■ Enforcement Decree of the Act on Installation and Management of Firefighting Facilities [Appendix 5] <Amended Dec. 31, 2024>
Criteria for Exemption from Installation of Firefighting Facilities in Specific Firefighting Targets (Related to Article 14)
┌──────────┬────────────────────────────┐
│installation exempted │Criteria for Installation Exemption │
│FirefightingFacility │ │
├──────────┼────────────────────────────┤
│1. Automatic fire extinguishing device │Automatic fire extinguishing system (residential kitchen automatic fire extinguishing system and commercial kitchen automatic fire extinguishing system │
│ │Specific fire safety targets that must install (excluding fire extinguishing devices) │
│ │with water spray fire extinguishing systems installed in accordance with fire safety standards │
│ │, the effective range of the equipment (where the relevant fire extinguishing facility detects fire │
│ │Refers to a part capable of fire suppression, extinguishing, or alarming. The same applies hereinafter) │
│ │. │
├──────────┼────────────────────────────┤
│2. Indoor Fire Hydrant System │The head of the fire department or the fire station chief [regarding] the installation of indoor fire hydrant facilities │
│ │as a case recognized as a hose reel type fine mist fire extinguishing theory │
│ │Install fire or outdoor fire hydrant systems in accordance with fire safety standards. │
│ │, installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│3. Sprinkler System │a. Specific fire safety targets requiring the installation of sprinkler systems (Power generation │
│ │Automatic suitable for (excluding electrical storage facilities among facilities) │
│ │Fire extinguishing devices or water spray fire extinguishing systems conform to fire safety standards │
│ │In the case where it is installed in such a way that the installation is within the effective range of the equipment │
│ │is exempt. │
│ │b. In electrical storage facilities where sprinkler systems must be installed, fire extinguishing │
│ │facilities installed in accordance with the method prescribed and notified by the Commissioner of the Fire Department │
│ │, installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│4. Simple Sprinkler │Specific fire safety targets required to install simplified sprinkler systems │
│Equipment │sprinkler systems, water spray fire extinguishing systems or fine mist fire extinguishing systems │
│ │If installed in compliance with fire safety standards, the use of the equipment │
│ │. │
├──────────┼────────────────────────────┤
│5. Water spray extinguishing method │In garages and parking lots where water spray fire extinguishing systems must be installed, spray │
│B │If the rinkler system is installed in accordance with fire safety standards │
│ │Installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│6. Outdoor Fire Hydrant System │Wooden buildings that are cultural heritage requiring the installation of outdoor fire hydrant systems │
│ │, water supply fire extinguishing facilities as specified in the fire safety standards │
│ │Compliant with standards for pressure, water discharge volume, outdoor fire hydrant cabinets, and hoses │
│ │has been installed, installation is waived. │
├──────────┼────────────────────────────┤
│7. Emergency Alarm System │For specific fire safety targets requiring the installation of emergency alarm systems, a standalone alarm │
│ │By linking a START-type detector with two or more standalone alarm-type detectors, │
│ │is installed, installation is exempted within the effective range of the equipment │
│ │. │
├──────────┼────────────────────────────┤
│8. Emergency alarm system also │for which emergency alarm equipment or stand-alone alarm type detectors must be installed │
│is a standalone alarm type sensor │Automatic fire detection equipment or fire alarm equipment for specific fire-protected buildings │
│Keeper │If installed in compliance with fire safety standards, the use of the equipment │
│ │. │
├──────────┼────────────────────────────┤
│9. Automatic Fire Detection System │Functions of automatic fire detection equipment (referring to detection, reception, and alarm functions) │
│B │and performance │
│ │In the case where a non-light fire extinguishing system is installed in accordance with fire safety standards │
│ │is exempt from installation within the effective range of the facility. │
├──────────┼────────────────────────────┤
│10. Fire Alarm System │Automation │
│ │If the fire detection system is installed in accordance with fire safety standards │
│ │Installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│11. Emergency Broadcasting Equipment │For specific fire safety targets requiring the installation of emergency broadcasting facilities, automation │
│ │Acoustic sound of the same level or higher than that of a re-detection system or emergency alarm system │
│ │Broadcasting facilities equipped with a device emitting START that comply with fire safety standards │
│ │In the case where it is installed in a combined manner, the installation within the effective range of the equipment │
│ │is exempt. │
├──────────┼────────────────────────────┤
│12. Automatic Fire Alarm Installation │Specific fire safety targets required to install automatic fire alarm systems │
│B │If the re-notification system is installed in accordance with fire safety standards, │
│ │Installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│13. Leakage Alarm │Specific fire safety targets or their parts requiring the installation of leakage alarms │
│ │section regarding arc alarm (break or line damage of indoor distribution lines, etc. │
│ │으로 인하여 발생하는 아크를 감지하고 경보하는 장치를 │
│ │(referring to) or installing a ground fault circuit breaker in accordance with electrical regulations │
