Annex 3 — 건축물의 설비기준 등에 관한 규칙
279459 · 2025-10-31
■ Rules on Building Equipment Standards, etc. [Appendix 3-3] <Amended Sep. 2, 2013>
Standards for Securing Installation Space for Electrical Facilities (Related to Article 20-2)
┌─────┬────────┬─────────────────────────────┐
│receiving voltage │Power Receiving Capacity │Secured Area │
├─────┼────────┼─────────────────────────────┤
│ExtraHighVoltage │100 kilowatts or more│Width 2.8 meters, Length 2.8 meters │
│or High Pressure │ │ │
├─────┼────────┼─────────────────────────────┤
│LowVoltage │75 kilowatts or more │Width 2.5 meters, Length 2.8 meters │
│ │Less than 150 kilowatts│ │
│ ├────────┼─────────────────────────────┤
│ │150 kilowatts or more│Width 2.8 meters, Length 2.8 meters │
│ │Less than 200 kilowatts│ │
│ ├────────┼─────────────────────────────┤
│ │200 kilowatts or more│Width 2.8 meters, Length 4.6 meters │
│ │Less than 300 kilowatts│ │
│ ├────────┼─────────────────────────────┤
│ │300 kilowatts or more│Width 2.8 meters or more, height 4.6 meters or more │
└─────┴────────┴─────────────────────────────┘
Remarks
1. The definitions of “low voltage,” “high voltage,” and “extra-high voltage” are respectively Article 2, Paragraph 8 of the Enforcement Rules of the Electric Power Business Act.
, Nos. 9 and 10.
2. The space for installing electrical facilities must not hinder the underground installation of pipes, manholes, etc., and the electricity provider's
It must be a location where maintenance, such as the installation, repair, inspection, and operation of electrical facilities, is easy.
3. The space for installing electrical facilities must be secured on the land outside the relevant building. However, external ground space
In cases where securing that space is impossible due to a narrow gap, there is no risk of flooding and moisture does not accumulate.
Space can be secured inside the building.
4. In cases where the receiving voltage is low voltage and the power receiving capacity is 300 kilowatts or more, etc., the power supply of a building
In cases where it is deemed necessary due to circumstances, the building owner and the electricity provider based on the above table
The secured area may be determined separately through consultation.
5. In cases where the receiving voltage is low voltage and the power receiving capacity is less than 150 kilowatts, power to the air
In the case of receiving , space for electrical equipment installation may not need to be secured.