Annex 9 — 고압가스 안전관리법 시행규칙

286887 · 2026-06-11

■ 고압가스 안전관리법 시행규칙 [별표 9] <개정 2026. 6. 11.> Facility, Technology, and Inspection Standards for High-Pressure Gas Sales and Import Businesses (Article 8, Paragraph 1, Subparagraph 5, 제8조제2항, 제28조제4항제5호, 제30조제3항제5호 및 제31조제3항제5호 관련) 1. 용기에 의한 고압가스 판매 가. 시설기준 1) 배치기준 가) 사업소의 부지는 한 면이 폭 4m 이상의 도로에 접할 것. 다만, 교통소통 . b) Among high-pressure gas storage facilities, the volume of high-pressure gas that can be stored is 300㎥ (liquefaction Storage facilities exceeding 3 tons of gas are protected from the outside by a protective facility (located at the business site (excluding protection facilities and protection facilities located in exclusive industrial zones) up to Annex 4 Section 1 Maintain a safe distance in accordance with Item 1)a) of Subparagraph A. ) Storage facilities shall have a detour distance of at least 2m from their outer surface to the place where fire is handled Things to maintain d) After receiving the completion inspection pursuant to Article 16, Paragraph 3 of the Act, if it is non-compliant with the standards of Subparagraph 1, Item (a) 1)b) If all of the following measures have been taken for a facility that has become compliant with the applicable standards, it shall be deemed compliant with the standards. 보다. ① 시설 변경 전과 후의 안전도에 관하여 한국가스안전공사의 평가를 받 을 것 ② ①에 따른 평가 결과에 맞게 시설을 보완할 것 2) 저장설비기준 가) 용기보관실의 벽은 불연재료(不燃材料)를 사용하고, 그 지붕은 가벼운 불연재 Use non-flammable or flame-retardant materials. However, if the licensing authority [applies] to the structure of the building In cases where it is deemed significantly difficult to install a lightweight roof, the permitting authority It must be equipped with the structure or facilities prescribed by . 나) 용기보관실 및 사무실은 한 부지 안에 구분하여 설치할 것. 다만, 해상에서 가스판매업을 하려는 경우에는 용기보관실을 해상구조물 또는 선박에 설치할 can. d) The container storage room shall be installed in a structure that prevents leaked gas from entering the office. d) Container storage rooms for flammable gases, oxygen, and toxic gases shall be installed separately, and each shall be 10㎡ or more 마) 누출된 가스가 혼합될 경우 폭발하거나 독성가스가 생성될 우려가 있는 가스의 용기보관실은 별도로 설치할 것 3) 사고예방설비기준 가) 독성가스 및 공기보다 무거운 가연성가스의 용기보관실에는 가스가 누출될 is necessary Prepare measures b) In the toxic gas cylinder storage room, even if linked to the operation of equipment that absorbs and neutralizes toxic gases Install a lock alarm device, and in the event of a toxic gas leak, to the absorption and