Annex 4 — 소방시설 설치 및 관리에 관한 법률 시행령

287375 · 2026-07-01

■ Enforcement Decree of the Act on Installation and Management of Firefighting Facilities [Appendix 4] <Amended Nov. 25, 2025> Of firefighting facilities that the person responsible for a specific firefighting target must install and manage in the specific firefighting target Type (Related to Article 11) 1. Fire extinguishing equipment a. Specific fire safety targets required to install fire extinguishing equipment in accordance with fire safety standards are the following shall be considered as corresponding to one. 1) Those with a gross floor area of ​​33㎡ or more. However, in the case of facilities for the elderly and disabled, throwable fire extinguishers, etc. Can be installed at least half of the quantity of fire extinguishers calculated according to fire safety standards . 2) Facilities not falling under 1) including gas facilities, electricity storage facilities among power generation facilities and national Legacy 3) Tunnel 4) Underground b. Specific fire safety targets required to install automatic fire extinguishing devices fall under any of the following: is a specific firefighting target building that has a kitchen equipped with a hood and ducts It shall be considered as a commercial property. In this case, an automatic fire extinguishing system must be installed in the relevant kitchen. 1) Requirements for installing residential kitchen automatic fire extinguishing systems: All apartments, etc. and officetels floor 2) Requirements for installing commercial kitchen automatic fire extinguishing systems a) Among sales facilities, large-scale stores falling under Article 2, Subparagraph 3 of the Distribution Industry Development Act General restaurants located within b) Group meal service facilities pursuant to Article 2, Subparagraph 12 of the Food Sanitation Act 3) Cabinet-type automatic fire extinguishing system, gas automatic fire extinguishing system, powder automatic fire extinguishing system or solid air Places where automatic solubility fire extinguishing systems must be installed: Locations specified in fire safety standards . Specific fire safety targets required to install indoor fire hydrant systems fall under any of the following shall be deemed as follows. However, among hazardous material storage and processing facilities, gas facilities, underground areas and business Among facilities without personnel, unmanned substations (sprinkler systems or water spray fire extinguishing systems in fire control rooms, etc. (limited to unmanned substations that can be remotely controlled) is excluded. 1) In any of the following cases, all layers a) Those with a gross floor area of ​​3,000 m² or more (excluding tunnels) b) Basement floors or windowless floors (excluding livestock barns) with a floor area of ​​600㎡ or more thing with d) Among floors with 4 or more stories, there is a floor with a floor area of ​​600㎡ or more 2) Neighborhood living facilities, sales facilities, transportation facilities, medical facilities, and facilities for the elderly and disabled that do not fall under 1) facilities, office facilities, accommodation facilities, entertainment facilities, factories, warehouse facilities, aircraft and automobile-related facilities Among facilities, correctional and military facilities, national defense and military facilities, broadcasting and telecommunications facilities, power generation facilities, and funeral facilities or in the case of a complex building falling under any of the following, all floors a) Those with a gross floor area of ​​1,500 m² or more b) Basement floors or windowless floors having a floor area of ​​300㎡ or more d) Among floors with 4 or more stories, there is a floor with a floor area of ​​300㎡ or more 3) A garage or parking lot installed on the rooftop of a building with an area of ​​200㎡ or more , the relevant part 4) Any of the following tunnels a) Tunnels with a length of 1,000 m or more b) as prescribed by the Ordinance of the Ministry of the Interior and Safety, taking into consideration the characteristics of the tunnel such as expected traffic volume and gradient tunnel 5) As a factory or warehouse facility not falling under 1) and 2), the "Fire Prevention and Safety Management special combustible materials at least 750 times the quantity specified in Annex 2 of the Enforcement Decree of the Act on the Use of Firefighting Storing and handling materials d. Specific fire safety targets requiring the installation of sprinkler systems (hazardous material storage and processing facilities ) shall be deemed to fall under any of the following: . 