in cases where heating facilities using gas boilers are installed and gas is supplied via a centralized supply system, the standards prescribed by gas-related laws and regulations shall apply; however, in the case of officetels, heating compartments must be partitioned as fire compartments. <Newly added May 11, 1999, Aug. 7, 2024> ③ In the case of buildings equipped with individual boilers, the licensing authority may recommend the installation of carbon monoxide alarms in accordance with the standards prescribed and notified by the Commissioner of the National Fire Agency. <Newly added 2020.4.9> [Title Revised 2020.4.9] Article 14 (Smoke Exhaust Facilities) ① In buildings required to install smoke exhaust facilities pursuant to Article 49, Paragraph 2 of the Act, smoke exhaust facilities shall be installed in accordance with the standards of each of the following subparagraphs. However, this shall not apply to evacuation floors. <Amended Feb. 9, 1996; May 11, 1999; Aug. 31, 2002; Dec. 31, 2009; Nov. 5, 2010; Dec. 4, 2017; Apr. 9, 2020> 1. In cases where a building is divided into fire compartments pursuant to Article 46, Paragraph 1 of the Enforcement Decree, at least one smoke vent window shall be installed in each compartment, provided that the vertical distance between the upper edge of the smoke vent window and the ceiling or suspended ceiling is within 0.9 meters. However, if the suspended ceiling height is 3 meters or more from the floor, the smoke vent window shall be installed so that its lower edge is positioned at a height of 2.1 meters or more from the floor. 2. The effective area of ​​smoke exhaust windows shall be at least 1 square meter, calculated according to the calculation standards in Attached Table 2, and the sum of such areas shall be at least 1/100 of the floor area of ​​the building (in cases where fire compartments are installed pursuant to the provisions of Article 46, Paragraph 1 or 3 of the Enforcement Decree, this refers to the floor area of ​​the partitioned portion). In this case, when calculating the floor area, the area of ​​a room where ventilation windows are installed covering at least 1/20 of the room floor area shall not be included. 3. The exhaust vent shall be constructed to open automatically upon detection by a smoke detector or heat detector, but shall also be designed to be open and closed manually. 4. The ventilation shaft shall be able to be opened by a backup power source 5. In the case of installing mechanical smoke exhaust facilities, notwithstanding the provisions of Subparagraphs 1 through 4, they shall comply with the provisions of fire-related laws and regulations. ② The structure of smoke exhaust facilities installed in special evacuation staircases and elevator lobbies of emergency elevators pursuant to the provisions of Article 90, Paragraph 3 of the Enforcement Decree shall comply with the standards of each of the following subparagraphs. <Amended Feb. 9, 1996, May 11, 1999> 1. The smoke exhaust vents and exhaust ducts shall be made of non-combustible materials and shall be sized to allow for smooth smoke exhaust in the event of a fire, and shall be connected to an outdoor chimney or a chimney not used under normal circumstances. 2. Manual or automatic opening devices installed in exhaust vents (referring to those based on heat detectors or smoke detectors) shall be designed to be openable and closeable by hand. 3. The smoke vent shall be kept closed under normal circumstances, and when opened, ensure that it does not close due to airflow caused by the smoke. 4. If the smoke exhaust duct is not exposed to the outside air, install a smoke exhaust fan. 5. The smoke exhaust system shall operate automatically upon the opening of the exhaust vent and shall have sufficient air discharge or pressurization capabilities 6. Install a backup power supply for the smoke exhauster 7. In cases where the air intake method is a pressurized air supply method or a supply and exhaust method, notwithstanding the provisions of Subparagraphs 1 through 6, it shall comply with the provisions of fire safety-related laws and regulations. Article 15 Deleted <1996.2.9> Article 16 Deleted <1999.5.11> Article 17 (Piping Facilities) ① The installation and structure of piping facilities used for purposes such as water supply and drainage installed in buildings shall comply with the standards of each of the following subparagraphs. 1. When burying piping in concrete, take corrosion prevention measures for materials susceptible to corrosion. 2. When piping penetrates the main parts of a building, ensure that the structural strength of the building is not compromised. 3. Piping facilities other than those necessary for the operation of the elevator shall not be installed inside the elevator shaft. 