neutralization equipment Be equipped with facilities capable of transferring ) Flammable gases (excluding ammonia, methane bromide, and gases that self-ignite in air d), electrical facilities shall be appropriate according to the installation location and the type of gas It shall have explosion-proof performance d) In the container storage room for flammable gases, ventilation holes shall be installed to prevent leaked high-pressure gas from accumulating Take necessary measures, such as equipping 4) 피해저감설비기준 가) 용기보관실의 벽은 방호벽으로 할 것 b) For facilities selling toxic gases, in the event of a toxic gas leak from such facilities, toxic gas Take necessary measures to prevent damage caused by START. 5) 부대설비기준 가) 판매시설에는 압력계 및 계량기를 갖출 것 나) 판매업소에는 용기운반자동차의 원활한 통행과 용기의 원활한 하역작업을 위하여 용기보관실 주위에 11.5㎡ 이상의 부지를 확보할 것 d) The office area shall be 9㎡ or more. 6) 표시기준 In order to ensure the safety of high-pressure gas sales facilities, where necessary, where high-pressure gas is handled So that it can be clearly identified as a facility or a facility where access by the general public is restricted 경계표지, 식별표지 및 위험표지 등 적절한 표지를 하고, 외부인의 출입을 통제할 Install appropriate boundaries so that 7) 그 밖의 기준 a) Containers, etc. installed or used in high-pressure gas sales facilities, inspected in accordance with Article 17 of the Act 받아야 하는 것인 경우에는 그 검사에 합격한 것일 것 나) 시장ㆍ군수 또는 구청장은 가목1)가)ㆍ나), 같은 목 2)라) 및 같은 목 5)나)ㆍ 다)에 해당하는 기준의 2배 이내의 범위에서 시ㆍ군 또는 구(자치구인 구를 말한다)의 특수한 상황을 고려하여 강화된 기준을 정하여 고시할 수 있다. 다만, 문화유산 보호를 위하여 필요하거나 해당 지방자치단체가 관광특구인 경우에는 산업통상부장관과 협의하여 별도의 기준을 조례로 정할 수 있다. 다) 고압가스 판매사업소 대표자와 「액화석유가스의 안전관리 및 사업법」 제3조 제2항에 따른 액화석유가스 판매사업 허가를 받은 대표자가 동일하고, 고압가스 판매시설과 액화석유가스 판매시설이 동일부지에 설치된 경우에는 고압가스 판매시설의 사무실면적은 5)다)ㆍ7)나)의 면적과 「액화석유가스의 안전관리 및 사업법 시행규칙」 별표 6 제1호가목5)가)ㆍ7)가)의 면적 중 넓은 쪽의 면적을 확보하면 5)다)ㆍ7)나)에 적합한 것으로 본다. 나. 기술기준 1) 안전유지기준 가) 용기보관장소 또는 용기는 다음의 기준에 적합하게 할 것 ① 충전용기와 잔가스용기는 각각 구분하여 용기보관장소에 놓을 것 ② 가연성가스ㆍ독성가스 및 산소의 용기는 각각 구분하여 용기보관장소에 놓을 것 ③ 용기보관장소에는 계량기 등 작업에 필요한 물건 외에는 두지 않을 것 ④ 용기보관장소의 주위 2m 이내에는 화기 또는 인화성물질이나 발화성물질을 두지 않을 것 ⑤ 충전용기는 항상 40℃ 이하의 온도를 유지하고, 직사광선을 받지 않도록 조치할 것 ⑥ 충전용기(내용적이 5L 이하인 것은 제외한다)에는 넘어짐 등에 의한 충격 및 밸브의 손상을 방지하는 등의 조치를 하고 난폭한 취급을 하지 않을 것 ⑦ 가연성가스 용기보관장소에는 방폭형 휴대용 손전등 외의 등화를 지니고 들어가 지 않을 것 나) 밸브가 돌출한 용기(내용적이 5L 미만인 용기는 제외한다)에는 고압가스를 충전한 후 용기의 넘어짐 및 밸브의 손상을 방지하는 조치를 할 것 다) 판매하는 가스의 충전용기는 외면에 그 강도를 약하게 하는 균열 또는 주름등이 없고 고압가스가 누출되지 않은 것일 것 라) 판매하는 가스의 충전용기가 검사유효기간이 지났거나, 도색이 불량한 경우에 는 그 용기충전자에게 반송할 것 마) 가연성가스 또는 독성가스의 충전용기를 인도할 때에는 가스의 누출 여부를 인수자가 보는 데서 확인할 것 2) 공급자의무기준 가) 고압가스는 「계량에 관한 법률」에 따른 법정단위로 계량한 용적 또는 질량으로 판매할 것 나) 고압가스를 공급할 때에는 수요자시설의 안전을 확보하기 위하여 필요한 안전점 검인원 및 점검장비 등을 갖추고 적절한 방법으로 점검을 할 것 다. 