1) In the case of specific fire safety target buildings with 6 or more floors, all floors. However, any of the following Excludes cases corresponding to one. a) In cases where existing apartments, etc. are remodeled in accordance with housing-related laws and regulations, as construction Where the gross floor area and floor height of the building are not changed. In this case, the relevant apartment, etc. Presidential Decree or Fire Safety Standards concerning the installation of firefighting facilities at the time of the inspection of use of . b) In the case of changing the use of an existing specific fire safety target building that does not have a sprinkler system. c Only for specific fire safety targets falling under provisions 2) through 6) and 9) through 12) In the event of a change of use, sprinkler systems shall be installed in accordance with the relevant regulations. 2) Dormitory (referring to one for accommodating students located within educational research facilities or training facilities) or in the case of a complex building with a gross floor area of ​​5,000 m² or more, all floors 3) Cultural and assembly facilities (excluding zoos and botanical gardens), religious facilities (those with a main structural frame made of wood are excluded), sports facilities (water play type facilities and facilities where the floor is made of non-combustible material and there are no spectator seats (excluding sports facilities) and in any of the following cases, all floors a) Those with a capacity of 100 or more b) Where the floor area of ​​the floor used for movie theater purposes is a basement or a windowless floor 500㎡ or more, and 1,000㎡ or more for other floors d) In cases where the stage area is located in a basement, a windowless floor, or a floor of the 4th floor or higher, the stage area with an area of ​​300㎡ or more d) If the stage area is on a floor other than c), the area of ​​the stage area is 500㎡ or more 4) The sum of the floor areas of sales facilities, transportation facilities, and warehouse facilities (limited to logistics terminals) If the total area is 5,000 m² or more, or the capacity is 500 people or more, all floors 5) The total floor area of ​​facilities used for any of the following purposes For those exceeding 600㎡, all floors a) Midwifery centers and postpartum care centers among neighborhood living facilities b) Mental health institutions among medical facilities d) Among medical facilities, general hospitals, hospitals, dental hospitals, oriental medicine hospitals, and nursing hospitals d) Facilities for the Elderly and Disabled e) Training facilities with accommodation available Bar) Accommodation 6) In the case of warehouse facilities (excluding logistics terminals) with a total floor area of ​​5,000㎡ or more , all layers 7) Basement floors, windowless floors (excluding livestock barns), or buildings with 4 or more stories In cases where there is a floor with a floor area of ​​1,000 m² or more, the relevant floor 8) Rack (referring to a shelf or something similar capable of storing goods. The same applies hereinafter) As a warehouse facility with installed ceilings or suspended ceilings (in the case where there are no suspended ceilings, the interior of the roof) The height of the part where the rack is installed (referring to the part where the rack is installed) exceeds 10m, and the floor area of ​​the part where the rack is installed is 1,500㎡ or more, all floors 9) A factory or warehouse facility falling under any of the following a) the number prescribed in Annex 2 of the Enforcement Decree of the Act on the Prevention of Fire and Safety Management Facilities storing or handling special combustible materials exceeding 1,000 times the amount b) Intermediate and low-level radioactive waste pursuant to Article 2, Subparagraph 1 of the Enforcement Decree of the Atomic Energy Safety Act (this Collecting and treating firefighting water among storage facilities for “low- and intermediate-level radioactive waste” (hereinafter referred to as “intermediate- and low-level radioactive waste”) Storage facility having a facility for managing 10) When a factory or warehouse where the roof or exterior walls are not made of non-combustible materials or are not of a fire-resistant structure As a theory corresponding to any of the following a) Among warehouse facilities (limited to logistics terminals), those not falling under 4) as floor In cases where the total area is 2,500 m² or more, or the capacity is 250 people or more, All layers b) Among warehouse facilities (excluding logistics terminals), those not falling under 6) and floor If the total area is 2,500㎡ or more, all floors c) Among factory or warehouse facilities that do not fall under 7), basement floors, windowless floors, or applies to all floors with a floor area of ​​500㎡ or more among floors with 4 or more stories d) Rack-type warehouses that do not fall under 8) and have a total floor area of ​​750㎡ or less phase, all layers e) Among factories or warehouse facilities that do not fall under 9)a), "Fire Prevention 500 times or more the quantity specified in Annex 2 of the