Form 27 — 액화석유가스의 안전관리 및 사업법 시행규칙
282369 · 2026-01-02
■ Enforcement Rules of the Act on Safety Management and Business of Liquefied Petroleum Gas [Form No. 27] <Amended Oct. 10, 2023>
Consuming Equipment Safety Inspection Checklist
Inspection Date: Year month day
1. Facility Status
┌─────────┬───┬─────┬───┬───────┬─────┬────┬────────┬─────┐
│Plumbing │Steel Pipe │ A, m │Dongguan │ A, m │Hose │ m │Other matters( )│ A, m │
├─────────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│Intermediate Valve │ballValve│ open│Fusecock│ open │Hosecock │ open │Other matters( )│ open│
├─────────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│Other Matters │ │ │ │ │ │ │ │ │
├────┬────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│combustor │range │29 │ open│39 │ open │Oven Range│ open │Other matters( )│ open│
│ │ │range│ │range│ │ │ │ │ │
│ ├────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│ │Boiler │Format │FF,FE,CF │Location │Indoor,Outdoor,Exclusive│GasConsumption│ ㎏/h │Contractor │ │
│ ├────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│ │Water heater │format │FF,FE,CF │Location │Indoor, Outdoor │GasConsumption│ ㎏/h │Contractor │ │
│ ├────┼───┼─────┼───┼───────┼─────┼────┼────────┼─────┤
│ │Other │ │ │ │ │ │ │ │ │
│ │Matters │ │ │ │ │ │ │ │ │
└────┴────┴───┴─────┴───┴───────┴─────┴────┴────────┴─────┘
2. Inspection result
┌─────────┬─────────────────────────────────────────┬─────┐
│Category │InspectionDetails │Judgment │
├─────────┼─────────────────────────────────────────┼─────┤
│Gas Leak Inspection │ a. From the gas meter outlet (container outlet in the case of weight sales) to the piping, hose, and burner │Red │
│ │Check for gas leakage and sealing measures at each connection point │ │
├────┬────┼─────────────────────────────────────────┼─────┤
│Gas │Inspection │ B. Presence or absence of the Korea Gas Safety Agency approval mark or Korean Industrial Standard (KS) inspection mark on gas appliances │Red │
│Supplies ├────┼─────────────────────────────────────────┼─────┤
│Status │Intermediate Valve│ c. Whether a fuse cock, box cock or an equivalent or better safety device is installed for each combustion appliance │Red │
│Check ├────┼─────────────────────────────────────────┼─────┤
│ │Hose │ d. Compliance with the prohibition on "T" type connections and hose clamp connections │Red │
│ ├────┼─────────────────────────────────────────┼─────┤
│ │Combustor │ E. Compliance with regulations prohibiting the installation of boilers and water heaters in bathhouses or restrooms │Red │
│ │ ├─────────────────────────────────────────┼─────┤
│ │ │ B. Boiler in a dedicated boiler room (closed-type boiler or boiler installed outdoors is subject to │Accumulation·Department │
│ │ │etc.) installed │ │
│ │ ├─────────────────────────────────────────┼─────┤
│ │ │ Company. Products with exhaust pipes that have received performance certification from the Korea Gas Safety Agency or an accredited testing institution │Red │
│ │ │whether the required condition is satisfied │ │
│ │ ├─────────────────────────────────────────┼─────┤
│ │ │ A. Gas boiler and gas water heater and exhaust pipe, and whether the exhaust pipe is detached │Red │
├────┴────┼─────────────────────────────────────────┼─────┤
│Other Matters │ J. Whether the container is installed (stored) indoors │Red │
│ ├─────────────────────────────────────────┼─────┤
│ │ d. The piping from the pressure regulator to the intermediate valve shall be reinforced in accordance with Item 1, Subparagraph (a) 4)d) of Attached Table 20 │Red │
│ │Whether it is installed with pipes, copper pipes, or metal flexible hoses, etc. │ │
│ ├─────────────────────────────────────────┼─────┤
│ │ K. Whether a carbon monoxide alarm is installed │Red │
│ ├─────────────────────────────────────────┼─────┤
│ │ T. Whether there is any other risk of causing a gas accident │Red │
├─────────┼─────────────────────────────────────────┼─────┤
│of gas appliances │ Part. Whether the recommended service period of the pressure regulator, high-pressure hose, low-pressure hose, fuse cock, and gas boiler has expired│Red │
│Recommended Usage Period │ │ │
└─────────┴─────────────────────────────────────────┴─────┘
┌─────────┬───────────────────────────────────────────────┐
│ImprovementNotice │ │
│ │ │
│ │ │
│ │ │
│ │※ The piping from the pressure regulator to the intermediate valve shall be in accordance with Item 1, Subparagraph (a), 4)d) of Attached Table 20, steel pipe/copper │
│ │Houses not installed with pipes or metal flexible hoses must, by December 31, 2030, [require] the relevant │
│ │piping. │
└─────────┴───────────────────────────────────────────────┘
┌─────────┬───────────────────────────────────────────────┐
│Gas Appliance Replacement │ │
│Recommendations │ │
└─────────┴───────────────────────────────────────────────┘
┌────┬─────────────────────┐┌────┬────────────────────────┐
│Gas │ Business Name: ││Consumer │ Trade Name: │
│Supplier │ Address: ││ │ Address: │
│ │ Telephone Number: ││ │ Telephone Number: │
│ │ Inspector Name: (Signature or seal) ││ │ Name: (Signature or seal) │
└────┴─────────────────────┘└────┴────────────────────────┘
※ Insurance benefits cannot be received if a gas accident occurs while facilities are not improved within the improvement period.