Rules on Structural Standards for Buildings, etc.

267091 · 2024-12-17

Chapter 1 General Provisions Article 1 (Purpose) The purpose of this Rule is to prescribe necessary matters concerning structural safety, such as standards for the structural strength of buildings, methods of structural calculation, and loads used therein, in accordance with Articles 48, 48-2, and 48-3 of the Building Act and Article 32 of the Enforcement Decree of the same Act. <Amended Dec. 31, 2009; Jan. 20, 2017> Article 2 (Definitions) The definitions of terms used in this Rule are as follows. <Amended Dec. 31, 2009, Nov. 9, 2018> 1. The term "structural member" refers to a major part of a building in terms of structural strength that has the function of safely supporting the building against the design loads acting on the building pursuant to Article 9, such as foundations, walls, columns, floor slabs, roof frames, bases, diagonal members (referring to braces, supports, corner brackets, and other similar items), and transverse members (referring to beams, purlins, and other similar items). 2. "Member force" refers to axial force, bending moment, shear force, torsion, etc., generated in a structural member by loads and external forces. 3. Delete<2009.12.31> 4. "Structural strength" refers to the member forces that structural members and parts in contact with them can withstand. 5. The term "wall" refers to a vertical member in which the horizontal dimension measured perpendicular to the thickness exceeds three times its thickness. 6. The term "column" refers to a member having a height of three times or more of the minimum cross-sectional dimension and used primarily to support axial compressive loads. 7. The term "non-structural element" refers to any of the following items as determined and notified by the Minister of Land, Infrastructure and Transport. A. Non-structural elements of a building: Components of a building that do not bear structural load, such as exhaust vents, attachments, and non-structural walls. B. Mechanical and Electrical Non-structural Elements: Mechanical and electrical systems installed in buildings and attachments and equipment supporting them 8. Delete<2009.12.31> 9. Delete<2009.12.31> 10. Delete<2009.12.31> 11. Delete<2009.12.31> 12. Delete <2009.12.31> 13. "Structural Plan" refers to a document from the initial stage of structural design that determines the materials, shapes, and approximate dimensions of structural members, taking into consideration the building's intended use, load conditions, and ground characteristics, in order to create a structurally safe space. 14. "Structural design drawing" refers to a drawing that expresses the composition, shape, connection details, etc., of structural members as the final result of structural design. 15. The term "structural design documents" refers to structural plans, structural design drawings, structural calculation sheets, and construction specifications in the structural field. Article 3 (Scope of Application, etc.) ① This Rule shall apply to the design, construction, construction supervision, and maintenance and management of buildings pursuant to Articles 23 through 25 and Article 35 of the Building Act as minimum standards for ensuring that buildings have a safe structure in accordance with Article 48 of the Building Act (hereinafter referred to as the "Act"). ② Detailed standards other than those stipulated in this Rule shall be in accordance with the standards classified in each of the following subparagraphs, notified by the Minister of Land, Infrastructure and Transport pursuant to Article 68 of the Act and the delegation under this Rule. <Amended Mar. 23, 2013; Feb. 3, 2017; Jun. 1, 2018; Dec. 17, 2024> 1. In the case of buildings other than small-scale buildings [referring to buildings that are two stories or less and have a gross floor area of ​​less than 500 square meters, and do not fall under any of subparagraphs 3 through 8 of Article 32, Paragraph 2 of the Enforcement Decree of the Building Act (hereinafter referred to as the "Decree"). The same applies hereinafter]: Building structural standards (including special purpose building standards. The same applies hereinafter) 2. For small-scale buildings: Building Structural Standards or Small-scale Building Structural Standards ③ The standards for structural safety pursuant to the provisions of Articles 21 through 55 shall apply only to small-scale buildings. <Amended Nov. 28, 2014, Feb. 3, 2017> ④ In cases where a structure is designed based on structural calculations or tests by a research institution, academic organization, or specialized service agency, and is confirmed to possess safety equivalent to or greater than the technical standards under this Rule following deliberation by the Architectural Committee pursuant to Article 4 of the Building Act or the Construction Technology Deliberation Committee pursuant to Article 5 of the Construction Technology Promotion Act, and is recognized by the Special City Mayor, Metropolitan City Mayor, or Mayor, County Governor, or District Head (referring to the head of an autonomous district; hereinafter the same applies), such recognition may be applied. <Amended May 22, 2014> [Wholly Revised 2009.12.31] Chapter 2 Structural Design <Revised 2009.12.31> Section 1. Principles of Structural Design <Revised 2009.12.31> Article 4 (Safety) ① The design regarding the structure of a building shall take into consideration the building's use, scale, type of structure, and ground conditions, and shall effectively arrange foundations, columns, beams, floors, walls, non-structural elements, etc., so that the entire building is structurally safe against the design loads acting thereon pursuant to Article 9. <Amended Dec. 31, 2009, Nov. 9, 2018> ② Walls that are structural members shall be arranged in a balanced manner so as to effectively withstand lateral forces acting on the building. <Amended 2009.12.31> ③ The structure of a building shall not be impaired in its structural strength against differential settlement of the ground, uplift, slipping, overturning, or frost damage. [Title revised 2009.12.31] Article 5 (Serviceability and Durability of Structural Members) ① Structural members of a building shall secure the necessary stiffness to prevent deformation or vibration that impedes use, and shall consider securing toughness to prevent instantaneous failure. <Amended Dec. 31, 2009> ② With respect to structural members that are particularly susceptible to corrosion or wear away, necessary measures shall be taken, such as using materials capable of preventing such occurrences. <Amended Dec. 31, 2009> ③ For timber used as structural members, parts in contact with brick, concrete, soil, or other similar water-retaining materials shall be coated with a preservative or subjected to preservative measures having an effect equivalent to or greater than that. 4. Parts of a building's walls that come into direct contact with the soil shall be constructed of water-resistant materials, with the exception of gates, fences, and other similar structures or buildings. [Title revised 2009.12.31] Article 6 Deleted <2009.12.31> Article 7 Deleted <2009.12.31> Section 2 Design Loads <Revised 2009.12.31> Article 8 (Scope of Application) ① The calculation of various design loads acting on a building shall be in accordance with the provisions of this Section. <Amended 2009.12.31> ② The provisions of this Section may not apply when calculating design loads based on an investigation and analysis of actual load conditions, such as the area where a building is constructed, the building's use, and other environmental factors. In such cases, the basis for the calculation must be specified. <Amended Dec. 31, 2009> Article 9 (Design Load) ① The design loads applied to the structural design of buildings shall be as follows: <Amended Dec. 31, 2009, Nov. 9, 2020> 1. Dead Load 2. Live load 2-2. Roof Live Load 3. Snow load 4. Wind load 5. Seismic Load 6. Earth Pressure and Groundwater Pressure 7. Temperature load 8. Fluid Pressure and Container Content Load 9. Load of conveying equipment and auxiliary devices 10. Other Loads ② The standards and methods for calculating design loads pursuant to Paragraph 1 shall be as prescribed in the “Architectural Structural Standards.” <Amended 2009.12.31> ③ When performing structural design for a building, the effects of the loads specified in each subparagraph of Paragraph 1 and combinations thereof shall be considered in accordance with the actual condition of the building. <Amended 2009.12.31> [Title revised 2009.12.31] Section 3 Structural Calculations, etc. <Newly Added 2009.12.31> Article 9-2 (Structural Calculations) Structural calculations for buildings for which structural safety must be verified pursuant to Article 48, Paragraph 2 of the Act shall be in accordance with the provisions of the “Architectural Structural Standards.” [New article established 2009.12.31] Article 9-3 (Restrictions on Building Size) Buildings whose main structural components are non-reinforced masonry shall be limited to a roof height of 15 meters or less, an eaves height of 11 meters or less, and three stories or less. [Wholly Revised 2020.11.9] Article 10 Deleted <2009.12.31> Article 11 Deleted <2009.12.31> Article 12 Deleted <2009.12.31> Article 13 Deleted <2009.12.31> Article 14 Deleted <2009.12.31> Article 15 Deleted <2009.12.31> Article 16 Deleted <2009.12.31> Article 17 Deleted <2009.12.31> Section 4 Structural Standards for Foundations <Newly Added 2009.12.31> Article 18 (Allowable Bearing Capacity) The allowable bearing capacity of the ground shall be determined by ground investigation and load testing in accordance with the “Architectural Structural Standards.” However, in cases where ground investigation and load testing are not conducted, the value specified in Annex 8 may be used. <Amended Dec. 31, 2009> [Title revised 2009.12.31] Article 19 (Basis) ① Direct foundations shall directly bear the load of the superstructure in the foundation