Enforcement Decree of the Act on Safety Management and Safety Management Facilities for storing and handling special combustible materials of START 11) Among correctional and military facilities, in the case of any of the following, the relevant place a) Protective custody centers, prisons, detention centers and their branches, probation offices, rehabilitation facilities, treatment Detention cells of correctional facilities, juvenile detention centers and juvenile classification and examination centers b) Detention facilities pursuant to Article 52, Paragraph 2 of the Immigration Control Act (in the case of foreigner detention centers The part used as the living space of the protected person. (The same applies hereinafter.) However, Cases where the protective facility is located in a leased building are excluded. d) A detention facility pursuant to Article 9 of the “Act on the Execution of Duties by Police Officers” 12) Underground shopping malls with a gross floor area of ​​1,000㎡ or more 13) Electricity storage facilities among power generation facilities 14) Boiler rooms or connecting passages, etc. attached to the specific fire safety targets from 1) to 13) E. Specific fire safety targets required to install simplified sprinkler systems shall, in any of the following It shall be considered applicable. 1) Row houses and multi-family houses among multi-unit dwellings (Simplified installation in row houses and multi-family houses This sprinkler system is a simplified sprinkler system for residential use in accordance with fire safety standards ) 2) Among neighborhood living facilities, any of the following a) For those where the total floor area of ​​the portion used as a neighborhood living facility is 1,000 m² or more, [] all floors b) Medical clinics, dental clinics, and Korean medicine clinics that have inpatient rooms or artificial kidney units c) Facilities as midwifery centers and postpartum care centers with a total floor area of ​​less than 600㎡ 3) Among medical facilities, any of the following facilities a) General hospitals, hospitals, dental hospitals, Korean medicine hospitals, and nursing hospitals (excluding medical rehabilitation facilities Facilities with a total floor area of ​​less than 600㎡ used as () b) The total floor area used as a psychiatric medical institution or medical rehabilitation facility is 300㎡ or larger and less than 600㎡ d) The total floor area used as a psychiatric medical institution or medical rehabilitation facility is 300㎡ and bars (made of steel, plastic, or wood, etc. to prevent people from escaping, etc. , and having a structure that opens automatically in the event of a fire Facilities where bars are installed (excluding bars) 4) In the case of a dormitory within an educational or research facility with a total floor area of ​​100㎡ or more, all floors 5) Facilities for the elderly and children that fall under any of the following categories a) Facilities pursuant to each item of Article 7, Paragraph 1, Subparagraph 7 [subparagraph a, item 2) and subparagraph b of the same subparagraph Among the facilities up to item (f), facilities installed in detached houses or multi-unit dwellings are excluded, and Hereinafter referred to as “Residential Facility for the Elderly and Disabled”] b) Facilities for the elderly and children not falling under a) Sum of floor areas used as said facilities Facilities with a total area of ​​300㎡ or more but less than 600㎡ c) The sum of the floor areas used as facilities for the elderly and children that do not fall under a) The area is less than 300㎡, and bars (made of steel, plastic, or wood, etc., for people's escape It refers to something installed to block lights, etc., and is structured to open automatically in the event of a fire. Facilities where bars that are installed (excluding bars that are installed) 6) Facilities with a total floor area used as accommodation of 300㎡ or more but less than 600㎡ 7) leasing a building and using it as a detention facility pursuant to Article 52, Paragraph 2 of the Immigration Control Act is a part 8) A complex building (only applicable to complex buildings under Item 30, Subparagraph B of Annex 2) with a gross floor area of ​​1,000㎡ The one above is all layers B. Specific fire safety targets requiring the installation of water spray fire extinguishing systems [Hazardous material storage and processing facilities and [Underground sections are excluded] shall be deemed to fall under any one of the following. 1) Aircraft hangars among aircraft and automobile-related facilities 2) Garages, parking structures, or steel-framed prefabricated parking facilities. In this case, the gross floor area must be 800㎡ or more . 