4. Install facilities capable of preventing risks such as explosions in pressure tanks and hot water supply systems. ② Piping facilities used for drainage pursuant to the provisions of Paragraph 1 shall comply with the standards of each of the following subparagraphs in addition to the standards of each subparagraph of Paragraph 1. <Amended Feb. 9, 1996> 1. Depending on the volume and quality of the rainwater or wastewater being discharged, provide an appropriate capacity and slope, or use suitable materials. 2. Ensure that piping facilities do not compromise hygiene by installing drain traps and vent pipes, etc. 3. Use water-resistant materials for parts of the piping system that come into contact with wastewater 4. In places such as basements where natural drainage via public sewers is not possible, install forced drainage facilities suitable for the drainage capacity. 5. Separate the rainwater and sewage pipes during piping. 6. When piping is embedded in a concrete structure or penetrates a concrete structure, measures such as pre-burying pipe covers in the structure shall be taken to prevent corrosion of the piping and facilitate repair and replacement. ③ Delete <1996.2.9> Article 17-2 (Water Barrier Facilities) ① Any person intending to construct a building in any of the areas falling under any of the following subparagraphs shall install facilities capable of preventing flooding of the building (hereinafter referred to as "water barrier facilities"), such as water barriers, at the entrances (including entrances to parking lots; hereinafter the same applies in this Article) of the basement and first floor of the building to prevent the building from being flooded by the inflow of rainwater, etc. However, if the entrances to the basement and first floor of the building are installed at a height equal to or greater than the expected flood height determined and notified by the Minister of Land, Infrastructure and Transport, the water barrier facilities shall be deemed to have been installed. <Amended 2020.4.9, 2021.8.27, 2024.3.21> 1. Disaster prevention district pursuant to Article 37, Paragraph 1, Subparagraph 4 of the "Act on Planning and Utilization of National Land" 2. Areas notified by the Minister of the Interior and Safety pursuant to Article 15, Subparagraph 2, Item (e) of the Enforcement Decree of the Natural Disaster Countermeasures Act ② Water barrier facilities installed pursuant to Paragraph 1 shall comply with the standards of each of the following subparagraphs. <Amended Mar. 23, 2013, Aug. 27, 2021> 1. The structure shall not hinder the use of the building or evacuation. 2. It shall be installed in accordance with other standards prescribed and notified by the Minister of Land, Infrastructure and Transport. [This Article Newly Established 2012.4.30] [Title Revised 2021.8.27] Article 18 (Piping Facilities for Drinking Water) Pursuant to Article 87, Paragraph 2 of the Enforcement Decree, the installation and structure of piping facilities for drinking water installed in buildings shall comply with the standards set forth in each of the following subparagraphs. <Amended Feb. 9, 1996; May 11, 1999; Aug. 31, 2002; Feb. 13, 2006; Dec. 31, 2009; Aug. 27, 2021; Aug. 24, 2026> 1. Must comply with the standards of each subparagraph of Article 17, Paragraph 1 2. Piping systems for drinking water shall not be directly connected to piping systems for other purposes 3. Water supply pipes and water meters shall be installed in accordance with the standards prescribed in Annex 3-2 so as not to freeze and break. 4. In addition to the standards set forth in Subparagraph 3, if standards have been established by the ordinance of the relevant local government in accordance with local conditions to prevent water supply pipes and water meters from freezing and breaking, they shall be installed in compliance with said standards. 5. Water supply and storage tanks shall be constructed in a manner compliant with the storage tank installation standards set forth in Annex 3-2 of the Enforcement Rule of the Water Supply Act. 6. The diameter of drinking water supply pipes shall be at least the standard appropriate for the use and scale of the building. However, for residential buildings, piping shall be installed using pipes of a diameter conforming to the standards in Attached Table 3, based on the number of households or the total floor area supplied by the relevant piping. 