검사기준 1) 중간검사ㆍ완성검사ㆍ정기검사 및 수시검사의 검사항목은 시설이 적합하게 설치 또는 유지ㆍ관리되고 있는지 확인하기 위하여 다음의 검사항목으로 할 것 ┏━━━━┯━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┓ ┃검사종류│검사항목 ┃ ┠────┼────────────────────────────────────────┨ ┃가) │가목의 시설기준에 규정된 항목 중 4)가)(방호벽의 기초설치 공정으로 한정 ┃ ┃중간검사│함) ┃ ┠────┼────────────────────────────────────────┨ ┃나) │가목의 시설기준에 규정된 항목. 다만, 중간검사에서 확인된 검사항목은 제 ┃ ┃완성검사│외할 수 있다. ┃ ┠────┼────────────────────────────────────────┨ ┃다) │① 가목의 시설기준에 규정된 항목 중 해당사항 ┃ ┃정기검사│② 나목의 기술기준에 규정된 항목[1)다)ㆍ라)ㆍ마), 2)가)는 제외한다] 중 해당 ┃ ┃ │사항 ┃ ┠────┼────────────────────────────────────────┨ ┃라) │시설별 정기검사 항목 중에서 다음에 열거한 안전장치의 유지ㆍ관리 상태 중 필요한 ┃ ┃수시검사│사항과 법 제11조에 따른 안전관리규정 이행 실태 ┃ ┃ │① 독성가스 제해설비 ┃ ┃ │② 가스누출 검지경보장치 ┃ ┃ │③ 강제환기시설 ┃ ┃ │④ 안전용 접지기기, 방폭전기기기 ┃ ┃ │⑤ 그 밖에 안전관리상 필요한 사항 ┃ ┗━━━━┷━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┛ 2) 중간검사ㆍ완성검사ㆍ정기검사 및 수시검사는 시설이 검사항목에 적합한지를 명확하게 판정할 수 있는 방법으로 실시할 것 2. 배관에 의한 고압가스 판매 가. 시설기준 1) 배치기준 제1호가목1)에 따를 것 2) 기초기준 The foundations of high-pressure gas facilities shall take necessary measures to ensure they do not have a harmful effect on the facilities. shall be provided. In this case, storage tanks (referring only to those with a storage capacity of 100㎥ or 1 ton or more) The base shall be installed on the same foundation 3) 저장설비기준 a) The structure of a storage tank (including a gas holder) protects the storage tank and the storage tank , the type and temperature of the gas stored in the storage tank The degree, pressure, and the operating environment of the storage tank shall be appropriate, and the storage capacity shall be determined accordingly. 5 tons (10 tons if not flammable or toxic gas) or 500 m³ (flammable or Storage tanks and pressure vessels (reaction/destruction) of 1000 m³ or more in the case of non-toxic gases (Referring only to towers for desalination, purification, and distillation that are 5m or taller) includes earthquake occurrence In order to protect the storage tank at START, necessary measures such as measures to ensure seismic performance shall be provided, and a gas discharge device shall be installed for storing 5㎥ or more of gas b) Flammable gas storage tanks (referring only to tanks with a storage capacity of 300 m³ or 3 tons or