3) A garage or parking lot installed inside a building, used for garage or parking purposes If the total area is 200㎡ or more, the relevant part (row houses with fewer than 50 households and Multi-family housing is excluded) 4) A parking facility capable of parking 20 or more vehicles using a mechanical device Facility 5) Electrical rooms, generator rooms, and substations installed in specific fire safety target buildings (where combustible insulating oil is not used and electrical equipment that does not use flammable coatings (excluding electrical rooms, generator rooms, and substations where only lines and cables are installed)ㆍbattery roomㆍ A telecommunications equipment room or computer room, or other similar facility with a floor area of ​​300㎡ or more that is [in the case where two or more rooms are installed within a single fire compartment [The floor area is calculated by considering this as a single room.] However, process control made of a fire-resistant structure room, a positive pressure facility (blocking the intrusion of external contaminated air and internal (Refers to a facility that allows bad air to naturally flow to the outside) installation and low voltage of 220 volts or less is used in electrical equipment and employees are present 24 hours a day excludes the place. 6) Intermediate and low-level radioactive waste for which facilities for collecting and treating fire extinguishing water are not installed Water storage facilities. These facilities include carbon dioxide fire extinguishing systems, halon fire extinguishing systems, or halogenated Compound and inert gas fire extinguishing systems must be installed. 7) As prescribed by the Ordinance of the Ministry of the Interior and Safety, taking into consideration the characteristics of the tunnel such as expected traffic volume and gradient Tunnel. A water spray fire extinguishing system must be installed in this facility. 8) Among national heritage, designated cultural heritage pursuant to the "Act on the Preservation and Utilization of Cultural Heritage" Mountains (excluding cultural heritage materials) or the "Act on the Preservation and Utilization of Natural Heritage" , designated by the Commissioner of the Fire Department as National Heritage Determined in consultation with the Commissioner Inc. Specific fire safety targets requiring the installation of outdoor fire hydrant systems (apartments, etc., hazardous material storage and (excluding gas facilities, underground passages, and tunnels among treatment facilities) shall be in any of the following It shall be treated as being subjected to. 1) Those where the total floor area of ​​the first and second floors above ground is 9,000 m² or more. In this case, the same district Two or more specific fire safety targets within a district, as prescribed by the Ordinance of the Ministry of the Interior and Safety, combustion (延燒) In the case of a structure where there is a concern, it shall be deemed as a single specific fire safety target. 2) Among cultural heritage, pursuant to Article 23 of the "Act on the Preservation and Utilization of Cultural Heritage," Treasure or wooden buildings designated as national treasures 3) As a factory or warehouse facility not falling under 1), in accordance with the "Fire Prevention and Safety Management Special combustible materials exceeding 750 times the quantity specified in Annex 2 of the Enforcement Decree of the Act concerning... Items handled 2. Alarm equipment a. Specific fire safety targets required to install stand-alone alarm type detectors shall not fall under any of the following: It shall be deemed applicable. In this case, the detached ceiling installed in row houses and multi-family houses under 5) The START-type detector must be installed as an interlocking type. 1) Dormitories or boarding houses located within educational and research facilities with a gross floor area of ​​less than 2,000 m² 2) Dormitories or boarding houses located within training facilities with a total floor area of ​​less than 2,000 m² 3) Training facilities not falling under Item 7) (only those with accommodation facilities) 4) Kindergartens with a gross floor area of ​​less than 400㎡ 5) Row houses and multi-family houses among multi-unit dwellings 6) In cases where a garage or parking lot is installed in the basement of a building, as a garage or parking lot In cases where the total area used is less than 200㎡, the relevant garage/parking lot portion B. Specific fire safety targets required to install emergency alarm systems (factories using non-combustible materials such as sand and stone and warehouse facilities, gas facilities among hazardous materials storage and handling facilities, or uninhabited or (excluding animal and plant-related facilities such as livestock sheds without walls and underground areas) is the following It shall be deemed to correspond to any one of the following. 