Annex 5 — 소방시설 설치 및 관리에 관한 법률 시행령

287375 · 2026-07-01

■ Enforcement Decree of the Act on Installation and Management of Firefighting Facilities [Appendix 5] <Amended Dec. 31, 2024> Criteria for Exemption from Installation of Firefighting Facilities in Specific Firefighting Targets (Related to Article 14) ┌──────────┬────────────────────────────┐ │installation exempted │Criteria for Installation Exemption │ │FirefightingFacility │ │ ├──────────┼────────────────────────────┤ │1. Automatic fire extinguishing device │Automatic fire extinguishing system (residential kitchen automatic fire extinguishing system and commercial kitchen automatic fire extinguishing system │ │ │Specific fire safety targets that must install (excluding fire extinguishing devices) │ │ │with water spray fire extinguishing systems installed in accordance with fire safety standards │ │ │, the effective range of the equipment (where the relevant fire extinguishing facility detects fire │ │ │Refers to a part capable of fire suppression, extinguishing, or alarming. The same applies hereinafter) │ │ │. │ ├──────────┼────────────────────────────┤ │2. Indoor Fire Hydrant System │The head of the fire department or the fire station chief [regarding] the installation of indoor fire hydrant facilities │ │ │as a case recognized as a hose reel type fine mist fire extinguishing theory │ │ │Install fire or outdoor fire hydrant systems in accordance with fire safety standards. │ │ │, installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │3. Sprinkler System │a. Specific fire safety targets requiring the installation of sprinkler systems (Power generation │ │ │Automatic suitable for (excluding electrical storage facilities among facilities) │ │ │Fire extinguishing devices or water spray fire extinguishing systems conform to fire safety standards │ │ │In the case where it is installed in such a way that the installation is within the effective range of the equipment │ │ │is exempt. │ │ │b. In electrical storage facilities where sprinkler systems must be installed, fire extinguishing │ │ │facilities installed in accordance with the method prescribed and notified by the Commissioner of the Fire Department │ │ │, installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │4. Simple Sprinkler │Specific fire safety targets required to install simplified sprinkler systems │ │Equipment │sprinkler systems, water spray fire extinguishing systems or fine mist fire extinguishing systems │ │ │If installed in compliance with fire safety standards, the use of the equipment │ │ │. │ ├──────────┼────────────────────────────┤ │5. Water spray extinguishing method │In garages and parking lots where water spray fire extinguishing systems must be installed, spray │ │B │If the rinkler system is installed in accordance with fire safety standards │ │ │Installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │6. Outdoor Fire Hydrant System │Wooden buildings that are cultural heritage requiring the installation of outdoor fire hydrant systems │ │ │, water supply fire extinguishing facilities as specified in the fire safety standards │ │ │Compliant with standards for pressure, water discharge volume, outdoor fire hydrant cabinets, and hoses │ │ │has been installed, installation is waived. │ ├──────────┼────────────────────────────┤ │7. Emergency Alarm System │For specific fire safety targets requiring the installation of emergency alarm systems, a standalone alarm │ │ │By linking a START-type detector with two or more standalone alarm-type detectors, │ │ │is installed, installation is exempted within the effective range of the equipment │ │ │. │ ├──────────┼────────────────────────────┤ │8. Emergency alarm system also │for which emergency alarm equipment or stand-alone alarm type detectors must be installed │ │is a standalone alarm type sensor │Automatic fire detection equipment or fire alarm equipment for specific fire-protected buildings │ │Keeper │If installed in compliance with fire safety standards, the use of the equipment │ │ │. │ ├──────────┼────────────────────────────┤ │9. Automatic Fire Detection System │Functions of automatic fire detection equipment (referring to detection, reception, and alarm functions) │ │B │and performance │ │ │In the case where a non-light fire extinguishing system is installed in accordance with fire safety standards │ │ │is exempt from installation within the effective range of the facility. │ ├──────────┼────────────────────────────┤ │10. Fire Alarm System │Automation │ │ │If the fire detection system is installed in accordance with fire safety standards │ │ │Installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │11. Emergency Broadcasting Equipment │For specific fire safety targets requiring the installation of emergency broadcasting facilities, automation │ │ │Acoustic sound of the same level or higher than that of a re-detection system or emergency alarm system │ │ │Broadcasting facilities equipped with a device emitting START that comply with fire safety standards │ │ │In the case where it is installed in a combined manner, the installation within the effective range of the equipment │ │ │is exempt. │ ├──────────┼────────────────────────────┤ │12. Automatic Fire Alarm Installation │Specific fire safety targets required to install automatic fire alarm systems │ │B │If the re-notification system is installed in accordance with fire safety standards, │ │ │Installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │13. Leakage Alarm │Specific fire safety targets or their parts requiring the installation of leakage alarms │ │ │section regarding arc alarm (break or line damage of indoor distribution lines, etc. │ │ │으로 인하여 발생하는 아크를 감지하고 경보하는 장치를 │ │ │(referring to) or installing a ground fault circuit