soil, provided that the pressure acting on the soil at the base of the foundation does not exceed the allowable bearing capacity. <Revised 2009.12.31> ② Pile foundations shall ensure that the member forces of the piles do not exceed the allowable bearing capacity of the piles, and shall not exert harmful effects on the superstructure due to settlement, etc. <Amended 2009.12.31> Article 20 Deleted <2009.12.31> Chapter 3 Structural Standards for Small-Scale Buildings Section 1 General Rules Article 21 (Purpose) The purpose of this Chapter is to prescribe matters necessary to ensure the structural safety of small-scale buildings and related structural standards, etc. Article 22 (Scope of Application) The technical standards for timber, masonry, reinforced block, and concrete structures classified as small-scale buildings shall be as prescribed by this Chapter. However, the provisions of this Chapter may not apply in cases where the design is carried out in accordance with the "Architectural Structural Standards." <Amended Dec. 31, 2009> Section 2 Timber Structure Article 23 (Scope of Application) The provisions of this Section shall apply to the wooden parts of buildings with a timber structure or buildings that combine timber, masonry, or other structures. However, this shall not apply to pavilions, other buildings similar thereto, or mines, warehouses, or other similar buildings with a gross floor area of ​​10 square meters or less. Article 24 (Minimum Cross-section of Compression Members and Columns Installed at Corners) ① The cross-sectional area of ​​compression members that are structural members made of wood shall be at least 4,500 square millimeters. <Revised 2009.12.31> ② In buildings of two stories or more, columns installed at corners or columns equivalent thereto shall be solid columns (referring to columns made as a single piece without joints). However, this shall not apply to spliced ​​columns if the spliced ​​portion is reinforced to have a load-bearing capacity equal to or greater than that of a solid column. <Amended Aug. 27, 2021> Article 25 (Braiding) ① Braces subjected to tensile force shall be made of timber with a thickness of at least 15 millimeters and a width of at least 90 millimeters, or steel having equivalent or greater strength. ② Braces subjected to compressive force shall use timber with a thickness of at least 35 millimeters and a thickness equivalent to one-third of the frame column. ③ The two ends of a brace shall be connected to a column, beam, or other horizontal structural member. <Amended 2009.12.31> ④ Bracing shall not be excavated or otherwise damaged in a way that impairs its load-bearing capacity. Article 26 (Floor Frames and Roof Frames) Corner braces shall be used at the corners of floor frames and roof frames, and bracing shall be installed on roof frames. Article 27 (Preservative Measures) ① For timber used as structural members, parts in contact with brick, concrete, soil, or other similar moisture-retaining materials shall be coated with a preservative or subjected to preservative measures having an effect equivalent to or greater than that. <Amended 2009.12.31> ② Parts susceptible to corrosion, such as columns, braces, and foundations located at a height of 1 meter or less above the ground surface, shall be coated with a preservative or constructed with a structure having an equivalent or superior preservative effect. Section 3 Masonry Structure Article 28 (Scope of Application) ① The provisions of this Section shall apply to buildings of brick, stone, concrete block, or other masonry structures (excluding reinforced block structures; hereinafter the same applies in this Section), or to the masonry parts of buildings that combine masonry structures with timber or other structures. ② For buildings with a height of 4 meters or less and a gross floor area of ​​20 square meters or less, the provisions of Articles 29, 30, 35, 36, 38, and 40 shall apply only to them. ③ With respect to boundary walls of masonry structure that are not structural members and whose height is 2 meters or less, only Articles 29, 30, 33, and Article 35, Paragraph 3 shall apply. <Amended Dec. 31, 2009; Nov. 28, 2014> Article 29 (Design of Masonry Structures) ① Masonry materials shall be designed so as not to have continuous joints. ② The walls of each floor of a masonry structure shall be designed so that eccentric loads do not act upon them. Article 30 (Basis) ① The foundation of a load-bearing wall of a masonry structure (referring to the portion corresponding to the floor surface of the lowest story or lower) shall be a continuous foundation. ② Among the foundations prescribed in Paragraph 1, the foundation plate shall be of a reinforced concrete or plain concrete structure, and the thickness of the foundation wall shall be at least 250 millimeters. Article 31 (Height and Length of Load-Bearing Walls) ① In the case of a two-story building of masonry structure, the height of the load-bearing wall on the second floor shall not exceed 4 meters. ② The length of a load-bearing wall of masonry structure [in the case of adjacent walls (referring to walls that intersect at right angles to each other), it refers to the length of the line connecting the centers of the joined parts. The same shall apply hereinafter in this Section] shall not exceed 10 meters. <Amended Aug. 27, 2021> ③ The floor area of ​​a part enclosed by load-bearing walls of masonry structure shall not exceed 80 square meters. Article 32 (Thickness of Load-Bearing Walls) ① The thickness of a load-bearing wall of masonry structure (excluding the thickness of finishing materials; hereinafter the same applies in this Section) shall be greater than or equal to the thickness of the load-bearing wall of the floor immediately above. ② The thickness of load-bearing walls of masonry structure shall be at least the thicknesses specified in the following table, respectively, according to the number of stories, height, and length of the building; provided, however, that if the masonry material is brick, it shall be at least 1/20 of the wall height, and if it is block, it shall be at least 1/16 of the wall height. <img src="http://www.law.go.kr/flDownload.do?flSeq=28484648" alt="img28484648" > ┌───────┬─────────────┬─────────────┬─────────────┐ Building height less than 5 meters 5 meters or more less than 11 meters 11 meters or more ├───────┼──────┬──────┼──────┬──────┼──────┬──────┤ Wall length less than 8 meters 8 meters or more less than 8 meters 8 meters or more less than 8 meters 8 meters or more ├──┬────┼──────┼──────┼──────┼──────┼──────┼──────┤ By Floor 1st Floor 150mm 190mm 190mm 190mm 190mm 190mm 290mm Thickness 2nd floor - - 190 millimeters 190 millimeters 190 millimeters 190 millimeters └──┴────┴──────┴──────┴──────┴──────┴──────┴──────┘ </img> ③ In applying the provisions of Paragraph 2, where the masonry material is stone, or where stone is used in combination with brick or blocks, etc., the thickness of the load-bearing wall shall be at least the thickness specified in Paragraph 2 plus 2/10, provided that it shall be at least 1/15 of the height of the wall. 4. In cases where the floor area of ​​a portion enclosed by load-bearing walls of masonry structure exceeds 60 square meters, the thickness of each load-bearing wall shall be at least the thickness specified in the following table; provided, however, that the provisions of Paragraphs 2 and 3 shall apply mutatis mutandis to the thickness of load-bearing walls by material for masonry structures. <img src="http://www.law.go.kr/flDownload.do?flSeq=28484650" alt="img28484650" > ┌────────┬──────┬──────┐ Number of floors in the building 1st floor 2nd floor ├─────┬──┼──────┼──────┤ Layer Thickness 1 Layer 190 mm 290 mm │ │ │ │ │ 2 layers - 190 millimeters └─────┴──┴──────┴──────┘ </img> ⑤ Load-bearing walls subjected to earth pressure shall not be of masonry construction. However, if the height of the portion subjected to earth pressure does not exceed 2.5 meters, they may be of brick masonry construction. ⑥ In the case of the proviso to Paragraph 5, if the height of the part subject to earth pressure is 1.2 meters or more, the thickness of the load-bearing wall shall be at least the thickness of the wall of the immediately upper floor plus 100 millimeters. 7. In cases where a load-bearing wall of masonry structure is constructed as a double wall, the provisions of Paragraphs 1 through 6 shall apply to only one of the said load-bearing walls. However, in the case of a double load-bearing wall located on the uppermost floor of a building (or the first floor in the case of a one-story building) with a height not exceeding 3 meters, and reinforced with a spacing of no more than 400 millimeters in both width and length between each wall, the sum of the thicknesses of each wall shall be deemed as the thickness of said load-bearing wall. Article 33 (Thickness of Boundary Walls, etc.) ① The thickness of boundary walls of masonry structure (including walls other than load-bearing walls; hereinafter the same applies in this Section) shall be 90 millimeters or more. <Amended 2014.11.28> ② In cases where a boundary wall or major structure of masonry construction is installed on the floor immediately above a boundary wall of masonry construction, the thickness of said boundary wall shall be at least 190 millimeters. However, this shall not apply in cases where a perimeter beam is installed pursuant to the provisions of Article 34. <Amended 2014.11.28> ③ The provisions of Article 32 shall apply mutatis mutandis to the thickness of boundary walls of masonry structure. <Amended 2014.11.28> [Title revised 2014.11.28] Article 34 (Perimeter Beams) Perimeter beams of steel or reinforced concrete structure, with a depth of at least 1.5 times the wall thickness, shall be installed above load-bearing walls of masonry structure on each floor of a building. However, for a single-story building where the wall thickness is at least 1/16th of the wall height or the wall length is 5 meters or less, wooden perimeter beams may be installed. Article 35 (Openings) ① The structure of windows, doorways, and other openings in walls of masonry construction shall comply with the standards of each of the following subparagraphs. 