1) For those with a gross floor area of ​​400㎡ or more, all floors 2) For those with a basement or windowless floor area of ​​150㎡ (100㎡ in the case of a performance hall) or more All layers 3) Tunnels with a length of 500m or more 4) Indoor workplaces where 50 or more workers are working 5) In cases where a garage or parking lot is installed in the basement of a building, as a garage or parking lot In cases where the total area used is less than 200㎡, all floors of the relevant building Specific fire safety targets required to install automatic fire detection systems are those that [missing] any of the following [missing] It shall be treated as being subjected to. 1) In the case of apartments, dormitories, and lodging facilities among multi-unit dwellings, all floors 2) In the case of buildings with 6 or more floors, all floors 3) Neighborhood living facilities (excluding bathhouses), medical facilities (psychiatric medical institutions and nursing hospitals are ), in the case of entertainment facilities, funeral facilities, and complex buildings with a gross floor area of ​​600㎡ or more is all layers 4) Among neighborhood living facilities, bathhouses, cultural and assembly facilities, religious facilities, sales facilities, transportation facilities, Sports facilities, office facilities, factories, warehouse facilities, hazardous materials storage and handling facilities, aircraft and equipment Facilities related to electric vehicles, correctional and military facilities including national defense and military facilities, broadcasting and telecommunications facilities, power generation facilities In the case of facilities, tourist rest areas, or underground shopping malls with a gross floor area of ​​1,000 m² or more, all floors 5) Educational and research facilities (including dormitories and lodgings located within educational facilities), training facilities (Including dormitories and training centers within the training facility, and training facilities with accommodation facilities are excluded), animal and plant-related facilities (consisting only of pillars and roofs, external and excluding places where air flows), resource recycling-related facilities, correctional and military facilities (National Defense (excluding military facilities) or cemetery-related facilities with a gross floor area of ​​2,000 m² or more , all layers 6) In the case of residential facilities for the elderly and disabled, all floors 7) Facilities for the elderly and children that do not fall under 6) and have a total floor area of ​​400㎡ or more, and For training facilities with accommodation facilities with a capacity of 100 or more people, all floors 8) Among medical facilities, a psychiatric medical institution or a nursing hospital falling under any of the following is facility a) Nursing hospitals (excluding medical rehabilitation facilities) b) The total floor area used as a psychiatric medical institution or medical rehabilitation facility is 300㎡ Facilities exceeding d) The total floor area used as a psychiatric medical institution or medical rehabilitation facility is 300㎡ and bars (made of steel, plastic, or wood, etc. to prevent people from escaping, etc. , and having a structure that opens automatically in the event of a fire Facilities where bars are installed (excluding bars) 9) Traditional markets among sales facilities 10) Tunnels with a length of 1,000m or more 11) Underground 12) Among neighborhood living facilities not falling under 3), midwifery centers and postpartum care centers 13) 4) and are subject to the "Regarding fire prevention and safety management Special combustible materials exceeding 500 times the quantity specified in Annex 2 of the Enforcement Decree of the Act Items handled 14) Electricity storage facilities among power generation facilities not corresponding to 4) 15) In cases where a garage or parking lot is installed in the basement of a building, as a garage or parking lot If the total area used is 200㎡ or more, all floors of the relevant building d. Specific fire safety targets required to install visual alarms shall, in accordance with subparagraph c, automatic fire detection equipment Among the specific fire safety targets required to install START, those deemed to fall under any of the following: . 1) Neighborhood living facilities, cultural and assembly facilities, religious facilities, sales facilities, transportation facilities, medical facilities, elderly Yuja Facility 2) Sports facilities, office facilities, accommodation facilities, entertainment facilities, logistics terminals among warehouse facilities, power generation facilities and Funeral Facilities 3) Libraries among educational and research facilities, broadcasting stations among broadcasting and telecommunications facilities 4) Underground Shopping Mall 5) Lithium primary battery plant (using lithium as the main electrode material, non-rechargeable primary Refers to a factory that manufactures, processes, assembles, stores, or charges batteries, etc.) E. Specific fire safety targets required to install fire alarm systems are traditional markets among sales facilities. . B. Specific fire safety targets requiring the installation of emergency broadcasting equipment (among hazardous material storage and processing facilities Gas facilities, animal and plant-related facilities such as livestock sheds that are uninhabited or wall-less, (excluding tunnels and underground sections) shall be deemed to fall under any one of the following. 