7. Water supply pipes for drinking water shall comply with the sanitary safety standards pursuant to Article 24 and Annex 1-2 of the Enforcement Decree of the Water Supply Act, and water supply materials and products pursuant to Article 24-2 of the same Decree shall be used. [Title Revised 2021.8.27] Article 19 Deleted <1999.5.11> Article 20 (Lightning Protection Facilities) Pursuant to Article 87, Paragraph 2 of the Enforcement Decree, lightning protection facilities shall be installed in accordance with the standards of each of the following subparagraphs on buildings where there is a risk of lightning strikes, buildings 20 meters or more in height, or structures 20 meters or more in height as stipulated in Article 118, Paragraph 1 of the Enforcement Decree (including buildings where a structure stipulated in Article 118, Paragraph 1 of the Enforcement Decree is installed to have a total height of 20 meters or more). <Amended Nov. 5, 2010; Apr. 30, 2012; Aug. 27, 2021> 1. Lightning protection systems shall be in accordance with the lightning protection level grades prescribed by the Korean Industrial Standards. However, lightning protection systems installed in hazardous material storage and handling facilities shall be at least Lightning Protection System Level II as prescribed by the Korean Industrial Standards. 2. Stone supports shall be installed protruding at least 25 centimeters from the uppermost part of the building, and shall be of a structure capable of withstanding design loads pursuant to Article 9 of the "Rules on Structural Standards for Buildings, etc." 3. The materials of the lightning protection system shall have a minimum cross-sectional area of ​​at least 50 square millimeters for the lightning receiver, down conductor, and grounding electrode, based on unclad copper wire, or possess equivalent or superior performance. 4. When steel structures of steel frame buildings and reinforced concrete structures, etc., are used in place of the down conductor of a lightning protection system, electrical continuity shall be ensured. In this case, for electrical continuity to be deemed to exist, the electrical resistance between the uppermost part of the building's metal structure and the ground level must be 0.2 ohms or less. 5. To prevent lateral lightning strikes, lightning receivers shall be installed on the sides of buildings, etc., exceeding 60 meters in height, from a point 4/5 of the building's height from the ground up to the top; for buildings where the height of the top from ground level exceeds 150 meters, lightning receivers shall be installed on the sides from a point 120 meters up to the top. However, if the exterior walls of the building are finished with metal members, electrical continuity between the metal members in accordance with the latter part of Paragraph 4 is ensured, and the member is installed in accordance with the lightning protection system level grade and connected to a down conductor, the lateral lightning receiver shall be deemed to have been installed. 6. Grounding shall not use construction methods or chemical additives that may cause environmental pollution. 7. Metal piping and metal fixtures installed in buildings to supply water, hot water, heating, gas, etc. shall be electrically connected so that the electric potential is equalized. 8. In the case of integrated grounding work where the grounding system of electrical facilities shares the grounding electrodes of building lightning protection facilities and communication facilities, etc., a surge protection device compliant with Korean Industrial Standards shall be installed to protect electrical facilities, etc. from overvoltage caused by lightning strikes, etc. [referring to a device for protecting various facilities from surges (surge: refers to transient waveforms of current, voltage, etc.)]. 9. Other matters related to lightning protection facilities shall be installed in accordance with Korean Industrial Standards. [Wholly Revised 2006.2.13] Article 20-2 (Standards for Installation Space for Electrical Facilities) In cases where electricity is to be distributed to a building pursuant to Article 87, Paragraph 6 of the Enforcement Decree, space in accordance with Annex 3-3 must be secured. [This Article Newly Established 2010.11.5] Article 21 Deleted <2013.9.2> Article 22 Deleted <2013.2.22> Article 23 (Cooling Facilities, etc. of Buildings) ① Delete <1999.5.11> ② In cases where central cooling facilities are installed in buildings falling under subparagraphs 3 through 6 of Article 2, which are designated by the Minister of Climate, Energy and Environment in consultation with the Minister of Land, Infrastructure and Transport, the system shall be a thermal storage or gas-based central cooling system as determined by the Minister of Climate, Energy and Environment in consultation with the Minister of Land, Infrastructure and Transport. <Amended Feb. 9, 1996; May 11, 1999; Aug. 31, 2002; Mar. 14, 2008; Apr. 30, 2012; Mar. 23, 2013; Sep. 2, 2013; Oct. 31, 2025> ③ The installation of exhaust vents and exhaust devices for cooling and ventilation facilities installed in buildings in commercial and residential areas shall comply with all of the standards in each of the following subparagraphs. <Amended Apr. 30, 2012, Dec. 27, 2013> 1. The exhaust vent shall be installed at a height of at least 2 meters above the road surface 2. Ensure that heat emitted from the exhaust system does not directly reach residents of nearby buildings or pedestrians. 