1. In each wall partitioned by a wall on each floor, the sum of the widths of the openings shall not exceed half the length of the wall. 2. The vertical distance between an opening on a single floor and an opening on the floor immediately above it shall be at least 600 millimeters. If upper and lower openings are separated in the walls of the same floor, the distance between them shall also be the same. ② For openings installed in walls of masonry structure, the horizontal distance between openings or between an opening and the center of the adjacent wall shall be at least twice the thickness of the wall for each floor. However, this shall not apply if the upper part of the opening is an arch structure. ③ A reinforced concrete lintel (referring to a structure installed across the bottom or top of a door or window to support the weight of the upper section) must be installed at the top of openings exceeding 1.8 meters in width. <Revised Aug. 27, 2021> ④ Cantilevered windows or cantilevered windows of masonry structure shall be reinforced with steel or reinforced concrete. Article 36 (Grooves in Walls) Where continuous vertical grooves extending at least three-quarters of the height of the floor are installed in a wall of masonry structure, the depth of the grooves shall not exceed one-third of the wall thickness; and where horizontal grooves are installed, the depth of the grooves shall not exceed one-third of the wall thickness, provided that the length is not more than 3 meters. Article 37 (Walls of Timber or Steel Masonry Structures) The masonry portion of a wall of a timber or steel masonry structure shall be fixed to the timber or steel frame using bolts, brackets, or other hardware. Article 38 (Handrails and Handrail Walls) When installing handrails or handrail walls, they shall be reinforced with reinforcing bars, etc., and their lower portions shall be anchored to perimeter beams or floor slabs (including rooftop floor slabs in the case of the top floor; hereinafter the same applies). Article 39 (Fences of Masonry Structure) The structure of fences of masonry structure shall comply with the standards in each of the following subparagraphs. 1. The height shall be 3 meters or less 2. The thickness of the wall shall be 190 millimeters or more. However, for walls with a height of 2 meters or less, it may be 90 millimeters or more. 3. Install a buttress wall protruding from the wall surface by an amount greater than or equal to the thickness of that part of the wall for every 2 meters or less of the wall length, or install a buttress wall protruding from the wall surface by an amount greater than or equal to 1.5 times the thickness of that part of the wall for every 4 meters or less of the wall length. However, this shall not apply if the thickness of the wall in each part is 1.5 times or more of the wall thickness specified in Subparagraph 2. Article 40 (Support Method for Structural Members) A structural member of masonry construction shall not be supported by a structural part of timber construction. <Amended Dec. 31, 2009> [Title revised 2009.12.31] Section 4 Reinforcement Block Structure Article 41 (Scope of Application) ① The provisions of this Section shall apply to the reinforced block structure portions of buildings constructed of reinforced block structures or to buildings that combine reinforced block structures with reinforced concrete structures or other structures. ② For buildings with a height of 4 meters or less and a gross floor area of ​​20 square meters or less, the provisions of Articles 42 and 45 shall apply only. Article 42 (Foundation) The foundation of a load-bearing wall of reinforced block structure (referring to the portion below the lowest floor level) shall be a continuous foundation, provided that the foundation plate portion thereof shall be of reinforced concrete. Article 43 (Load-bearing Walls) ① For each floor of a building, the length of load-bearing walls of a reinforced block structure in the longitudinal or transverse direction (in the case of a lintel wall, the length of the line connecting the centers of the joined parts thereof; hereinafter the same applies in this Section) shall be such that the sum of the lengths of the load-bearing walls in each direction is at least 0.15 meters per 1 square meter of the floor area of ​​that floor, provided that the floor area of ​​the part enclosed by such load-bearing walls shall not exceed 80 square meters. ② The thickness of a load-bearing wall of a reinforced block structure (excluding the thickness of finishing materials; hereinafter the same applies in this Section) shall be at least 150 millimeters, provided that it is at least 1/50th of the horizontal distance between points critical to the structural strength of the load-bearing wall. ③ For load-bearing walls of reinforced block structures, reinforcing bars of 12 millimeters or more shall be placed vertically at their ends and corners, and reinforcing bars of 9 millimeters or more shall be placed at intervals of no more than 800 millimeters horizontally or vertically. ④ Both ends of the longitudinal reinforcement pursuant to the provisions of Paragraph 3 shall be anchored to the foundation plate, perimeter beam, or floor slab at a distance of at least 40 times the diameter of the reinforcement. Article 44 (Ceramic Beams) A perimeter beam made of reinforced concrete, with a depth of at least 1.5 times the wall thickness, shall be installed above the walls of each floor of load-bearing walls of reinforced block structure. However, this shall not apply to the walls of the uppermost floor where a reinforced concrete roof slab is installed above them. Article 45 (Walls of Reinforced Block Structure) The structure of a wall of reinforced block structure shall comply with the standards in each of the following subparagraphs. 1. The height of the wall shall be 3 meters or less 2. The thickness of the wall shall be 150 millimeters or more. However, for walls with a height of 2 meters or less, it may be 90 millimeters or more. 3. Reinforcement bars shall be placed inside the wall at intervals of no more than 800 millimeters horizontally or vertically, and reinforcement bars with a diameter of at least 9 millimeters shall be placed vertically at the ends and corners of the wall. Article 46 (Applicable Provisions) Paragraphs 2 through 4 of Article 35, Article 36, Article 38, and Article 40 shall apply mutatis mutandis to the parts comprising the reinforced block structure in the case of a building of reinforced block structure or a building utilizing both a reinforced block structure and other structures. Section 5 Concrete Structure Article 47 (Scope of Application) ① The provisions of this Section shall apply to the reinforced concrete parts of buildings constructed of reinforced concrete or buildings that combine reinforced concrete, masonry, or other structures. ② For buildings with a height of 4 meters or less and a gross floor area of ​​30 square meters or less, or for walls with a height of 3 meters or less, the provisions of Articles 49 and 51 shall apply only to such buildings. Article 48 (Concrete Mix Design) ① The 4-week compressive strength of concrete used in reinforced concrete structures shall be at least 15 megapascals (11 megapascals in the case of using lightweight aggregates). ② Concrete shall be mixed by determining the mixing ratios of aggregate and cement, and water and cement, to meet the design standard strength. Article 49 (Curing of Concrete) Concrete shall be cured during and after construction so that its temperature is maintained at 2 degrees Celsius or higher until the compressive strength of the concrete reaches 5 megapascals or more (or 5 days if the compressive strength is not confirmed by a concrete compressive strength test), and so that the solidification and hardening of the concrete are not affected by drying or vibration. Article 50 (Removal of Formwork and Support Columns) ① Formwork and supporting columns of structural members shall not be removed until they have solidified or hardened to the extent that deformation, cracking, or other structural strength caused by the self-weight of the concrete and loads received during construction is not affected. <Amended Dec. 31, 2009, Aug. 27, 2021> ② The period during which formwork and supporting columns pursuant to the provisions of Paragraph 1 must be retained shall be determined in consideration of the part or location of the relevant building, the type of cement, the method of concrete curing, the environment, and other conditions. Article 51 (Thickness of Concrete Covering Reinforcement) The thickness of concrete covering reinforcement shall comply with the standards in each of the following subparagraphs. 1. In the case of concrete in contact with soil or directly exposed to outdoor air A. Reinforcing bar with a diameter of 29 millimeters or more: 60 millimeters or more B. Rebar with a diameter exceeding 16 mm and less than 29 mm: 50 mm or more C. Reinforcing bar with a diameter of 16 millimeters or less: 40 millimeters or more 2. In the case of concrete that is not in direct contact with outdoor air or soil A. Slabs, walls, joists: 20 millimeters or more B. Beams, Columns: 40 millimeters or more Article 52 (Structure of Beams) Beams, which are structural members, shall be reinforced with double reinforcement, and the main reinforcement shall be of 12 millimeters or more in diameter. However, stirrups shall be of 6 millimeters or more in diameter, and their spacing shall be no more than three-quarters of the beam depth or 450 millimeters. <Amended Dec. 31, 2009> Article 53 (Structure of Concrete Slabs) The structure of concrete slabs serving as structural members (excluding those that are prefabricated concrete products) shall comply with the standards set forth in each of the following subparagraphs. <Amended Dec. 31, 2009> 1. The thickness of the concrete slab shall be at least 80 millimeters and shall be greater than or equal to the thickness calculated according to Attached Table 9. 