1) For those with a gross floor area of ​​3,500㎡ or more, all floors 2) For those with 11 or more floors, all floors 3) For those with 3 or more basement floors, all floors d. Specific fire safety targets required to install automatic fire alarm systems shall not fall under any of the following . However, in places where fire receivers are installed, such as fire control rooms, 24-hour fire If a person capable of monitoring fire is on duty, install an automatic fire alarm system. may not. 1) Residential Facility for the Elderly and Disabled 2) Facilities for the elderly and disabled that have floors with a floor area of ​​500㎡ or more 3) Training facilities (only those with accommodation facilities) with a floor area of ​​500㎡ or more having 4) Among cultural heritage, pursuant to Article 23 of the "Act on the Preservation and Utilization of Cultural Heritage," Treasure or wooden buildings designated as national treasures 5) Among neighborhood living facilities, any of the following facilities a) Medical clinics, dental clinics, and Korean medicine clinics with inpatient rooms b) Midwifery centers and postpartum care centers 6) Among medical facilities, any of the following a) General hospitals, hospitals, dental hospitals, Korean medicine hospitals, and nursing hospitals (excluding medical rehabilitation facilities ( b) Where the total floor area used as a psychiatric hospital and medical rehabilitation facility is 500㎡ or more having a layer 7) Traditional markets among sales facilities A. Specific fire safety targets requiring the installation of integrated monitoring facilities shall be underground structures. . The leakage alarm is based on the contracted current capacity (where electricity of different contract types is supplied to the same building where the maximum contracted current capacity among them is exceeded 100 amperes, specific fire protection Subject matter (buildings not of fire-resistant structure in which all or part of the walls, floors, or ceilings are non-combustible (Applies only to materials that are not non-combustible or semi-non-combustible and are made by inserting wire mesh) must be done. However, among hazardous material storage and handling facilities, gas facilities, tunnels, and underground sections Above, it is not so. . Specific fire safety targets requiring the installation of gas leak alarms (only where gas facilities are installed (applicable) shall be deemed to correspond to any one of the following. 1) Cultural and assembly facilities, religious facilities, sales facilities, transportation facilities, medical facilities, facilities for the elderly and children 2) Training facilities, sports facilities, accommodation facilities, factories, and logistics terminals among warehouse facilities, funeral facilities 3. Evacuation and Rescue Equipment a. Evacuation equipment shall be installed on all floors of a specific fire-protected building in accordance with fire safety standards. must be done. However, evacuation floors, 1st floor above ground, and 2nd floor above ground (among facilities for the elderly and disabled, whether it is an evacuation floor (Excluding the 1st floor and the 2nd floor above ground that is not an evacuation floor), floors with 11 or more floors and dangerous This is not the case for gas facilities, tunnels, and underground passages among water storage and treatment facilities. b. Specific fire safety targets required to install life-saving equipment fall under any of the following: is to be. 1) Heat-resistant or fire-resistant clothing (including safety helmets, protective gloves, and safety shoes), artificial resuscitation devices and Specific fire safety targets requiring the installation of self-contained breathing apparatus: 7 floors including basement floors Among those above, floors used for tourist hotel purposes END 2) Heat-resistant or fire-resistant clothing (including safety helmets, protective gloves, and safety shoes) and self-contained breathing apparatus Specific fire safety targets requiring the installation of START: Those with 5 or more floors, including basement floors. 