Standards for the Storage and Handling of Special Combustible Materials (Related to Article 19, Paragraph 2)
Standards for Storage and Handling of Special Combustible Materials
Special combustible materials must be stacked and stored in accordance with the standards of each of the following items. However, coal and charcoal...
is stored for power generation are excluded.
a. Stack separated by product name
B. Stack according to the following criteria
┌────┬──────────────┬─────────────┐
│Classification │install sprinkler system or │In other cases │
│ │Corresponds to radioactivity range │ │
│ │to include special combustible materials │ │
│ │Installing a large manual fire extinguisher │ │
│ │case │ │
├────┼──────────────┼─────────────┤
│Height │15 meters or less │10 meters or less │
├────┼──────────────┼─────────────┤
│Stacking │200 square meters (of coal and charcoal │50 square meters (of coal and charcoal │
│in the START section of MTQ721e3ceef283e77000385 │, 300 square meters or less │, 200 square meters or less│
│Floor Area│ │ │
└────┴──────────────┴─────────────┘
. In the case of outdoor stacking for storage, the stacked portion must meet the site boundary, road, and adjacent buildings
Maintain a gap of at least 6 meters. However, for "construction" that is at least 0.9 meters higher than the stacking height...
A wall of a fire-resistant structure (hereinafter referred to as “fire-resistant structure”) pursuant to Article 2, Subparagraph 7 of the Enforcement Decree of the Act
case.
d. In the case of stacked storage indoors, the main structural components must be fire-resistant and made of non-combustible materials,
Do not store in the same space as other types of special combustible materials. However, fire-resistant walls
.
E. The gap between the floor areas of the stacked parts shall be 1.2 meters in the case of indoors, or 1/2 of the stacking height.
A spacing greater than the larger value must be maintained, and for outdoor areas, 3 meters or the stacking height, whichever is greater, must be maintained.
value
2. Special Combustible Material Marking
a. In places where special combustible materials are stored or handled, the product name, maximum storage quantity, and per unit volume
Mass or mass per unit volume, name and position of manager, contact information, and prohibition on handling fire
Special combustible material signs including a START indicator must be installed.
B. The specifications for special combustible material labels are as follows.
┌────────────────┐
│Special Combustible Material │
├────────────────┤
│No Open Flames │
├─────────┬──────┤
│Product Name │Synthetic resins │
├─────────┼──────┤
│MaximumStorageQuantity │000 tons (00 times) │
│(multiple) │ │
├─────────┼──────┤
│Mass per unit volume │000kg/㎥ │
│(Mass per unit volume) │ │
├─────────┼──────┤
│Manager │Team Leader Hong Gil-dong │
│( book) │ │
├─────────┼──────┤
│Contact │02-000-0000 │
└─────────┴──────┘
1) Special combustible material signs, with one side length of 0.3 meters or more and the other side length of 0.6 meters
Make it a rectangle of at least
2) The background of the special combustible material sign shall be white, and the text shall be black. However, “fire
Exclude the section marked “STOP”.
3) Among special combustible material signs, the background of the "Strictly No Open Fire" mark is red, and the text is white
Set to START
. The special combustible material sign must be in an easily visible place among the locations where special combustible materials are stored or handled
.