2. In parts subjected to the maximum bending moment, the spacing of tensile reinforcement shall be 200 millimeters or less in the short direction and 300 millimeters or less in the long direction, provided that it is not more than three times the thickness of the slab. Article 54 (Structure of Load-Bearing Walls) Concrete walls that are structural members shall comply with the standards in each of the following subparagraphs. <Amended Dec. 31, 2009> 1. The minimum thickness of load-bearing walls shall be at least 150 millimeters up to 4.5 meters from the top of the wall, and shall be increased by a rate of 10 millimeters for every 3 meters descending. However, this shall not apply in cases where the thickness is 120 millimeters or more and is confirmed to be safe through structural calculations. 2. Reinforcement of load-bearing walls shall consist of materials at least 9 millimeters thick, spaced no more than 450 millimeters apart, and shall not exceed three times the wall thickness. In this case, if the wall thickness is 200 millimeters or more, double reinforcement shall be applied to both sides of the wall. Article 55 (Unreinforced Concrete Structures) The provisions of Section 3 (excluding Article 29, Paragraph 1 and Article 30, Paragraph 2) and the provisions of Article 49 shall apply mutatis mutandis to the unreinforced concrete structural parts of a building with an unreinforced concrete structure or a building that combines an unreinforced concrete structure with a masonry structure or other structures. <Amended Dec. 31, 2009> Chapter 4 Verification of Structural Safety <Newly Added 2009.12.31> Article 56 (Scope of Application) ① The procedures, contents, and methods for verifying structural safety (including structural safety against earthquakes) at each stage pursuant to Article 32, Paragraph 1 of the Enforcement Decree shall be in accordance with Articles 57 through 59. <Amended 2014.11.28> ② In Subparagraph 6 of Article 32, Paragraph 2 of the Enforcement Decree, the term "buildings prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" refers to buildings corresponding to Importance Grade Special or Importance Grade 1 pursuant to Annex 11. <Amended Mar. 23, 2013; Nov. 28, 2014; Oct. 24, 2017> ③ In Subparagraph 7 of Article 32, Paragraph 2 of the Enforcement Decree, the phrase "buildings worthy of preservation as national cultural heritage as prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" refers to museums, memorial halls, or other similar structures worthy of preservation as national cultural heritage, with a total floor area of ​​5,000 square meters or more. <Amended Mar. 23, 2013; Nov. 28, 2014> [New article established 2009.12.31] Article 57 (Preparation of Structural Design Documents) Structural design documents shall be prepared in accordance with this Rule, and the contents to be included in the structural design documents and the technical standards for verification of structural safety shall be as prescribed in the “Architectural Structural Standards” or the “Structural Standards for Small-Scale Buildings.” <Amended Feb. 3, 2017> [New article established 2009.12.31] Article 58 (Submission of Structural Safety Confirmation Certificate) For a building falling under any of the subparagraphs of Article 32, Paragraph 2 of the Enforcement Decree, for which structural safety (including structural safety against earthquakes) has been confirmed pursuant to Paragraph 1 of the same Article, when filing a report on commencement of construction pursuant to Article 21 of the Act, a structural safety and seismic design confirmation certificate classified according to the following subparagraphs shall be prepared and submitted. <Amended Nov. 28, 2014; Feb. 3, 2017> 1. Buildings of 6 stories or more: Confirmation of Structural Safety and Seismic Design in accordance with Form No. 1 2. Small-scale buildings: Certificate of Structural Safety and Seismic Design pursuant to Form No. 2 or Certificate of Structural Safety and Seismic Design pursuant to Form No. 3 3. Buildings other than those in Nos. 1 and 2: Confirmation of Structural Safety and Seismic Design in accordance with Form No. 2 [New article established 2009.12.31] Article 58-2 (Special Provisions for Submission of Structural Safety Confirmation Certificate for Extension or Major Repair for Performance Improvement) ① A building owner who expands or extensively renovates an existing building in accordance with the following subparagraphs pursuant to the main text of the part other than the subparagraphs of Article 32, Paragraph 3 of the Enforcement Decree shall submit a Structural Safety Confirmation Certificate in the form of Annex 4 when filing a report on commencement of construction pursuant to Article 21 of the Act. 1. Extension for the purpose of repairing, altering, or adding a roof or exterior wall (limited to cases where changes in the building coverage ratio, floor area ratio, and height of the building are within the permissible tolerance range pursuant to Article 26 of the Act) 2. Major repairs falling under any of the following items a. Major repairs pursuant to Subparagraph 5 of Article 3-2 of the Enforcement Decree (limited to cases where a fire door or fire shutter is installed or altered, and a part of the floor or wall for a fire compartment is repaired) B. Major repairs pursuant to Subparagraph 9 of Article 3-2 of the Enforcement Decree (limited to cases where heavy finishing materials such as bricks or stone in accordance with building structural standards are not installed on the exterior walls of a building) 3. Expansion or major repair equivalent to Subparagraph 1 or 2, as prescribed by the local government's ordinance on construction ② In Article 32, Paragraph 3, Subparagraph 2 of the Enforcement Decree, "minor change prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" refers to a change in which the increase in structural strength according to the Building Structural Standards is 5 percent or less. [This Article Newly Established 2024.12.17] Article 59 (Verification of Structural Safety during the Construction Phase) The construction supervisor shall review and verify, prior to the notification of commencement of construction or the actual commencement date, whether the detailed construction drawings related to structural members have been properly prepared and whether they have been prepared in accordance with the structural calculations and structural design documents. [New article established 2009.12.31] Article 60 (Standards for Seismic Grades of Buildings) The standards for seismic grades of buildings pursuant to Article 48-2, Paragraph 2 of the Act are as set forth in Attached Table 12. [This Article Newly Established 2014.2.7] Article 60-2 (Standards for Calculation of Seismic Capacity of Buildings and Method of Disclosure) ① The criteria for calculating seismic resistance capacity (hereinafter referred to as "seismic resistance capacity") pursuant to Article 48-3, Paragraph 1 of the Act are as set forth in Attached Table 13. ② A person applying for approval of use pursuant to Article 22 of the Act for a building under Article 48-3, Paragraph 1 of the Act shall submit the seismic capacity calculated in accordance with Item 1, Subparagraph (a) of Annex 13, stating it in the application form. In this case, a certificate of structural safety and seismic design pursuant to Article 58 must be submitted together. <Amended 2024.12.17> ③ The disclosure of seismic resistance capacity pursuant to Article 48-3, Paragraph 1 of the Act shall be made by recording the seismic resistance capacity in the building register, and the method of indicating seismic resistance capacity shall be in accordance with Subparagraph 2 of Annex 13. <Amended 2024.12.17> ④ The owner of a building who intends to calculate and disclose the seismic resistance capacity of a building that is not subject to disclosure under Article 48-3, Paragraph 1 of the Act, in the manner prescribed in Paragraph 3, shall submit data capable of verifying the seismic resistance capacity to the licensing authority in accordance with Item 1, Subparagraph (b) of Annex 13. <Newly added 2024.12.17> [New article established 2017.1.20] Article 61 (Cooperation with Structural Engineers) In cases where a building designer confirms the structural safety of a building pursuant to Article 91-3, Paragraph 1, Subparagraph 6 of the Enforcement Decree, buildings requiring the cooperation of a structural engineer shall be buildings constructed in an Earthquake Zone I area as specified in Annex 10 and classified as "Special" in importance as specified in Annex 11. <Amended Dec. 17, 2024> [Wholly Revised 2015.12.21] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 1] <Amended Nov. 9, 2018> ┌───────────────────────────────────────────┐ Certificate of Structural Safety and Seismic Design (Buildings of 6 Stories or More) ├─────────┬─────────────────────────┬───────┤ 1) Project Name Remarks ├─────────┼─────────────────────────┼───────┤ 2) Site Location / Region Coefficient ├─────────┼─────────────────────────┤ │ 3) Application ├─────────┼─────────────────────────┤ │ 4) Importance ├─────────┼───┬──────┬──────┬───────┤ │ 5) Scale Gross Floor Area m2 Number of Floors (Height) / ( m) ├─────────┼───┴──────┴──────┴───────┤ │ 6) Design Standards ├─────────┼─────────────────────────┼───────┤ 7) Structural Planning: Establishment of a Common Classification System for Structural Systems ├─────────┼────────┬──┬─────┬───────┼───────┤ 8) Soil and Foundation Soil Classification Groundwater Level │ ├────────┴──┴─────┴───────┤ │ Basic Format │ ├────────┬──┬─────┬───────┤ │ Bearing Capacity Foundation Design Bearing Capacity Pile Foundation Applicable Pile Diameter= │ │ │fe= t/m2 │ │ fp = ton │ │ ├─────────┼────────┼──┼─────┼───────┼───────┤ 9) Wind Load Overview Basic Wind Speed ​​V0=(m/sec) Exposure Diagram A, B, C, D │ ├────────┼──┼─────┼───────┤ │ Gf Importance Factor Iw= ├─────────┼────────┼──┴┬────┴───────┼───────┤ 10) Wind Load Analysis X Direction Y Direction Result Maximum floor displacement δx-max δy-max │ ├────────┼───┼────────────┤ │ Maximum story displacement Δx,max Δy,max ├─────────┼────────┴───┴────────────┼───────┤ 11) Overview of Seismic Design Earthquake according to the "Rules on Structural Standards for Buildings" and "Architectural Structural Standards" Requirements for Load Calculation │ ├────────┬────────────────┼───────┤ Analysis Method Seismic Design Categories (A,B,C,D) │ │ ├────────────────┤ │ Equivalent Static Analysis Method, Dynamic Analysis Method │ ├────────┼───┬─────┬──────┼───────┤ Importance Factor IE= Building Effective W= Weight ├─────────┼────────┼───┼─────┴──────┼───────┤ 12) Basic seismic resistance in X-direction and Y-direction structural systems systems Establishment of Lateral Force Resistance System │ ├────────┼───┼────────────┤ │ Reaction modification factor Rx= Ry= │ ├────────┼───┼────────────┤ │ Excess strength factor Ωox= Ωoy= │ ├────────┼───┼────────────┤ │ Displacement amplification factor Cdx= Cdy= │ ├────────┼───┴────────────┤ │ Allowable inter-story displacement Δax= (0.010 hs,0.015hs,0.020hs) ├─────────┼────────┼───┬────────────┼───────┤ 13) Main Seismic Design X Direction Y Direction Result Seismic Response Coefficient CSx= CSy= │ ├────────┼───┼────────────┤ │ Base shear force VSx= VSy= │ ├────────┼───┼────────────┤ │ Approximate natural period Tax= Tay= │ ├────────┼───┼────────────┤ │ Maximum story displacement Δx,max Δy,max ├─────────┼────────┼───┼────────────┼───────┤ 14) Eigenvalue Analysis Vibration Period Mass Participation Ratio (For dynamic analysis) 1st Mode Sec % │ ├────────┼───┼────────────┤ │ 2nd mode Sec % │ ├────────┼───┼────────────┤ │ 3rd Mode Sec % ├─────────┼───────┬┴───┼────────────┼───────┤ 15) Structural Element Seismic Resistance Special Seismic Load Piloti Presence, Absence Application of Design Review Items Presence, Absence of Out-of-Flat Discrepancy │ │ ├────┼────────────┤ │ Presence or Absence of Vertical Elements for Lateral Force Resistance Discontinuous │ ├───────┴────┼────────────┤ │ Vertical system discontinuity presence, absence ├─────────┼─────────┬──┴────────────┼───────┤ 16) Non-structural elements Architectural non-structural elements during the construction phase requiring verification Mechanical & Electrical Non-structural Elements Non-structural element description ├─────────┼─────────┴───────────────┼───────┤ 17) Special Notes ├─────────┴─────────────────────────┴───────┤ Pursuant to Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, the confirmation certificate of structural safety and seismic design of the subject building . │ │ Year Month Day │ │ Author: Structural Engineer ?? Designer: Architect ?? Address: Address: Contact: Contact: └───────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] Original file: /LSW/flDownload.do?flSeq=146312469 Original file: /LSW/flDownload.do?flSeq=146312471 Original file: /LSW/flDownload.do?flSeq=146312473 ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 2] <Amended Nov. 9, 2018> ┌────────────────────────────────────────────────┐ Certificate of Structural Safety and Seismic Design (Buildings of 5 stories or less, etc.) ├─────────┬─────────────────────────────┬────────┤ 1) Project Name Remarks ├─────────┼─────────────────────────────┼────────┤ 2) Site Location / Region Coefficient ├─────────┼─────────────────────────────┤ │ 3) Purpose ├─────────┼─────────────────────────────┤ │ 4) Importance ├─────────┼───┬─────┬─────────┬─────────┤ │ 5) Scale Gross Floor Area m2 Number of Floors (Height) / ( m) ├─────────┼───┴─────┴─────────┴─────────┤ │ 6) Design Standards ├─────────┼─────────────────────────────┼────────┤ 7) Structural Planning: Establishment of a common classification system for structural systems ├─────────┼────────┬──────┬─────┬───────┼────────┤ 8) Soil and Foundation Soil Classification Groundwater Level │ ├────────┴──────┴─────┴───────┤ │ Basic Format │ ├────────┬──────┬─────┬───────┤ │ Bearing Capacity Foundation Design Bearing Capacity Pile Foundation Applicable Pile Diameter= │ │ │fe= t/m2 │ │ fp = ton │ │ ├─────────┼────────┼──────┴─────┴───────┼────────┤ 9) Overview of Seismic Design Analysis Methods Seismic Design Categories (A, B, C, D) │ │ ├────────────────────┤ │ Equivalent Static Analysis Method, Dynamic Analysis Method │ ├────────┼──────┬─────┬───────┤ │ Importance Factor IE= Building Effective W= Weight ├─────────┼────────┼──────┴───┬─┴───────┼────────┤ 10) Basic seismic force X direction Y direction to structural system Common Classification for Resistor Systems Establishment of Lateral Force Resistance System │ ├────────┼──────────┼─────────┤ │ Reaction modification factor │ ├────────┼──────────┴─────────┤ │ Allowable inter-story displacement Δax= (0.010 hs,0.015hs,0.020hs) ├─────────┼────────┼──────────┬─────────┼────────┤ 11) Key Seismic Response Coefficients for Seismic Design CSx= CSy= Result Bottom shear force VSx= VSy= │ ├────────┼──────────┼─────────┤ │ Approximate eigencycle Tax= Tay= │ ├────────┼──────────┼─────────┤ │ Maximum story displacement Δx,max Δy,max ├─────────┼────────┼──────────┼─────────┼────────┤ 12) Structural Element Seismic Special Seismic Load Piloti Presence, Absence Whether Design Review Considerations Are Applied Presence, Absence of extra-plane deviation │ │ ├──────────┼─────────┤ │ Presence or absence of vertical element for lateral force resistance Discontinuous │ ├────────┴──────────┼─────────┤ │ Vertical system discontinuity presence, absence ├─────────┼────────┬──────────┴─────────┼────────┤ 13) Non-structural elements Architectural non-structural elements Confirm during the construction phase non- Mechanical and Electrical Structural Elements Specification Non-structural element ├─────────┼────────┴────────────────────┼────────┤ 14) Special information ├─────────┴─────────────────────────────┴────────┤ │ │ Pursuant to Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, the confirmation certificate of structural safety and seismic design of the subject building . │ │ Year Month Day │ │ Author: Structural Engineer ?? Designer: Architect ?? Address: or Address: Contact: Contact: └────────────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] Original file: /LSW/flDownload.do?flSeq=146312475 Original file: /LSW/flDownload.do?flSeq=146312477 Original file: /LSW/flDownload.do?flSeq=146312479 Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Concrete Structure, Concrete Wall Structure, Steel Structure, Masonry Structure, Timber Structure, Traditional Timber Structure) ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] <Amended Feb. 12, 2020> (Chapter 1) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Concrete Structures) ┌────────┬─────────────────────────────────────────┐ 1) Construction name ├────────┼─────────────────────────────────────────┤ 2) Site location ├────────┼───────┬─────────┬────┬──────────────────┤ 3) Scale 2 stories above ground Floor height m Number of floors Basement () floors/Above ground () floors │ ├───────┼─────────┼────┼──────────────────┤ Ground Floor Height m Gross Floor Area m2 │ ├───────┼─────────┤ │ │ Basement height m ├────────┼───────┴─────────┴────┼──────────────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) * 「Small-scale building structure Standard" 5) Structural Type Laterally Restrained Frame ( ) / Unlater Restrained Frame ( ) ├────────┼───────┬─────────┬────┤ │ 6) Application Limitations Design Load Floor Dead Load Exceeded Yes / No │ │ ├─────────┼────┤ │ Presence of Floor Live Load Exceeded Yes / No │ │ ├─────────┼────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├─────────┼────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├───────┼─────────┼────┤ │ Structural Planning Presence/Absence of Discontinuities in Vertical Members │ │ ├─────────┼────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├─────────┼────┤ │ With/Without Cantilever Beam │ │ │ ├────┼──────────────────┤ Length m *Maximum 1.5m or less ├────────┼───────┼─────────┴────┼──────────────────┤ 7) Floor Plan Floor Dimensions Width: m *Aspect Ratio Height: m 1:5 or less │ ├───────┼──────────────┴──────────────────┤ Column span max m, min m │ ├───────┼─────────────────────────────────┤ Beam spacing max m, minimum m ├────────┼───────┼─────────┬────┬──────────────────┤ 8) Material Strength Concrete fck= MPa Rebar fy= MPa ├────────┼───────┼─────────┼────┼──────────────────┤ 9) Slab short side direction m Thickness mm Maximum span ├────────┼───────┼─────────┼────┴──────────────────┤ 10) Beam Classification Maximum Span (m) Section Size (mm) │ │ │ ├────┬──────────────────┤ Width Depth │ ├───────┼─────────┼────┼──────────────────┤ Small beam │ ├───────┼─────────┼────┼──────────────────┤ Big Boy │ ├───────┼─────────┼────┼──────────────────┤ small step Supporting large beam ├────────┼───────┴─────────┼────┴──────────────────┤ 11) Column Maximum Cumulative Load Area (m2) Section Size (mm) │ │ ├────┬──────────────────┤ Width Depth │ ├───────┬─────────┼────┼──────────────────┤ 2nd floor pillar │ ├───────┼─────────┼────┼──────────────────┤ 1st floor pillar │ ├───────┼─────────┼────┼──────────────────┤ Basement Column ├────────┼───────┴─────────┼────┴──────────────────┤ 12) Applicability of Foundation Reclaimed Area/Soft Soil Ground Yes / No │ ├─────────────────┼───────────────────────┤ Foundation Type/Thickness Column Bottom: / Lower part of wall: / ├────────┼───────┬─────────┴────┬──────────────────┤ 13) Shear Wall Placement Direction Total Wall Length (m) Wall Thickness (mm) │ │ ├──────┬───────┤ │ 1st floor 2nd floor │ ├───────┼──────┼───────┼──────────────────┤ Horizontal Direction │ ├───────┼──────┼───────┼──────────────────┤ Vertical orientation ├────────┼───────┼──────┴───────┼──────────────────┤ 14) Non-structural elements Architectural non-structural