Annex 2 — 방송통신설비의 기술기준에 관한 규정

263865 · 2024-07-19

■ Regulations on Technical Standards for Broadcasting and Telecommunications Facilities [Appendix 2] <Amended Apr. 25, 2017> Standards for Securing In-house Telecommunications Room Area in Commercial Buildings (Related to Article 19, Subparagraphs 1 and 3) ┏━━━━━━━━┯━━━━━━━━┯━━━━━━━━━━━━━━━━━━━━┓ ┃Building Scale │TargetForSecure │Secured Area ┃ ┠────────┼────────┼────────────────────┨ ┃1. 6th floor or higher and │a. Concentrated Internal Communication│At least one location of 10.2 square meters or more ┃ ┃Gross floor area 5,000 square meters │room │ ┃ ┃Meter or higher business ├────────┼────────────────────┨ ┃Dance Architecture │B. Floor Communication Room│ 1) Exclusive area of ​​1,000 square meters or more per floor ┃ ┃ │ │, 10.2 square meters per floor ┃ ┃ │ │or higher, at least 1 location ┃ ┃ │ │ 2) Exclusive area of ​​800 square meters or more per floor ┃ ┃ │ │, 8.4 square meters per floor ┃ ┃ │ │via ┃ ┃ │ │ 3) Exclusive area of ​​500 square meters or more per floor ┃ ┃ │ │, 6.6 square meters per floor ┃ ┃ │ │via ┃ ┃ │ │ 4) Exclusive area per floor is less than 500 square meters ┃ ┃ │ │, 5.4 square meters per floor ┃ ┃ │ │via ┃ ┠────────┼────────┼────────────────────┨ ┃2. Business other than Item 1│Centralized Communications Room │In cases where the gross floor area of ​​a building is 500 square meters or more ┃ ┃Dance Architecture │ │At least one location of 10.2 square meters or more. ┃ ┃ │ │cases less than 500 square meters, 5.4 square meters ┃ ┃ │ │or more than 1 location. ┃ ┗━━━━━━━━┷━━━━━━━━┷━━━━━━━━━━━━━━━━━━━━┛ Remarks 1. In cases where a centralized in-building telecommunications room and a floor in-building telecommunications room must be secured on the same floor, the centralized Only the telecommunications room within Jung-gu can be secured. 2. In cases where the exclusive area per floor is less than 500 square meters, secure a communication room for each floor In cases where it is difficult to [do this], communication facilities for two or more floors [do this] are connected to a single floor communication room can be combined to accommodate each. In this case, the secured area for the in-floor telecommunications room is the integrated area accommodated for each By adding the exclusive areas of the floors, the standard for the secured area of ​​the in-floor telecommunications room in Item 1 of the table above . 3. If you intend to separate and install the floor-level telecommunications room into two or more locations on the same floor, the floor-level The area of ​​the internal communications room must be at least 5.4 square meters. 4. The centralized in-building communications room must be located on the ground floor with minimal impact from the external environment. However, In cases where securing the ground is difficult due to unavoidable circumstances, if there is no risk of flooding and moisture... . 5. The centralized in-building communications room shall be equipped with lighting facilities and power supply facilities dedicated to communications equipment. 6. The area of ​​each communication room shall be the area excluding walls, pillars, etc. 7. A locking device must be installed at the entrance of the centralized internal communications room.