3. When installing exhaust vents or exhaust devices on the exterior walls of a building, they shall be securely connected so as not to be separated from the exterior wall or protective devices, such as supports, that comply with the standards of each of the following subparagraphs, thereby preventing the exhaust vents or exhaust devices from falling. a. It shall be a structure capable of supporting an exhaust port or exhaust device B. Use materials capable of preventing corrosion or apply paint. [Title Revised 2012.4.30] Article 24 Deleted <2020.4.9> ■ Rules on Standards for Building Facilities, etc. [Attachment Form No. 1] <Amended May 2, 2017> Confirmation of Building Equipment Installation ───┬────┬───┬────────────────────────────── 1. Location of Building General Overview Details Usage Gross Floor Area Number of Floors ├────┼───┼──────┼────┼───┴─────────┴──── Contractor Name License Number │ ├───┼──────┼────┼────────────────── Company Name Address ───┴────┴───┴──────┴────┴────────────────── ───┬────────┬────────────────────────┬───── 2. Classification Confirmation Opinion Confirmation Date OK Details Water Supply and Hot Water Supply Facilities ├────────┼────────────────────────┼───── Drainage and Ventilation Equipment ├────────┼────────────────────────┼───── Piping Installation (Water Supply & Drainage) ├────────┼────────────────────────┼───── Sanitary Fixtures ├────────┼────────────────────────┼───── Heat Source Equipment ├────────┼────────────────────────┼───── Air Conditioning Equipment Installation ├────────┼────────────────────────┼───── Duct Installation ├────────┼────────────────────────┼───── Piping Installation (Air Conditioning) ├────────┼────────────────────────┼───── Cooling Equipment ├────────┼────────────────────────┼───── Heating Equipment ├────────┼────────────────────────┼───── Piping System (Heating & Cooling) ├────────┼────────────────────────┼───── Gas Equipment ├────────┼────────────────────────┼───── Fire Extinguishing and Smoke Exhaust Equipment ├────────┼────────────────────────┼───── Waste Treatment Equipment ├────────┼────────────────────────┼───── Elevators (Mechanical Division) ├────────┼────────────────────────┼───── Elevator (Electrical Division) ├────────┼────────────────────────┼───── Electrical Installation ├────────┼────────────────────────┼───── Lightning rod installation ├────────┼────────────────────────┼───── Others ───┴────────┴────────────────────────┴───── I confirm that construction has been carried out as stated above in accordance with Article 3, Paragraph 2 of the "Rules on Standards for Building Facilities, etc." (However, Professional Engineer Verification is limited to cases where related equipment is installed) Year Month Day Verifier: Professional Engineer in Architectural Electrical Equipment (Seal) Qualification Number: Professional Engineer in Power Transmission and Distribution (Seal) Qualification No. : Professional Engineer in Architectural Mechanical Equipment (Seal) Qualification No. : Professional Engineer in Air Conditioning and Refrigeration (Seal) Qualification No. : Professional Gas Engineer (Seal) Qualification No. : To the Building Owner & Construction Supervisor ━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━ 210㎜×297㎜[(Newspaper (54g/㎡)] Original file: /LSW/flDownload.do?flSeq=168578921 Original file: /LSW/flDownload.do?flSeq=168578925 Original file: /LSW/flDownload.do?flSeq=168578923 [Attachment Form No. 2] <Revised Mar. 2, 2020> ┏━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┓ Ondol Installation Confirmation ┠─────────────────────────────────────────────┨ 1. General Requirements ┠─────┬───┬───────────────────────────────────┨ Building Location Overview Usage Building Area Heating Area ┃ ├───┼┴────────┴────┬────┼────┴──────────┨ Building Owner Phone Number ┠─────┼───┼──────────────┼────┼───────────────┨ Contractor Name Registration Number ┃ ├───┼──────────────┼────┼───────────────┨ Company Name Phone Number ┃ ├───┼──────────────┴────┴───────────────┨ Address ┠─────┴───┴───────────────────────────────────┨ 2. Installation Status ┠─────┬───┬──────────────┬────┬────┬──────────┨ Boiler Heat Source □ Oil, □ Electric, □ Gas Radiation Tube Specifications □ Other heat sources ( ) Type Capacity Interval ┃ ├───┼──────────────┼────┼────┴──────────┨ Manufacturer Ondol Type □ Hot Water Ondol, □ Gudeul Ondol ┠─────┴───┴──────────────┴────┴───────────────┨ 3. Installation Details Verification ┠───────────────────┬───────────────┬─────────┨ Classification Confirmation Details Special Notes ┠────┬──────────────┼───────────────┼─────────┨ Boiler Water Pressure and