elements Verification during the construction phase Specify necessary non-structural elements Mechanical & Electrical Non-structural element ├────────┼───────┴──────────────┴──────────────────┤ 15) Special information ├────────┴─────────────────────────────────────────┤ In accordance with Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, I hereby submit the Certificate of Verification of Structural Safety and Seismic Design of the Building. │ │ Year Month Day │ │ Author (Designer): (Signature) │ │ Address: / Contact: └──────────────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] (Chapter 2) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Concrete Wall Structure) ┌───────┬──────────────────────────────────────────┐ 1) Construction name ├───────┼──────────────────────────────────────────┤ 2) Site location ├───────┼─────────┬───────┬────┬───────────────────┤ 3) Scale 2 stories above ground Floor height m Number of floors Basement ( ) floors/Above ground ( ) floors │ ├─────────┼───────┼────┼───────────────────┤ Ground Floor Height m Gross Floor Area m2 │ ├─────────┼───────┤ │ │ Basement height m ├───────┼─────────┴───────┴────┼───────────────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) *「Small-scale building structure Standard 5) Application Limitations Design Load Floor Dead Load Exceeded Yes / No │ │ ├───────┼────┤ │ Presence of Floor Live Load Exceeded Yes / No │ │ ├───────┼────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├───────┼────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├─────────┼───────┼────┤ │ Structural Planning Presence/Absence of Discontinuities in Vertical Members │ │ ├───────┼────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├───────┼────┤ │ With/Without Cantilever Beam │ │ │ ├────┼───────────────────┤ Length m *Maximum 1.5m or less ├───────┼─────────┼───────┴────┼───────────────────┤ 6) Floor Plan Floor Dimensions Width: m *Aspect Ratio 1:5 Vertical length: m or less │ ├─────────┼────────────┴───────────────────┤ Maximum m with concrete wall Enclosed floor area │ ├─────────┼────────────────────────────────┤ Slab short side direction max m Span ├───────┼─────────┼───────┬────┬───────────────────┤ 7) Material Strength Concrete fck= MPa Rebar fy= MPa ├───────┼─────────┼───────┼────┼───────────────────┤ 8) Slab short side direction m Thickness mm Maximum span ├───────┼─────────┼───────┴────┴───────────────────┤ 9) Beam Classification Cross-sectional Size (mm) │ │ ├───────┬────────────────────────┤ Width Depth │ ├─────────┼───────┼────────────────────────┤ Internal wall │ │ │  │ │ │ ├─────────┼───────┼────────────────────────┤ exterior wall and Stairwell Wall ├───────┼─────────┴───────┼────────────────────────┤ 10) Wall Wall Thickness (mm) Wall Ratio │ ├─────────┬───────┼────┬───────────────────┤ Interior wall 2nd floor: * See A.0206.2(3) │ ├─────────┼───────┼────┤ │ Exterior walls and 1st floor: Stairwell Wall ├───────┼─────────┴───────┼────┴───────────────────┤ 11) Applicability of Foundation Reclaimed Area/Soft Soil Ground Yes / No │ ├─────────┬───────┴────────────────────────┤ Strip Foundation Width/Thickness Minimum Width mm, Minimum Thickness mm │ │ ├────────────────────────────────┤ Max width mm, Max thickness mm ├───────┼─────────┼────────────┬───────────────────┤ 12) Non-structural elements Architectural non-structural elements Verification during the construction phase Specify necessary non-structural elements Mechanical & Electrical Non-structural element ├───────┼─────────┴────────────┴───────────────────┤ 13) Special information ├───────┴──────────────────────────────────────────┤ In accordance with Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, I hereby submit the Certificate of Verification of Structural Safety and Seismic Design of the Building. │ │ Year Month Day │ │ Author (Designer): (Signature) │ │ Address: / Contact: └──────────────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] (Chapter 3) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Steel Structure) ┌─────────┬──────────────────────────────────────────┐ 1) Construction name ├─────────┼──────────────────────────────────────────┤ 2) Site location ├─────────┼────────┬───────────────┬─────┬───────────┤ 3) Scale 2 stories above ground Floor height m Number of floors Basement () floors/Above ground () floors │ ├────────┼───────────────┼─────┼───────────┤ Ground Floor Height m Gross Floor Area m2 │ ├────────┼───────────────┤ │ │ Basement height m ├─────────┼────────┴───────────────┴─────┼───────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) * 「Small-scale building structure 기준」 5) Structural Type Laterally Restrained Frame ( ) / Unlater Restrained Frame ( ) ├─────────┼────────┬───────────────┬─────┤ │ 6) Application Limitations Design Load Floor Dead Load Exceeded Yes / No │ │ ├───────────────┼─────┤ │ Presence of Floor Live Load Exceeded Yes / No │ │ ├───────────────┼─────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├───────────────┼─────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├────────┼───────────────┼─────┤ │ Structural Planning Presence/Absence of Discontinuities in Vertical Members │ │ ├───────────────┼─────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├───────────────┼─────┤ │ With/Without Cantilever Beam │ │ │ ├─────┼───────────┤ Length m *Maximum 1.5m or less ├─────────┼────────┼───────────────┴─────┼───────────┤ 7) Floor Plan Floor Dimensions Width: m *Aspect Ratio Height: m 1:5 or less │ ├────────┼──────┬──────────────┴───────────┤ Maximum column span in m, *Maximum span is 10m or less *When exceeding 8m 0604 Lateral Restraint Frame Design Must be applied │ ├────────┼──────┼──────────────────────────┤ Beam spacing max m, *max 3.5m or less ├─────────┼────────┼──────┴──────────────────────────┤ 8) Roof Structure Structural Type Lightweight Finished Roof / Reinforced Concrete Roof │ ├────────┼─────────────────────────────────┤ Roof Type Sloped Roof / Flat Roof ├─────────┼────────┼───────────────┬─────┬───────────┤ 9) Material Strength Concrete fck= MPa Rebar fy= MPa │ ├────────┼───────────────┼─────┴───────────┤ Steel Standard: Fy= MPa ├─────────┼────────┴─────┬─────────┼─────┬───────────┤ 10) Ground floor slab short side direction maximum span m thickness mm ├─────────┼──────────────┼─────────┼─────┴───────────┤ 11) Beam Classification Maximum Span (m) H-shaped Steel Section Dimensions (mm) │ ├──────────────┼─────────┼─────────────────┤ Small beam │ ├──────────────┼─────────┼─────────────────┤ Big Bo │ ├──────────────┼─────────┼─────────────────┤ Large beam supporting small beams ├─────────┼──────────────┴─────────┼─────────────────┤ 12) Column Load Area (m2) Maximum Cross-sectional Size (mm) │ ├──────────────┬─────────┼─────────────────┤ 2nd floor pillar │ ├──────────────┼─────────┼─────────────────┤ 1st floor pillar │ ├──────────────┼─────────┼─────────────────┤ Basement reinforced concrete column ├─────────┼──────────────┴─────────┼─────────────────┤ 13) Applicability of Foundation Reclaimed Area/Soft Soil Ground Yes / No │ ├──────────────┬─────────┴─────────────────┤ Foundation Type/Thickness Column Bottom: / Lower part of wall: / ├─────────┼───────┬──────┼─────────┬──────┬──────────┤ 14) Lateral Force Resistance Element Shear Wall Presence / Absence Arrangement Direction Horizontal Direction Vertical Direction │ │ │ ├─────────┼──────┼──────────┤ Number of items per floor/Total length pieces/m pieces/m │ │ │ ├─────────┼──────┼──────────┤ Wall thickness mm mm │ ├───────┼──────┼─────────┼──────┼──────────┤ Vertical Bracing Presence / Absence Number per Floor Number Number │ │ │ ├─────────┼──────┼──────────┤ Bracing angle │ ├───────┴──────┴─────────┴──────┴──────────┤ * Refer to 0604.5 for installation standards for vertical bracing or shear walls * If not installed, design of 0605 Unlaterally Restrained Frames must be applied ├─────────┼───────┬─────────────────────────┬────────┤ 15) Non-structural elements Architectural non-structural elements during the construction phase requiring verification Mechanical & Electrical Non-structural Elements Specification Non-structural elements ├─────────┼───────┴─────────────────────────┴────────┤ 16) Special information ├─────────┴──────────────────────────────────────────┤ In accordance with Article 48 and Article 32 of the Building Act, I hereby submit the Certificate of Verification of Structural Safety and Seismic Design of the Building. │ │ Year Month Day │ │ Author (Designer): (Signature) │ │ Address: / Contact: └────────────────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] (Chapter 4) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Masonry Structure) ┌────────┬──────────────────────────────────────┐ 1) Construction name ├────────┼──────────────────────────────────────┤ 2) Site location ├────────┼─────────┬────────┬──────┬────────────┤ 3) Scale 2 stories above ground Floor height m Number of floors Basement ( ) floors/Above ground ( ) floors │ ├─────────┼────────┼──────┼────────────┤ Ground Floor Height m Gross Floor Area m2 │ ├─────────┼────────┤ │ │ Basement height m ├────────┼─────────┴────────┴──────┼────────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) *「Small-scale Building Structure Standards」 See 5) Application Limitations Design Load Floor Dead Load Exceeded Presence/Absence │ │ ├────────┼──────┤ │ Floor Live Load Exceeded / Yes │ │ ├────────┼──────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├────────┼──────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├─────────┼────────┼──────┤ │ Structural Plan Presence/Absence of Discontinuity in Upper and Lower Floor Load-Bearing Walls │ │ ├────────┼──────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├────────┼──────┤ │ With/Without Cantilever Beam │ │ │ ├──────┼────────────┤ Length m *Maximum 1.5 m or less ├────────┼─────────┼────────┴──────┴────────────┤ 6) Floor Plan Plan Size Width: m Height length: m │ ├─────────┼────────────────────────────┤ Max m2 as load-bearing wall Enclosed floor area │ ├─────────┼────────────────────────────┤ Max. length of