breaker in accordance with electrical regulations │ │ │In the case of installation, installation is exempted within the effective range of the equipment. │ ├──────────┼────────────────────────────┤ │14. Evacuation and Rescue Equipment │The location of specific fire safety targets required to install evacuation and rescue facilities │ │ │ㆍIf there is no impediment to evacuation depending on the condition of the structure or facilities │ │ │In cases where it is recognized, in accordance with the fire safety standards │ │ │Installation is waived. │ ├──────────┼────────────────────────────┤ │15. Emergency Lighting │Specific fire safety targets required to install emergency lighting, equipped with escape routes │ │ │guide lights or passageway guide lights installed in accordance with fire safety standards │ │ │, installation is exempted within the effective range of that exit sign. │ ├──────────┼────────────────────────────┤ │16. Water supply fire extinguishing water │A. Specific fire safety targets requiring the installation of water supply fire extinguishing facilities │ │Equipment │public place │ │ │Fire hydrants for the room are installed in accordance with fire safety standards. │ │ │is present. │ │ │b. The head of the fire department or the fire station chief [regarding] the installation of water supply fire extinguishing facilities │ │ │In cases where it is recognized that it is difficult to meet the requirements of the fire safety standards, │ │ │A combined fire water tank or reservoir is installed, or installed │ │ │In the case of installation, installation within the effective range of the equipment is exempted. │ │ │becomes. │ ├──────────┼────────────────────────────┤ │17. Smoke control equipment │A. Specific fire safety targets required to install smoke control systems [Attached Table 4 No. 5 │ │ │] Any of the following │ │ │Installation is exempted if the START facility is installed. │ │ │ 1) Air conditioning equipment shall comply with the smoke control equipment standards of the Fire Safety Standards │ │ │Installed in combination and in the event of a fire, the air conditioning system smoke control system │ │ │In the case where it is installed with a structure that automatically switches to the START function │ │ │ 2) The total area of ​​exhaust outlets directly connected to the outside air │ │ │Relevant smoke control area[Smoke control boundary(ceiling that is part of the smoke control system │ │ │refers to a space within a building partitioned by (including)] │ │ │is at least 1/100 of the floor area, and from the discharge port each part │ │ │The horizontal distance to the START is within 30m, and the air inlet is fire │ │ │In compliance with safety standards (direct natural intake of outside air │ │ │, the size of the inlet must be greater than or equal to the size of the outlet │ │ │) If installed │ │ │b. Those required to install smoke control equipment in accordance with Item 5, Subparagraph (a) 7) of Annex 4 │ │ │Special escape stairs connected to a balcony among specific fire safety target buildings, │ │ │An elevator landing of an emergency elevator with a balcony installed or the "Building Act │ │ │Smoke exhaust facilities are installed in accordance with the standards of Subparagraph 5 of Article 91 of the Enforcement Decree. │ │ │Installation is exempted at the landing of an evacuation elevator. │ ├──────────┼────────────────────────────┤ │18. Connecting Water Supply System │For fire-protected buildings requiring the installation of connected water supply facilities, outdoors │ │ │Indoor fire hydrant system with a water supply outlet and a water discharge outlet installed indoors, │ │ │sprinkler system, simplified sprinkler system or connected sprinkler system │ │ │If installed in compliance with fire safety standards, the use of the equipment │ │ │Installation is exempted within the effective range. However, from the ground surface to the top floor room │ │ │It must be installed if the height of the water outlet is 70m or more. │ ├──────────┼────────────────────────────┤ │19. Connected Sprinkler System │a. Water supply to specific fire-protected buildings requiring the installation of connected sprinkler systems │ │ │Sprinkler system with installed START outlets, simplified sprinkler system, water spray │ │ │A non-fire extinguishing system or a fine mist fire extinguishing system in accordance with fire safety standards │ │ │In the case of combined installation, within the effective range of the equipment │ │ │is waived. │ │ │b. water spray devices, etc. installed in accordance with gas-related laws and regulations │ │ │is installed or water │ │ │A water source capable of supplying weapons systems, etc., for more than 6 hours is │ │ │Installation is exempted if secured. │ ├──────────┼────────────────────────────┤ │20. Wireless communication auxiliary setup │to specific fire safety targets required to install wireless communication auxiliary facilities this │ │B │Mobile communication in-house repeater line equipment or wireless mobile repeater (「Former │ │ │Applicable only to products that have undergone conformity assessment pursuant to Article 58-2 of the "Small Act" │ │ │(etc. comply with the wireless communication auxiliary equipment standards of the fire safety standards) │ │ │Installation is exempted if installed as . │ ├──────────┼────────────────────────────┤ │21. Combustion Prevention Equipment │Spring for specific fire-fighting targets required to install combustion prevention equipment │ │ │Clamping equipment, water spray fire extinguishing equipment or fine mist fire extinguishing equipment for fire prevention │ │ │If installed in compliance with all standards, the effective range of the equipment │ │ │. │ └──────────┴────────────────────────────┘