Safety Device Equipment Combustion and Exhaust Performance ┃ ├──────────────┼───────────────┼─────────┨ Check for fuel system leaks ┃ ├──────────────┼───────────────┼─────────┨ Performance of Automatic Control ┠────┼──────────────┼───────────────┼─────────┨ Whether hot water floor surface temperature is uniform Ondol Installation Insulation Layer Construction Status ┃ ├──────────────┼───────────────┼─────────┨ Installation of waterproofing/moisture barrier ┃ ├──────────────┼───────────────┼─────────┨ Prefabricated Hot Water Underfloor Heating Panel Installation Status ┠────┼──────────────┼───────────────┼─────────┨ Whether ventilation holes or ventilation equipment are installed in the Gudeul Ondol Whether equipment air intake is installed ┃ ├──────────────┼───────────────┼─────────┨ Whale bottom slope status ┃ ├──────────────┼───────────────┼─────────┨ Fireplace guide pipe inclination status ┃ ├──────────────┼───────────────┼─────────┨ Suitability of Chimney Internal Cross-sectional Area ┠────┼──────────────┼───────────────┼─────────┨ Insulation status of other auxiliary piping facilities Matters Comfortable and efficient energy management ┠────┴──────────────┴───────────────┴─────────┨ Article 62 of the “Building Act,” Article 87, Paragraph 2 of the Enforcement Decree of the same Act, and the “Regarding Building Equipment Standards, etc.” I confirm that construction has been carried out as stated above in accordance with Article 12, Paragraph 2 of the [Rules]. ┃ ┃ Year Month Day ┃ ┃ Contractor: (Signature) To the Construction Supervisor ┠─────────────────────────────────────────────┨ Required Documents: Copy of Contractor's Construction Business Registration Certificate ┠─────────────────────────────────────────────┨ ※ How to fill out 1. In the “Registration Number” field, in cases where construction must be performed by a construction business operator pursuant to Article 41 of the Framework Act on the Construction Industry . 2. In the “Heat Source” column of the boiler, mark a √ in the corresponding □ box, and in the case of other heat sources, the corresponding ondol method. 3. Mark the appropriate □ box with a √ in the “Ondol method” column. ┗━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┛ 210㎜×297㎜[Standard Paper 60g/㎡ (Recycled)] Original file: /LSW/flDownload.do?flSeq=168578927 Original file: /LSW/flDownload.do?flSeq=168578931 Original file: /LSW/flDownload.do?flSeq=168578929 Revision ⊙Ministry of Land, Infrastructure and Transport Decree No. 1614 The Partial Amendment to the Rules on Standards for Building Facilities, etc. is hereby promulgated as follows. August 24, 2026 Minister of Land, Infrastructure and Transport (Seal) Partial Amendment to the Rules on Building Facility Standards, etc. The Rules on Standards for Building Facilities, etc. are partially amended as follows. In Article 18, subparagraph 5, "pursuant to the provisions of Annex 1 of the 'Rules on Cleaning and Sanitary Management, etc. of Waterworks Facilities'" shall be changed to "pursuant to Annex 3-2 of the 'Enforcement Rules of the Water Supply Act'," and subparagraph 7 of the same article shall be as follows. 7. Water supply pipes for drinking water shall comply with the sanitary safety standards pursuant to Article 24 and Annex 1-2 of the Enforcement Decree of the Water Supply Act, and water supply materials and products pursuant to Article 24-2 of the same Decree shall be used. In Note 2, Item (a) of Attached Table 1-2, "shall be installed" is changed to "must be installed," and Item 3 is newly added to the same Note as follows. 3. In the case of data centers corresponding to "other facilities" under Subparagraph (d) of Item 3 of the above table, the number of passenger elevators to be installed shall be calculated based on the total sum of living room areas, excluding the areas of server rooms and computer rooms. The following latter part is newly added to Item 2 of Attached Table 1-5. In this case, bathrooms and restrooms equipped with separate ventilation facilities may be excluded when calculating the total ventilation volume required for each room. Supplementary Provisions This rule shall take effect from the date of its promulgation. Reason for Enactment/Amendment [Partial revision] ◇ Reasons for Amendment and Key Contents This aims to improve and supplement certain shortcomings observed in the operation of the current system, such as allowing the area of ​​computer rooms and server rooms to be excluded from the area calculation standards when installing passenger elevators in data centers with a low number of users relative to the building area, and permitting the installation of mechanical ventilation systems only in the areas excluding bathrooms and restrooms in newly constructed multi-unit housing, etc., where separate ventilation facilities are already installed.