load-bearing wall lateral support in m ├────────┼─────────┼────────┬───────────────────┤ 7) Material Strength Masonry Material Brick( ) / ALC Block( ) fm(fALC)= MPa │ ├─────────┼────────┼──────┬────────────┤ Concrete fck = MPa Mortar fg = MPa ├────────┼─────────┼──────┬─┼──────┼────────────┤ 8) Slab brick structure short side direction m thickness mm Maximum span │ ├─────────┼──────┼─┼──────┼────────────┤ ALC Structure (Panel) Max Length m Panel Thickness mm ├────────┼─────────┼──────┴─┼──────┼────────────┤ 9) Lintel beam cross-sectional size mm opening width m ├────────┼─────────┼────────┼──────┼────────────┤ 10) Perimeter beam cross-sectional size mm reinforcement m ├────────┼─────────┴────────┼──────┴────────────┤ 11) Applicable to Foundation Reclaimed Areas, Soft Soil Ground Yes / No │ ├─────────┬────────┼───────────────────┤ Strip foundation( ) Foundation wall : mm Thickness : mm │ ├─────────┼────────┼───────────────────┤ Full Foundation( ) Protrusion Length** mm Thickness : mm │ │ ├────────┤ │ **If there is a protrusion length ├────────┼─────────┴────────┴──────┬────────────┤ 12) Wall ratio 2 stories: *「Small-scale Building Structure Standards」 See 1st floor: ├────────┼───────┬─────────────────┼────────────┤ 13) Non-structural elements Architectural non-structural elements Verification during the construction phase Specify necessary non-structural elements Mechanical and Electrical Non-structural elements ├────────┼───────┴─────────────────┴────────────┤ 14) Special information ├────────┴──────────────────────────────────────┤ In accordance with Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, I hereby submit the Certificate of Structural Safety and Seismic Design. │ │ Year Month Day │ │ Author (Designer): (Signature) │ │ Address: / Contact: └───────────────────────────────────────────────┘ 210 mm × 297 mm [white paper (80 g/m2)] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] (Chapter 5) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Timber Structure) ┌─────────┬─────────────────────────────────────────────┐ 1) Construction name ├─────────┼─────────────────────────────────────────────┤ 2) Site location ├─────────┼───────┬─────────────┬───────┬───────────────┤ 3) Scale 2 stories above ground Floor height m Number of floors 1 basement floor/2 stories above ground │ ├───────┼─────────────┼───────┼───────────────┤ Ground Floor Height m Gross Floor Area m2 │ ├───────┼─────────────┤ │ │ Basement height m ├─────────┼───────┴─────────────┴───────┼───────────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) *「Small-scale Refer to "Building Structural Standards" 5) Structural Type Light Timber Structure ( ) / Heavy Timber Structure ( ) ├─────────┼───────┬─────────────┬───────┤ │ 6) Application Limitations Design Load Floor Dead Load Exceeded Yes / No │ │ ├─────────────┼───────┤ │ Presence of Floor Live Load Exceeded Yes / No │ │ ├─────────────┼───────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├─────────────┼───────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├───────┼─────────────┼───────┤ │ Structural Planning Presence/Absence of Discontinuities in Vertical Members │ │ ├─────────────┼───────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├─────────────┼───────┤ │ With/Without Cantilever Beam │ │ │ ├───┬───┼───────────────┤ Length m * Max 1.5m or less ├─────────┼───────┼───────────┬─┴───┴───┼───────────────┤ 7) Floor Plan Floor Size Circumscribed Rectangle Longest Side Length: m * Longest side 18m or less Circumscribed rectangle short side length : m * Long side:short side length ratio 3:1 or less │ ├───────┼───────┬───┴─┬───────┼───────────────┤ Vertical load support maximum m * 6m or less Structure Spacing │ ├───────┼───────┼─────┼───────┼───────────────┤ Maximum distance between load-bearing walls: m * 12m or less Distance ├─────────┼───────┼────┬──┴─────┼───────┼──────┬────────┤ 8) Structural Timber Type Species Grade ├─────┬───┼───────┼────┼────────┼───────┼──────┼────────┤ 9) Roof rafter span m Apply section dimensions (mmxmm) span table │ ├───┼───────┼────┼────────┼───────┼──────┼────────┤ Cover Type Thickness mm Nailing mm Interval ├─────┼───┼───────┼────┼────────┼───────┼──────┼────────┤ 10) Ceiling joist span m Apply section dimensions (mmxmm) span table │ ├───┼───────┼────┼────────┼───────┼──────┼────────┤ Cover Type Thickness mm Nailing mm Interval ├─────┼───┼───────┼────┼────────┼───────┼──────┼────────┤ 11) Floor joist span m Apply section dimensions (mmxmm) span table │ ├───┼───────┼────┼────────┼───────┼──────┼────────┤ Cover Type Thickness mm Nailing mm Interval ├─────┴───┼───────┴────┴────────┼───────┴──────┴────────┤ 12) Vertical Load Light Timber Structure Heavy Timber Structure Resistance structure Location Type Section Dimensions Spacing Application Span Table │ │ │ │ │(mmxmm) │(m) │ │ │ ├───┬────┬───┬────┬───┼──┼──┼─────┼────┼──────┤ 1st Floor Section Dimensions Spacing mm 1st Floor Column Stud (mmxmm) see │ ├───┼────┼───┼────┼───┼──┼──┼─────┼────┼──────┤ 2nd Floor Section Dimensions Spacing mm 2nd Floor Column Stud (mmxmm) see ├─────────┼───┴┬───┴───┴─┬──┴───┴─┬┴──┴─────┴┬───┴──────┤ 13) Load-bearing wall or direction East(mm) West(mm) South(mm) North(mm) Shear wall Length Minimum Length Length Minimum Length Length Minimum Length Length Minimum Length │ ├────┼────┼────┼───┼────┼────┼─────┼────┼─────┤ 1st floor Load-bearing wall Authorization section │ ├────┼────┼────┼───┼────┼────┼─────┼────┼─────┤ 2nd floor Load-bearing wall Authorization section ├─────────┼────┴────┴────┴───┴──┬─┴────┴─────┴────┴─────┤ 14) Applicability of Foundation Reclaimed Area/Soft Soil Ground Yes / No │ ├──────┬────┬────┬────┴┬──┬────┬──────┬───────┤ Light timber frame structure strip foundation ( ) foundation wall mm foundation mm foundation mm Thickness Thickness Width │ │ ├────┼────┴───┬─┴──┴┬───┴────┬─┴───────┤ Raft foundation ( ) Width of reinforcement section mm Depth of reinforcement section mm │ ├──────┼────┼────┬───┴─┬──┬┴───┬────┴─┬───────┤ Heavy Timber Structure Column Foundation Width mm Length mm Depth mm ├─────────┼──────┼────┴────┴─────┴──┴────┴┬─────┴───────┤ 15) Non-structural elements Architectural non-structural elements Verification during the construction phase Specify necessary non-structural elements Mechanical and Electrical Non-structural element ├─────────┼──────┴────────────────────────┴─────────────┤ 16) Special information ├─────────┴─────────────────────────────────────────────┤ In accordance with Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, I hereby submit the Certificate of Verification of Structural Safety and Seismic Design of the Building. │ │ Year Month Day │ │ Author (Designer): (Signature or Seal) │ │ Address: / Contact: └───────────────────────────────────────────────────────┘ 210㎜×297㎜[White paper (80g/㎡)] ■ Rules on Structural Standards for Buildings, etc. [Attachment Form No. 3] (Chapter 6) Certificate of Structural Safety and Seismic Design (Small-scale Buildings - Traditional Timber Structure) ┌────────┬───────────────────────────────────────────┐ 1) Construction name ├────────┼───────────────────────────────────────────┤ 2) Site location ├────────┼────────┬──────────┬────────────┬──────────┤ 3) Scale Total Height m Number of Floors Basement Floors/Ground Floors │ ├────────┼──────────┼────────────┼──────────┤ 2 stories above ground Floor height m Gross floor area m2 │ ├────────┼──────────┤ │ │ Ground floor height m │ ├────────┼──────────┤ │ │ Basement height m ├────────┼────────┴──────────┴────────────┼──────────┤ 4) Use Residential facilities ( ) / Neighborhood living facilities ( ) *「Small-scale building structure 기준」 5) Structural Type Furniture Type 3-bay Furniture Type ( ) / 5-bay Furniture Type ( ) │ ├────────┼───────────────────────┤ │ Roof load normal 4kN/m2 ( ) / Weight 6kN/m2 ( ) ├────────┼────────┼──────────┬────────────┤ │ 6) Application Limitations Design Load Floor Dead Load Exceeded Yes / No │ │ ├──────────┼────────────┤ │ Exceeding Floor Live Load Yes / No │ │ ├──────────┼────────────┤ │ Applicable to Areas Exceeding Snow Load │ │ ├──────────┼────────────┤ │ Applicable to Wind Load Excess Areas Yes / No │ ├────────┼──────────┼────────────┤ │ Structural Planning Presence/Absence of Discontinuities in Vertical Members │ │ ├──────────┼────────────┤ │ 1st & 2nd Floor Structural Type Identity Presence / Absence │ │ ├──────────┼────────────┼──────────┤ Eaves depth (horizontal projection) m *Maximum 1.5m or less │ │ ├──────────┼────────────┼──────────┤ Eave depth (horizontal projection length) m *Maximum 2.5m or less ├────────┼────────┼──────────┼──────┬─────┼─────┬────┤ 7) Floor Plan Maximum Span 3-Bay Frame Area ( ) Beam Direction m Purlin Direction m │ │ ├──────────┼──────┼─────┼─────┼────┤ 5-bay furniture area ( ) Beam direction m Purlin direction m ├────────┼────────┼─────┬────┴──────┼─────┼─────┴────┤ 8) Structural Timber Sawn Timber ( ) Species (Group) Grade │ ├────────┼─────┼───────────┼─────┼──────────┤ Laminated Wood ( ) Type Grade ├────────┼────────┼─────┼───────────┼─────┼──────────┤ 9) Structural Members Horizontal Members Larger Beams mmxmm Longitudinal Beams mmxmm (Representative Section (Width x Depth) ) Main purlin mmxmm Ridge purlin mmxmm │ │ ├─────┼───────────┼─────┼──────────┤ Eaves mmxmm Rafters (Long Rafters) mm │ ├────────┼─────┼───────────┼─────┼──────────┤ Vertical Member Column (Square) mmxmm Column (Circular) mm (Width or Diameter) ├────────┼────────┼─────┴───────────┼─────┴──────────┤ 10) Direction of Lateral Force X-direction Shear Wall (Based on 1st Floor) Y-direction Shear Wall (Based on 1st Floor) Resistor Element Type Required Length Design Length Required Length Design Length │ ├────────┼───────┼─────────┼───────┼────────┤ Earthquake load mmmm │ ├────────┼───────┼─────────┼───────┼────────┤ Wind load mmmm │ ├────────┼───────┴─────────┴───────┴────────┤ Remarks * Shear walls are calculated based on the 1st floor, and the 2nd floor is applied the same as the 1st floor. 