│ │In the case of installation, installation is exempted within the effective range of the equipment. │
├──────────┼────────────────────────────┤
│14. Evacuation and Rescue Equipment │The location of specific fire safety targets required to install evacuation and rescue facilities │
│ │ㆍIf there is no impediment to evacuation depending on the condition of the structure or facilities │
│ │In cases where it is recognized, in accordance with the fire safety standards │
│ │Installation is waived. │
├──────────┼────────────────────────────┤
│15. Emergency Lighting │Specific fire safety targets required to install emergency lighting, equipped with escape routes │
│ │guide lights or passageway guide lights installed in accordance with fire safety standards │
│ │, installation is exempted within the effective range of that exit sign. │
├──────────┼────────────────────────────┤
│16. Water supply fire extinguishing water │A. Specific fire safety targets requiring the installation of water supply fire extinguishing facilities │
│Equipment │public place │
│ │Fire hydrants for the room are installed in accordance with fire safety standards. │
│ │is present. │
│ │b. The head of the fire department or the fire station chief [regarding] the installation of water supply fire extinguishing facilities │
│ │In cases where it is recognized that it is difficult to meet the requirements of the fire safety standards, │
│ │A combined fire water tank or reservoir is installed, or installed │
│ │In the case of installation, installation within the effective range of the equipment is exempted. │
│ │becomes. │
├──────────┼────────────────────────────┤
│17. Smoke control equipment │A. Specific fire safety targets required to install smoke control systems [Attached Table 4 No. 5 │
│ │] Any of the following │
│ │Installation is exempted if the START facility is installed. │
│ │ 1) Air conditioning equipment shall comply with the smoke control equipment standards of the Fire Safety Standards │
│ │Installed in combination and in the event of a fire, the air conditioning system smoke control system │
│ │In the case where it is installed with a structure that automatically switches to the START function │
│ │ 2) The total area of exhaust outlets directly connected to the outside air │
│ │Relevant smoke control area[Smoke control boundary(ceiling that is part of the smoke control system │
│ │refers to a space within a building partitioned by (including)] │
│ │is at least 1/100 of the floor area, and from the discharge port each part │
│ │The horizontal distance to the START is within 30m, and the air inlet is fire │
│ │In compliance with safety standards (direct natural intake of outside air │
│ │, the size of the inlet must be greater than or equal to the size of the outlet │
│ │) If installed │
│ │b. Those required to install smoke control equipment in accordance with Item 5, Subparagraph (a) 7) of Annex 4 │
│ │Special escape stairs connected to a balcony among specific fire safety target buildings, │
│ │An elevator landing of an emergency elevator with a balcony installed or the "Building Act │
│ │Smoke exhaust facilities are installed in accordance with the standards of Subparagraph 5 of Article 91 of the Enforcement Decree. │
│ │Installation is exempted at the landing of an evacuation elevator. │
├──────────┼────────────────────────────┤
│18. Connecting Water Supply System │For fire-protected buildings requiring the installation of connected water supply facilities, outdoors │
│ │Indoor fire hydrant system with a water supply outlet and a water discharge outlet installed indoors, │
│ │sprinkler system, simplified sprinkler system or connected sprinkler system │
│ │If installed in compliance with fire safety standards, the use of the equipment │
│ │Installation is exempted within the effective range. However, from the ground surface to the top floor room │
│ │It must be installed if the height of the water outlet is 70m or more. │
├──────────┼────────────────────────────┤
│19. Connected Sprinkler System │a. Water supply to specific fire-protected buildings requiring the installation of connected sprinkler systems │
│ │Sprinkler system with installed START outlets, simplified sprinkler system, water spray │
│ │A non-fire extinguishing system or a fine mist fire extinguishing system in accordance with fire safety standards │
│ │In the case of combined installation, within the effective range of the equipment │
│ │is waived. │
│ │b. water spray devices, etc. installed in accordance with gas-related laws and regulations │
│ │is installed or water │
│ │A water source capable of supplying weapons systems, etc., for more than 6 hours is │
│ │Installation is exempted if secured. │
├──────────┼────────────────────────────┤
│20. Wireless communication auxiliary setup │to specific fire safety targets required to install wireless communication auxiliary facilities this │
│B │Mobile communication in-house repeater line equipment or wireless mobile repeater (「Former │
│ │Applicable only to products that have undergone conformity assessment pursuant to Article 58-2 of the "Small Act" │
│ │(etc. comply with the wireless communication auxiliary equipment standards of the fire safety standards) │
│ │Installation is exempted if installed as . │
├──────────┼────────────────────────────┤
│21. Combustion Prevention Equipment │Spring for specific fire-fighting targets required to install combustion prevention equipment │
│ │Clamping equipment, water spray fire extinguishing equipment or fine mist fire extinguishing equipment for fire prevention │
│ │If installed in compliance with all standards, the effective range of the equipment │
│ │. │
└──────────┴────────────────────────────┘