중 병원 용도로 사용하는 층 3) Specific fire safety targets required to install air breathing apparatus fall under any of the following: is to be. a) Movie theaters among cultural and assembly facilities with a capacity of 100 or more b) Large-scale stores among sales facilities d) Underground stations among transportation facilities ra) Underground Shopping Mall e) In accordance with Subparagraph 1, Item f and fire safety standards, carbon dioxide fire extinguishing system (hose reel carbon dioxide Specific fire safety targets that must install (excluding fire extinguishing equipment) Specific fire safety targets required to install exit signs are those falling under any of the following: . 1) Evacuation guide lights, passageway guide lights, and guidance signs shall be installed in specific fire safety target buildings. However, The following cases are excluded. a) A portion of animal and plant-related facilities that serves as a livestock barn for directly confining and raising livestock b) Tunnel 2) Auditorium exit signs shall be installed in specific fire safety target buildings falling under any of the following. a) Entertainment establishment business facilities (entertainment establishment business pursuant to Article 21, Subparagraph 8, Item (d) of the Enforcement Decree of the Food Sanitation Act) A cabaret, nightclub, or the place where a stage is installed for guests to dance during business hours, or that (Applies only to similar business facilities outside of this) b) Cultural and Assembly Facilities d) Religious facilities d) Exercise Facilities 3) Evacuation guidance lines shall be installed in locations specified in the fire safety standards. d. Specific fire safety targets requiring the installation of emergency lighting (warehouses and loading docks among warehouse facilities, above Gas facilities and structures uninhabited or without walls among material storage and processing facilities (excluding animal and plant-related facilities such as companies) falls under any of the following: . 1) A building with 5 or more stories, including basement floors, and a gross floor area of ​​3,000 m² or more above all layers 2) The floor area of ​​the basement or windowless floor of a specific fire safety target that does not fall under 1) If the area is 450㎡ or more, the relevant floor 3) Tunnels with a length of 500m or more E. Specific fire safety targets required to install portable emergency lights shall not fall under any of the following: It shall be treated as being subjected to. 1) Accommodation 2) Movie theaters with a capacity of 100 or more, large-scale stores among retail facilities, railways and urban railways also among the facilities underground stations, underground shopping malls 4. Firefighting Water Supply System Specific fire safety targets required to install water supply fire extinguishing facilities are any of the following: . However, specific fire brigades required to install water supply fire extinguishing facilities Water supply drainage pipes with a diameter of 75 mm or more within 180 m from the boundary line of the property In areas where they are not installed, fire extinguishing water tanks or reservoirs in accordance with fire safety standards shall be installed must be installed. a. Those with a gross floor area of ​​5,000 m² or more. However, among hazardous material storage and processing facilities, gas facilities, tunnels or in the case of underground passages, excluded. b. Gas facilities in which the total storage capacity of tanks exposed above ground is 100 tons or more . Among resource circulation-related facilities, waste recycling facilities and waste disposal facilities 5. Firefighting Equipment A. Specific fire safety targets required to install smoke control systems are those falling under any of the following: . 1) Among cultural and assembly facilities, religious facilities, and sports facilities, those with a stage floor area of ​​200㎡ or more , the relevant stage part 2) In the case of movie theaters among cultural and assembly facilities with a capacity of 100 people or more, [ per movie theater 3) Neighborhood living facilities, sales facilities, transportation facilities, accommodation facilities, above installed in basements or windowless floors As a storage facility, medical facility, facility for the elderly and disabled, or warehouse facility (limited to logistics terminals) If the total floor area used for a specific purpose is 1,000 m² or more, the relevant part 4) Among transportation facilities, intercity bus stops, railway and urban railway facilities, airport facilities and port facilities , with a basement or windowless floor area of ​​1,000 m² or more , all layers 5) Underground shopping malls with a gross floor area of ​​1,000㎡ or more 6) As prescribed by the Ordinance of the Ministry of the Interior and Safety, taking into consideration the characteristics of the tunnel such as expected traffic volume and gradient tunnel 7) Special escape stairs attached to specific fire safety target buildings (excluding open-corridor type apartments, etc.), non Landing of a commercial elevator or landing of an evacuation elevator B. Specific fire safety targets requiring the installation of connected water supply systems (hazardous material storage and processing facilities ) shall be deemed to fall under any of the following . 