11) Foundation Reclaimed Area/Soft Soil Ground Applicability Yes / No Foundation Type/Thickness Column Base Isolated Foundation ( ) / Raft Foundation ( ) Minimum Thickness mm Wall Base Strip Foundation ( ) / Raft Foundation ( ) Minimum Thickness mm 12) Non-structural Elements Architectural Non-structural Elements List non-structural elements requiring verification during the construction phase Mechanical/Electrical Non-structural Elements 13) Special Notes In accordance with Article 48 of the Building Act and Article 32 of the Enforcement Decree of the same Act, we hereby submit the Certificate of Structural Safety and Seismic Design of the Building. Date (Year Month Day) Author (Designer): (Signature) Address: / Contact: 210㎜×297㎜ [White Paper (80g/㎡)] Original File: /LSW/flDownload.do?flSeq=146312481 Original File: /LSW/flDownload.do?flSeq=146312483 Original File: /LSW/flDownload.do?flSeq=146312485 Original File: /LSW/flDownload.do?flSeq=146312487 Original File: /LSW/flDownload.do?flSeq=146312489 Original File: /LSW/flDownload.do?flSeq=146312491 Original File: /LSW/flDownload.do?flSeq=146312493 Original File: /LSW/flDownload.do?flSeq=146312495 ■ Rules on Structural Standards, etc. for Buildings [Attachment Form No. 4] <Newly Inserted Dec. 17, 2024> Certificate of Structural Safety I. Overview of Extension/Major Renovation Project Name Site Location Date of Construction/Major Renovation/Initial Permit (Notification) Year Month Day History of Change of Use and Maintenance Date of Initial Approval for Use Year Month Day Years Elapsed Change History Since Initial Approval for Use Status of Management Inspections Inspection Type under the "Building Management Act" Date of Recent Inspection Year Month Day Classification of Extension/Major Renovation [ ] Extension [ ] Details of Changes Due to Major Renovation Reason for Change [ ] Improvement of Fire Protection Performance [ ] Improvement of Waterproofing Performance [ ] Improvement of Thermal Insulation Performance Changes [ ] Roof [ ] Exterior Wall Finishing Materials [ ] Fire Doors/Fire Shutters [ ] Other Details of Changes in Area, Location, etc. Ⅱ. Verification Items Regarding Structural Safety Common General Information Main Use Scale Gross Floor Area (㎡) Verification Items (Before Change) Number of Floors (Height) / (m) (Mandatory Item) Main Structure [ ] Reinforced Concrete [ ] Steel Frame [ ] Wooden [ ] Masonry Roof Roof Type: [ ] Sloped Roof [ ] Flat Roof Roof Finishing Materials: [ ] RC Slab [ ] Composite Material [ ] Metal Plate [ ] Glass [ ] Roof Tiles [ ] Others ( ) Main Structural Components Change in Main Structural Components: Confirm that there are no changes to the main structural components [ ] and Structural Strength Change in Structural Strength: Confirm that the increase in structural strength of each structural member is 5% or less [ ] Dead Load due to Addition, Demolition, Repair, Change, or Expansion: Change Area (㎡) Load Change (kN/㎡) Regarding Items Extension Classification Before Change After Change Verification Items on Whether Within Allowable Tolerance Range (Fill out if applicable) Building Coverage Ratio % % Within 0.5 percent (Building Area Not exceeding 5 square meters) [ ] Floor Area Ratio % % Within 1 percent (Gross floor area not exceeding 30 square meters) [ ] Height mm Within 2 percent (Not exceeding 1 meter) [ ] Major Repairs [ ] Fire Doors Expansion, Dismantling, Repair, or Modification [ Number ] Verification Items (Fill out if applicable) [ ] Fire Shutters Expansion, Dismantling, Repair, or Modification [ Number ] [ ] Expansion·Dismantling·Repair·Change of Building Exterior Wall Finishing Materials [ ㎡] * Confirm that no heavy exterior wall finishing materials are installed [ ] ─────────┴──────────────────────────────────────────────────── Article 48 of the Building Act, Article 32, Paragraph 3 of the Enforcement Decree of the same Act, and Article 58-2 of the Rules on Structural Standards, etc. for Buildings I hereby submit the Structural Safety Confirmation Certificate in accordance with Paragraph 1. Year Month Day Submitter (Building Owner) (Signature or Seal) ────────────────────────────────────────────────────────────── Resolver: Designer (Signature or Seal) Address: Contact: ────────────────────────────────────────────────────────────── 210mm×297mm[White paper (80g/㎡) or medium paper (80g/㎡)] Original file: /LSW/flDownload.do?flSeq=146312497 Original file: /LSW/flDownload.do?flSeq=146312499 Original file: /LSW/flDownload.do?flSeq=146312501 Revision ⊙Ministry of Land, Infrastructure and Transport Decree No. 1420 The Partial Amendment to the Rules on Structural Standards, etc. for Buildings is hereby promulgated as follows. December 17, 2024 Minister of Land, Infrastructure and Transport (Seal) Partial Amendment to the Rules on Structural Standards, etc. for Buildings The Rules on Structural Standards, etc. for Buildings are partially amended as follows. In Article 3, Paragraph 2, Subparagraph 1, "Building Structural Standards" shall be changed to "Building Structural Standards (including Special Purpose Building Standards; hereinafter the same applies)." Article 58-2 is newly added as follows. Article 58-2 (Special Provisions for Submission of Structural Safety Confirmation Certificate for Expansion or Major Repair for Performance Improvement) ① A building owner who expands or majorly repairs an existing building in accordance with the following subparagraphs pursuant to the main text of the part other than each subparagraph of Article 32, Paragraph 3 of the Enforcement Decree shall submit a Structural Safety Confirmation Certificate in the form of Annex 4 when filing a report on commencement of construction pursuant to Article 21 of the Act. 1. Extension for the purpose of repairing, altering, or adding a roof or exterior wall (limited to cases where changes in the building coverage ratio, floor area ratio, and height of the building are within the permissible tolerance range pursuant to Article 26 of the Act) 2. Major repairs falling under any of the following items a. Major repairs pursuant to Subparagraph 5 of Article 3-2 of the Enforcement Decree (limited to cases where a fire door or fire shutter is installed or altered, and a part of the floor or wall for a fire compartment is repaired) B. Major repairs pursuant to Subparagraph 9 of Article 3-2 of the Enforcement Decree (limited to cases where heavy finishing materials such as bricks or stone in accordance with building structural standards are not installed on the exterior walls of a building) 3. Expansion or major repair equivalent to Subparagraph 1 or 2, as prescribed by the local government's ordinance on construction ② In Article 32, Paragraph 3, Subparagraph 2 of the Enforcement Decree, "minor change prescribed by the Ordinance of the Ministry of Land, Infrastructure and Transport" refers to a change in which the increase in structural strength according to the Building Structural Standards is 5 percent or less. In the first part of Article 60-2, Paragraph 2, "pursuant to Paragraph 1" shall be changed to "pursuant to Subparagraph 1, Item (a) of Annex 13," and the latter part of the same paragraph shall be as follows. In this case, the certificate of structural safety and seismic design pursuant to Article 58 must be submitted together. In Article 60-2, Paragraph 3, replace "shall" with "shall, and the method of indicating seismic resistance capacity shall be in accordance with Subparagraph 2 of Annex 13," and add Paragraph 4 to the same Article as follows. ④ The owner of a building who intends to calculate and disclose the seismic resistance capacity of a building that is not subject to disclosure under Article 48-3, Paragraph 1 of the Act, in the manner prescribed in Paragraph 3, shall submit data capable of verifying the seismic resistance capacity to the licensing authority in accordance with Item 1, Subparagraph (b) of Annex 13. In Article 61, "Article 91-3, Paragraph 1, Subparagraph 5 of the Enforcement Decree" shall be changed to "Article 91-3, Paragraph 1, Subparagraph 6 of the Enforcement Decree". In Item 1 of Column 1 of the Building Use and Scale section of Attached Table 11, "Telegraph and Telephone Office · Importance (Special)" shall be changed to "Telegraph and Telephone Office, Importance (Special)". Attached Table 13 is as attached. Form No. 4 attached hereto is newly established as attached. Supplementary Provisions Article 1 (Enforcement Date) This Rule shall enter into force on the date of its promulgation. Article 2 (Transitional Measures Concerning Standards for Calculating Seismic Capacity of Buildings and Methods of Disclosure) Notwithstanding the amended provisions of Article 60-2, Paragraphs 2 and 3 and Annex 13, the former provisions shall apply to the standards for calculating seismic capacity and the method of disclosure in cases where an application for approval of use under Article 22, Paragraph 1 of the Act was submitted prior to the enforcement of this Rule. <img src="http://www.law.go.kr/flDownload.do?flSeq=146270341" alt="img146270341" > </img> <img src="http://www.law.go.kr/flDownload.do?flSeq=146270343" alt="img146270343" > </img> Reason for Enactment/Amendment [Partial revision] ◇ Reasons for Amendment and Key Contents As the Enforcement Decree of the Building Act was amended (Presidential Decree No. 35082, promulgated and effective on December 17, 2024) to allow for the application of more relaxed structural safety verification methods for extensions or major repairs aimed at improving the performance of existing buildings, matters delegated by the Presidential Decree and matters necessary for its implementation are determined, such as defining the scope of extensions and major repairs to which relaxed structural safety verification methods may be applied, while This is intended to improve and supplement certain shortcomings observed in the operation of the current system, such as by improving the methods for calculating and disclosing the seismic resistance capacity of buildings, in order to promote the disclosure of the seismic resistance capacity of buildings.