more) and Between other combustible gas storage tanks or oxygen storage tanks, the maximum diameter of the two storage tanks maintaining a distance of more than one-quarter of the added length, etc. generated in a single storage tank Ensure that hazardous elements do not transfer to other storage tanks, and store storage tanks underground or 실내에 설치하는 경우에는 그 저장탱크 설치실 안에서의 가스폭발을 방지하기 Make necessary measures for this purpose The storage room prevents the escalation of a disaster in the event of a high-pressure gas leak from the storage room. Install so that it can be START d) For storage tanks, measures to prevent negative pressure rupture and prevent overfilling are to protect the storage tank Prepare necessary measures, such as START measures 4) 가스설비기준 가) 가스설비의 재료는 그 고압가스의 취급에 적합한 기계적 성질 및 화학적 성분을 thing that has 나) 가스설비의 구조는 고압가스를 안전하게 취급할 수 있는 적절한 것일 것 d) The strength and thickness of the gas equipment shall be appropriate for safely handling the high-pressure gas thing_is_thing 라) 가스설비의 성능은 그 고압가스를 안전하게 취급할 수 있는 적절한 것일 것 5) 배관설비기준 가) 배관의 재료는 그 고압가스의 취급에 적합한 기계적 성질 및 화학적 성분을 가지는 것일 것 나) 배관의 구조는 고압가스를 안전하게 수송할 수 있는 적절한 것일 것 다) 배관의 강도 및 두께는 그 고압가스를 안전하게 취급할 수 있는 적절한 것일 것 라) 배관의 접합은 고압가스의 누출을 방지할 수 있도록 확실한 방법으로 하고, 이를 확인하기 위하여 필요한 경우에는 비파괴시험을 할 것 마) 배관은 신축 등으로 고압가스가 누출되는 것을 방지하기 위하여 필요한 조치를 Things to prepare f) Piping shall be designed considering the characteristics of the gas being transported and the conditions of the installation environment to prevent risks Install so as not to cause any issues, and install necessary facilities for the safe maintenance and management of the piping. or make necessary measures 6) 사고예방설비기준 a) In high-pressure gas facilities, if the pressure inside the facility exceeds the normal operating pressure, immediately... Take necessary measures, such as installing a safety device capable of returning the pressure to below the operating pressure. Things to prepare b) Attached to high-risk high-pressure gas facilities (excluding those with a capacity of less than 5,000 L) 배관에는 긴급 시 가스의 누출을 효과적으로 차단할 수 있는 조치를 마련하고, 필요한 곳에는 역류 및 역화를 방지할 수 있는 적절한 장치를 설치할 것 d) In order to prevent corrosion of the storage tank or piping, necessary Prepare measures 7) 피해저감설비기준 가) 가연성가스, 독성가스 또는 산소의 액화가스 저장탱크(가연성가스 또는 산소의 Liquefied gas storage tanks with a storage capacity of 5,000 L or more, and liquefied gas storage tanks for toxic gases In the vicinity of a storage capacity