■ Rules on Standards for Evacuation, Fire Protection, and Structures of Buildings [Appendix 1] <Amended Nov. 15, 2024>
Performance Standards for Fire-Resistant Structures (Related to Article 3, Item 8)
GeneralStandard
(Unit: Hour)
┏━━━━━━━━━━━━━━━━━━━━┯━━━━━━━━━━━━━━━━━━━━━┯━━┯━━┯━━┓
┃ Configuration Member │Wall │Bo │Floor│Roof┃
┃ ├───────────┬─────────┤ㆍ │ │ㆍ ┃
┃for │ExteriorWall │InnerWall │Pillar│ │G ┃
┃ ├─┬─────────┼─┬───────┤ │ │Bung ┃
┃ │My│Non-load-bearing wall │My│Non-load-bearing wall │ │ │Frame ┃
┠─────────────┬──────┤Force├────┬────┤Force├───┬───┤ │ │ ┃
┃ │UsageScale │Wall│Combustion Concern│Combustion Concern│Wall│boundaryWall│Elevator│ │ │ ┃
┃ │ │ │with START │MTQ8845b68899840b0703538 without START │ │ │ㆍStairs│ │ │ ┃
┃UsageClassification │FloorNumber/Highest │ │section │part │ │ │True │ │ │ ┃
┃ │Height(m) │ │ │ │ │ │VerticalWall│ │ │ ┃
┣━┯━━━━━━━━━━━┿━━━━┯━┿━┿━━━━┿━━━━┿━┿━━━┿━━━┿━━┿━━┿━━┫
┃day│Type 1 Neighborhood Living Facility, │12/50 │second│3 │1 │0.5 │3 │2 │2 │3 │2 │1 ┃
┃half│Type 2 Neighborhood Living Facility, │ │and│ │ │ │ │ │ │ │ │ ┃
┃Time│Cultural and assembly facilities, religious │ ├─┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃Section│Bridge facilities, sales facilities, transportation │ │이│2 │1 │0.5 │2 │1.5 │1.5 │2 │2 │0.5 ┃
┃ │Water facilities, educational and research facilities, │ │HA│ │ │ │ │ │ │ │ │ ┃
┃ │Facilities for the elderly and children, training facilities, ├────┴─┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃ │Sports facilities, Office facilities, │4/20 │1 │1 │0.5 │1 │1 │1 │1 │1 │0.5 ┃
┃ │Recreational facilities, automobile management │Below │ │ │ │ │ │ │ │ │ ┃
┃ │Related facilities (Maintenance plant No │ │ │ │ │ │ │ │ │ │ ┃
┃ │et al.), Animal and Plant House │ │ │ │ │ │ │ │ │ │ ┃
┃ │Related facilities, correctional and military │ │ │ │ │ │ │ │ │ │ ┃
┃ │Company facilities, broadcasting and telecommunications │ │ │ │ │ │ │ │ │ │ ┃
┃ │Installation, Power Generation Facility, Cemetery │ │ │ │ │ │ │ │ │ │ ┃
┃ │Related facilities, tourism and rest areas │ │ │ │ │ │ │ │ │ │ ┃
┃ │Facility, Funeral Facility │ │ │ │ │ │ │ │ │ │ ┃
┠─┼───────────┼───┬──┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃week│Detached house, multi-unit housing │12/50 │Second │2 │1 │0.5 │2 │2 │2 │3 │2 │1 ┃
┃Geo│Taxi, Accommodation, Medical │ │and │ │ │ │ │ │ │ │ │ ┃
┃Time│Facility │ ├──┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃Section│ │ │This │2 │1 │0.5 │2 │1 │1 │2 │2 │0.5 ┃
┃ │ │ │HA │ │ │ │ │ │ │ │ │ ┃
┃ │ ├───┴──┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃ │ │4/20 │1 │1 │0.5 │1 │1 │1 │1 │1 │0.5 ┃
┃ │ │Below │ │ │ │ │ │ │ │ │ ┃
┠─┼───────────┼────┬─┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃san│Factory, warehouse facilities, above │12/50 │Second│2 │1.5 │0.5 │2 │1.5 │1.5 │3 │2 │1 ┃
┃UP│Storage and Processing of Excavated Material │ │and│ │ │ │ │ │ │ │ │ ┃
┃Time│Facilities, Automotive Related │ ├─┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃Section│Maintenance plant among facilities, │ │이│2 │1 │0.5 │2 │1 │1 │2 │2 │0.5 ┃
┃ │Facilities related to natural circulation │ │HA│ │ │ │ │ │ │ │ │ ┃
┃ │ ├────┴─┼─┼────┼────┼─┼───┼───┼──┼──┼──┨
┃ │ │4/20 │1 │1 │0.5 │1 │1 │1 │1 │1 │0.5 ┃
┃ │ │Below │ │ │ │ │ │ │ │ │ ┃
┗━┷━━━━━━━━━━━┷━━━━━━┷━┷━━━━┷━━━━┷━┷━━━┷━━━┷━━┷━━┷━━┛
2. Application Criteria
a. Purpose
1) When a building is used for one or more purposes, standards according to the use classification in the table above
Apply the application with the highest fire resistance time among .
2) If the height or number of floors of different parts of a building differs, the maximum height or maximum number of floors
standard, apply the fire resistance time for each constituent member pursuant to Item 1 equally to the entire building
Uses.
3) The calculation of the number of floors and height of a building in terms of use-scale is in accordance with Article 119 of the Enforcement Decree of the Building Act.
shall apply. However, elevator shafts, stair towers, watchtowers, ornamental towers, rooftop towers, and other similar structures
The START section is excluded from the calculation of the building height and number of floors.
B. Components
1) Among the exterior walls, parts that are non-load-bearing walls and pose a risk of combustion are subject to the provisions of Article 22, Paragraph 2
refers to the minutes.
2) Parts of the exterior walls that are non-load-bearing walls and do not pose a risk of combustion are subject to the provisions of Article 22, Paragraph 2
.
3) Among interior walls, boundary walls that are non-load-bearing walls, walls that must be constructed of a fire-resistant structure in accordance with building regulations
says.
. Other criteria
1) Iron and steel plants, etc. with a low risk of fire, which are unavoidable for quality assurance
, the fire resistance time of the main structural parts is relaxed upon deliberation by the local architectural committee
can be applied.
2) The fire resistance performance test of the exterior wall shall be conducted by heating the interior surface of the building.