1) In cases where the number of floors is 5 or more and the gross floor area is 6,000 m² or more, all floors 2) Specific fire safety targets not falling under 1) with 7 or more floors including basement floors , all layers 3) Specific fire safety targets not falling under 1) and 2) with 3 or more basement floors In cases where the total floor area of ​​the basement floors is 1,000 m² or more, all floors 4) Tunnels with a length of 500m or more . Specific fire safety targets requiring the installation of connected sprinkler systems (excluding underground areas) are as follows: It shall be deemed to correspond to any one of the following. 1) Of the part used for the relevant purpose as a logistics terminal among sales facilities, transportation facilities, and warehouse facilities If the total floor area is 1,000 m² or more, the relevant facility 2) Basement floor (excluding cases where the main entrance of the evacuation floor faces a road) as the floor In cases where the total area is 150㎡ or more, all floors of the basement. However, the "Enforcement Decree of the Housing Act Underground floors of apartments, etc., with a national housing scale or smaller pursuant to Article 46, Paragraph 1 of the [Ordinance] (as evacuation facilities (Applicable only to use) and in the case of basement floors of schools among educational research facilities, 700㎡ It shall be deemed to be greater than or equal to. 3) Tank facilities among gas facilities where the capacity of tanks exposed above ground is 30 tons or more 4) Connecting passage attached to the specific fire-protected objects of 1) and 2) 5) In cases where a garage or parking lot is installed in the basement of a building, as a garage or parking lot In cases where the total area used is less than 200㎡, the relevant garage/parking lot portion 6) A parking facility capable of parking fewer than 20 vehicles using a mechanical device Facility (only if with roof and exterior walls) d. Specific fire safety targets requiring the installation of emergency outlet facilities (hazardous material storage and processing facilities ) shall be deemed to fall under any of the following: . 1) In the case of specific fire safety target buildings with 11 or more floors, the 11th floor or higher floors 2) Where the number of basement floors is 3 or more and the total floor area of ​​the basement floors is 1,000 m² or more that is all floors of the basement 3) Tunnels with a length of 500m or more E. Specific fire safety targets requiring the installation of wireless communication auxiliary equipment (hazardous material storage and processing facilities ) shall be deemed to fall under any one of the following: 1) Underground shopping malls with a gross floor area of ​​1,000㎡ or more 2) Those with a total floor area of ​​3,000 m² or more of basement floors, or those with 3 or more basement floors For those above and where the total floor area of ​​the basement is 1,000 m² or more, all floors of the basement 3) Tunnels with a length of 500m or more 4) Utility tunnel among underground tunnels 5) For buildings with 30 or more floors, all floors of the 16th floor or higher B. Combustion prevention equipment must be installed in underground conduits (only applicable to those for power or telecommunications businesses) . Remarks 1. Facilities corresponding to any of subparagraphs 1 through 27 of Attached Table 2 (hereinafter referred to in this subparagraph as “foundation The installation standards for fire fighting facilities of complex buildings (hereinafter referred to as "living facilities, etc.") are the installation standards for fire fighting facilities of complex buildings. , for the relevant neighborhood living facilities, etc. located within a complex building, that neighborhood The installation standards for fire fighting facilities in residential facilities, etc. shall apply. 2. Installed in reactors and related facilities pursuant to Article 2 of the Atomic Energy Safety Act among nuclear power plants Regarding firefighting facilities, in accordance with the licensing standards under Articles 11 and 21 of the Atomic Energy Safety Act Install. 3. The person responsible for a specific fire safety target shall, regarding the specific fire safety target subject to seismic design pursuant to Article 8, Paragraph 1 and Firefighting facilities to be installed and managed in specific firefighting targets subject to performance-based design pursuant to Article 9 , the seismic design standards for firefighting facilities pursuant to Article 7 of the Act and the performance standards pursuant to Article 8 of the Act It must be installed and managed in accordance with the standards for design focused on START.