of 5 tons or more), to prevent leakage in the event of a leak of liquid gas, will prepare measures to b) In the storage tank or piping, to protect the storage tank or piping, a temperature rise prevention Prepare necessary measures, such as START measures 8) 부대설비기준 To prevent abnormal situations from occurring in high-pressure gas sales facilities, and in the event of an abnormal situation 그 확대를 방지하기 위하여 압력계ㆍ비상전력설비 등 필요한 설비를 설치할 것 9) 그 밖의 기준 a) In addition to the facility standards under subparagraphs 1) through 8) of item a), the facility standards for the sale of high-pressure gas by piping are 제1호가목의 시설기준을 따를 것 b) Hydrogen products installed and used in high-pressure gas sales facilities are subject to the "Promotion of the Hydrogen Economy and Hydrogen In cases where an inspection is required pursuant to Article 44 of the Act on Safety Management, that 검사에 합격한 것일 것 d) Hydrogen products are [subject to] the Annex of the Enforcement Rules of the Act on the Promotion of the Hydrogen Economy and Hydrogen Safety Management. 5 Hydrogen gas facility standards pursuant to Subparagraph (d) of Item 1 or fuel cell installation standards pursuant to Subparagraph (f) of the same Item Meet the criteria 나. 기술기준 1) 안전유지기준 a) In areas of high-pressure gas facilities with severe vibration, measures to minimize vibration things to do 나) 고압가스설비를 이음쇠로 접속할 때에는 그 이음쇠와 접속되는 부분에 잔류 응력이 남지 않도록 조립하고 이음쇠밸브류를 나사로 조일 때에는 무리한 하중이 걸리지 않도록 하며, 상용압력이 19.6㎫ 이상이 되는 곳의 나사는 나사게이지로 검사한 것일 것 다) 가스설비에 설치한 밸브 또는 콕(조작스위치에 의하여 그 밸브 또는 콕을 개폐하는 경우에는 그 조작스위치를 말한다. 이하 “밸브등”이라 한다)에는 다음의 기준에 따라 종업원이 그 밸브등을 적절히 조작할 수 있도록 조치할 것 ① 밸브등에는 그 밸브등의 개폐방향(조작스위치에 의하여 그 밸브등이 설치된 가스설비에 안전상 중대한 영향을 미치는 밸브등에는 그 밸브등의 개폐상태를 포함한다)이 표시되도록 할 것 ② 밸브등(조작스위치에 의하여 개폐하는 것은 제외한다)이 설치된 배관에는 그 밸브등의 가까운 부분에 쉽게 알아볼 수 있는 방법으로 그 배관 내의 가스나 그 밖의 유체의 종류 및 방향이 표시되도록 할 것 ③ 조작함으로써 그 밸브등이 설치된 가스설비에 안전상 중대한 영향을 미치는 밸브등 중에서 항상 사용하지 않는 것(긴급 시에 사용하는 것은 제외한다)에는 자물쇠 채움 또는 봉인하는 등의 조치를 해 둘 것 ④ 밸브등을 조작하는 장소에는 그 밸브등의 기능 및 사용빈도에 따라 그 밸브등을 확실히 조작하는 데에 필요한 발판과 조명도를 확보할 것 라) 안전밸브 또는 방출밸브에 설치된 스톱밸브는 그 밸브의 수리 등을 위하여 특별히 필요한 때를 제외하고는 항상 완전히 열어 놓을 것 마) 산소 외의 고압가스 설비의 기밀시험이나 시운전을 할 때에는 산소 외의 고압가 스를 사용하고, 공기를 사용할 때에는 미리 그 설비 중에 있는 가연성가스를 방출한 후에 해야 하며, 온도는 그 설비에 사용하는 윤활유의 인화점 이하로 유지할 것 바) 가연성가스 또는 산소의 가스설비의 부근에는 작업에 필요한 양 이상의 연소되기 쉬운 물질을 두지 않을 것 사) 석유류ㆍ유지류 또는 글리세린은 산소압축기의 내부윤활제로 사용하지 않고, 공기압축기의 내부윤활유는 재생유가 아닌 것으로서 사용 조건에 안전성이 있는 것일 것 아) 가연성가스 또는 독성가스의 저장탱크 긴급차단장치에 딸린 밸브 외에 설치한 밸브 중 