Annex 7 — 위험물안전관리법 시행령
287381 · 2026-07-01
■ Enforcement Decree of the Dangerous Goods Safety Management Act [Table 7] <Amended Jan. 5, 2021>
Technical Capabilities, Facilities, and Equipment of Tank Testers (Related to Article 14, Paragraph 1)
1. Technical ability
A. Essential Personnel
1) At least one person among Master Craftsman in Hazardous Materials, Industrial Technician in Hazardous Materials, or Craftsman in Hazardous Materials
2) At least one Professional Engineer in Non-Destructive Testing or Ultrasonic Non-Destructive Testing/Magnetic Non-Destructive Testing
At least one Engineer or Industrial Engineer for each of START and Penetration Non-Destructive Testing
b. Personnel to be stationed when necessary
1) For filling/hydraulic pressure tests, vacuum tests, airtightness tests or withstand pressure tests: non-destructive leakage
Inspection Engineer, Industrial Engineer, or Craftsman
2) For verticality and horizontality tests: Professional Engineer, Engineer, and Industrial Engineer in Surveying and Geospatial Information
or Surveying Technician
3) For radiographic testing: Technician or Industrial Technician of Radiographic Non-Destructive Testing
4) Assistance with essential personnel: Radiographic non-destructive testing · Ultrasonic non-destructive testing · Magnetic non-destructive testing
or Penetration Non-Destructive Testing Technician
2. Facilities: Private Office
3. Equipment
a. Essential equipment: Magnetic particle detector, ultrasonic thickness gauge, and any of the following 1) or 2)
는 하나
1) Imaging Ultrasound Tester
2) Radiographic testing machine and ultrasonic testing machine
or. Equipment to be placed when necessary
1) In the case of filling/hydraulic pressure test, vacuum test, airtightness test or internal pressure test
a) Vacuum leak tester with a vacuum capacity of 53KPa or higher
b) Airtightness test device (equipped with a safety device and having a pressurization capacity of 200KPa or more,
In the case of pressure reduction, as follows: pressure reduction capability of 10KPa or more and sensitivity of 10Pa or less.
, capable of recording each pressure change independently)
2) For verticality and horizontality tests: Verticality and horizontality measuring instrument
※ Note: In the case of equipment having two or more functions, each
equipment.