Annex 4 — 소방용품의 품질관리 등에 관한 규칙

287833 · 2026-07-01

■ Rules on Quality Management, etc. of Firefighting Equipment [Appendix 4] <Amended July 27, 2022> of the test facilities that a person seeking type approval must possess 기준(Related to Article 6, Paragraph 2) 1. Install a test room meeting the standards of each of the following items at the place where firefighting products are manufactured thing to do a. The test room shall be designed to prevent flooding. b. The location for testing the sensitivity of the alarm device shall be free from ventilation, sunlight, etc. direction, and that the sensitivity tester is not affected by vibration or shock The floor shall be made of concrete at least 12 cm thick to prevent bearing. . Equipment for automatic fire extinguishing systems such as sprinklers or other fire extinguishing systems The test site is subject to the influence of ventilation, sunlight, vibration, and shock. Ensure that it does not happen, and install drainage facilities. d. The length of the escape ladder test room shall be 15m or more E. In the test chambers for fire hoses, nozzles, fire hydrants, and automatic fire extinguishing equipment, power pumps Install START B. The length of the fire hose test chamber shall be at least 20m. Inc. The test laboratory for air breathing apparatus chargers is a facility designated and notified by the Commissioner of the Fire Department Ensure installation and operation in accordance with standards 2. The walls of the fire extinguishing test site shall be constructed of a fire-resistant structure, and other surrounding buildings Maintain a distance of at least 3m from the wall. However, fire-resistant partitions Fire extinguishing in an open space where a wall is installed or there is no risk of fire This shall not apply in cases where a START test is performed. At places manufacturing descent devices and rescue equipment, a test tower of 15m or more in height Things to install 4. In places where sprinkler heads and water flow control valves are manufactured, Install a water reservoir. However, sprinkler heads and water flow control at the same location shall... When manufacturing a START valve, a single water tank can be used together. 5. The area of ​​the test room shall meet the following criteria ┌──────────────────┬─────┬──────────────────┐ │ Category │of the test room │B GO │ │ │If Red │ │ │ │(㎡ or more) │ │ │Item │ │ │ ┝━━━━┯━━━━━━━━━━━━━┿━━━━━┿━━━━━━━━━━━━━━━━━━┥ │Fire Extinguisher│Powder fire extinguisher · Carbon dioxide fire extinguisher│50 │ │ │ │Qa │ │1. Two or more types in the same place │ │ ├─────────────┼─────┤, │ │ │Acid, alkali and fortified liquid extinguishing │20 │Among them, regarding the wide item-specific test room area │ │ │Qa │ │one-fifth of the test room area for each item │ │ ├─────────────┼─────┤Solve the sum of the corresponding areas │ │ │Halogen compound fire extinguisher │20 │It shall be the area of ​​the test room per START. │ │ ├─────────────┼─────┤2. At the place where fire extinguishing equipment is manufactured, the same │ │ │Other fire extinguishing equipment │20 │manufacture fire extinguishing agent at or in addition │ │ │ │ │If you intend to calculate in accordance with Item 1, │ │ │ │ │to the test laboratory area by item of fire extinguisher │ │ │ │ │of the test laboratory area by item of fire extinguishing agent 5 │ │ │ │ │Each additional area corresponding to 1/ │ │ │ │ │used as the area of ​​the relevant test room │ │ │ │ │. │ ├────┼─────────────┼─────┼──────────────────┤ │FireExtinguishingAgent│Foam fire extinguishing agent │20 │ │ │ ├─────────────┼─────┤in the same place │ │ │Powder Fire Extinguishing Agent │20 │In the case of intending to manufacture a fire extinguishing agent, the │ │ ├─────────────┼─────┤Among the wide item-specific laboratory areas, different │ │ │Acid, alkali, and fortified liquid extinguishing │20 │Corresponds to one-fifth of the test laboratory area per item │ │ │pharmaceutical ├─────┤and the corresponding │ │ ├─────────────┤20 │It shall be the area of ​​the laboratory. │ │ │Other fire extinguishing agents │ │ │ ├────┼─────────────┼─────┼──────────────────┤ │Flame Retardant │flame retardant liquid, flame retardant paint, etc. │20 │ │ │ │Flame-retardant substance │ │ │ ├────┼─────────────┼─────┼──────────────────┤ │Evacuation Equipment│Escape Ladder │70 │ │ │ ├─────────────┼─────┤in the same place │ │ │Descent device·Simple descent device·Support bracket│70 │In the case of intending to manufacture an evacuation device, the │ │ ├─────────────┼─────┤Among the wide item-specific laboratory areas, different │ │ │RescueTeam │70 │Corresponds to one-fifth of the test laboratory area per item │ │ ├─────────────┼─────┤and the corresponding │ │ │Exit lights and emergency lighting │33 │It shall be the area of ​​the laboratory. │ ├────┼─────────────┼─────┼──────────────────┤ │Alarm device│Detector·Transmitter·Receiver·Middle│66 │in the same place │ │ │Instruments · Sound System │ │In the case of manufacturing an alarm device, the END │ │ ├─────────────┼─────┤Among the wide item-specific test room areas, different │ │ │Gas Leak Alarm │66 │Corresponds to half of the test laboratory area per item │ │ ├─────────────┼─────┤and the corresponding │ │ │Nu Jeon Gyeong Bo Gi │33 │It shall be the area of ​​the laboratory. │ ├────┼─────────────┼─────┼──────────────────┤ │AutomaticExtinguishing│Water flow control valve (Water flow detection device │100 │ │ │equipment's │ㆍSunset Opening Valve) │ │ │ │Device │SprinklerHead │ │ │ │ │Water pressure switch for starting │ │ │ │ │Gas Pipe Selector Valve │ │ │ ├────┼─────────────┼─────┼──────────────────┤ │Other │Firefighting Hose │100 │ │ │FirefightingSupplies├─────────────┼─────┼──────────────────┤ │ │Nozzle, fire hydrant (indoor fire hydrant room│100 │Place where automatic fire extinguishing equipment is manufactured │ │ │Water outlet, outdoor fire hydrant) │ │, the automatic fire extinguishing system │ │ │ │ │regarding the test room area by equipment item │ │ │ │ │corresponding to half of the test room area │ │ │ │ │areas of the corresponding test room │ │ │ │ │It shall be the area. │ │ ├─────────────┼─────┼──────────────────┤ │ │Air breathing apparatus │100 │ │ │ ├─────────────┼─────┼──────────────────┤ │ │SCREWAR charger │100 │ │ └────┴─────────────┴─────┴──────────────────┘ 6. Equipped with other test devices and equipment prescribed and notified by the Commissioner of the Fire Department Exit