그 저장탱크의 가장 가까운 부근에 설치한 밸브는 가스를 송출하거나 옮겨 넣을 때 외에는 잠가 둘 것 자) 차량에 고정된 탱크(내용적이 2천 L 이상인 것만을 말한다)에 고압가스를 충전하거나 그로부터 가스를 옮겨 넣을 때에는 차량정지목을 설치하는 등 그 차량이 고정되도록 할 것 차) 차량에 고정된 탱크 및 용기에는 안전밸브 등 필요한 부속품이 장치되어 있어야 하며 그 부속품은 다음 기준에 적합할 것 ① 가연성가스 또는 독성가스를 충전하는 차량에 고정된 탱크 및 용기(시안화수소 의 용기 또는 24.5㎫ 이상의 압력으로 실시한 내압시험에 합격한 소방설비 또는 항공기에 비치되는 탄산가스용기는 제외한다)에는 안전밸브가 부착되어 있고 그 안전밸브의 성능이 그 탱크 또는 용기에 대한 내압시험압력의 10분의 8 이하의 압력에서 작동할 수 있는 것일 것 ② 긴급차단장치는 그 성능이 원격조작에 의하여 작동되고 차량에 고정된 탱크 또는 이에 접속하는 배관 외면의 온도가 110℃일 때에 자동적으로 작동할 수 있는 것일 것 ③ 차량에 고정된 탱크에 부착되는 밸브ㆍ안전밸브ㆍ부속배관 및 긴급차단장치는 그 내압성능 및 기밀성능이 그 탱크의 내압시험압력 및 기밀시험압력 이상의 압력으로 하는 내압시험 및 기밀시험에 합격될 수 있는 것일 것 2) 점검기준 가) 고압가스 판매설비의 사용개시 전과 사용종료 후에는 반드시 그 판매설비에 속하는 판매시설의 이상 유무를 점검하는 외에 1일 1회 이상 판매설비의 작동상 황에 대하여 점검ㆍ확인을 하고 이상이 있을 때에는 그 설비의 보수 등 필요한 조치를 할 것 나) 안전밸브[액화산소저장탱크의 경우에는 안전장치를 말하며, 액체의 열팽창으 로 인한 배관의 파열방지용 안전밸브는 제외한다. 이하 나)에서 같다] 중 압축기 의 최종단에 설치한 것은 1년에 1회 이상, 그 밖의 안전밸브는 2년에 1회 이상 조정을 하여 고압가스설비가 파손되지 않도록 적절한 압력 이하에서 작동이 되도록 할 것. 다만, 법 제4조에 따라 고압가스특정제조허가를 받은 시설에 설치된 안전밸브의 조정주기는 4년(압력용기에 설치된 안전밸브는 그 압력용기 의 내부에 대한 재검사주기)의 범위에서 연장할 수 있다. 3) 수리ㆍ청소 및 철거 기준 가스설비를 수리ㆍ청소 및 철거할 때에는 그 작업의 안전 확보를 위하여 필요한 안전수칙을 준수하고, 수리 및 청소 후에는 그 설비의 성능 유지와 작동성 확인 등 안전 확보를 위하여 필요한 조치를 마련할 것 4) 그 밖의 기준 나목 중 1)부터 3)까지의 기술기준 외에 배관에 의한 고압가스 판매의 기술기준은 제1호나목의 기술기준을 따를 것 다. 검사기준 1) 중간검사ㆍ완성검사ㆍ정기검사 및 수시검사의 검사항목은 시설이 적합하게 설치 또는 유지ㆍ관리되고 있는지 확인하기 위하여 다음의 검사항목으로 할 것 ┏━━━━┯━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┓ ┃검사종류│검사항목 ┃ ┠────┼────────────────────────────────────────┨ ┃ │ ┃ ┃ │ ┃ ┃가) │제2호가목2)(저장탱크의 기초설치 공정으로 한정함), 3)나)(저장탱크를 지 ┃ ┃중간검사│하에 매설하기 직전의 공정으로 한정함), 4)라)(가스설비의 설치가 완료되어 ┃ ┃ │내압시험을 할 수 있는 상태의 공정으로 한정함), 5)가)ㆍ나)ㆍ라)ㆍ마)ㆍ ┃ ┃ │바)(배관을 지하에 매설하는 경우 한국가스안전공사가 지정하는 부분을 매몰 ┃ ┃ │하기 직전의 공정으로 한정함) ┃ ┃ │ ┃ ┃ │ ┃ ┠────┼────────────────────────────────────────┨ ┃나) │가목의 시설기준에 규정된 항목. 다만, 중간검사에서 확인된 검사항목은 제 ┃ ┃완성검사│외할 수 있다. ┃ ┠────┼────────────────────────────────────────┨ ┃다) │① 가목의 시설기준에 규정된 항목 중 해당 사항 ┃ ┃정기검사│② 나목의 기술기준에 규정된 항목 중 해당 사항 ┃ ┠────┼────────────────────────────────────────┨ ┃라) │시설별 정기검사 항목 중에서 다음에 열거한 안전장치의 유지ㆍ관리 상태 중 필요한 ┃ ┃수시검사│사항과 법 제11조에 따른 안전관리규정 이행 실태 ┃ ┃ │① 안전밸브 ┃ ┃ │② 긴급차단장치 ┃ ┃ │③ 독성가스 제해설비 ┃ ┃ │④ 가스누출 검지경보장치 ┃ ┃ │⑤ 물분무장치(살수장치포함) 및 소화전 ┃ ┃ │⑥ 긴급이송설비 ┃ ┃ │⑦ 강제환기시설 ┃ ┃ │⑧ 안전제어장치 ┃ ┃ │⑨ 운영상태 감시장치 ┃ ┃ │⑩ 안전용 접지기기, 방폭전기기기 ┃ ┃ │⑪ 그 밖에 안전관리에 필요한 사항 ┃ ┗━━━━┷━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┛ 2) 중간검사ㆍ완성검사ㆍ정기검사 및 수시검사는 시설이 검사항목에 적합한지 여부 를 명확하게 판정할 수 있는 방법으로 실시할 것