Annex 2 — 건축물의 설비기준 등에 관한 규칙
279459 · 2025-10-31
■ Rules on Building Equipment Standards, etc. [Appendix 2] <Newly Added Aug. 31, 2002>
Criteria for Calculating Effective Area of Smoke Vents (Related to Article 14, Paragraph 1, Subparagraph 2)
1. Sliding Window : H×ℓ
H
┌────────────────────┐
│ℓ : Effective width of sliding window │
│H : Effective height of window │
│W : Window width │
└────────────────────┘
2. Pivot Axis Window : H×ℓ'/2×2
┌──────────────────────┐
│H : Effective height of window │
│ℓ : Perpendicular to the window when rotated 90° │
│Horizontal distance open in the START direction │
│Li │
│ℓ' : Window when less than 90° or greater than 0° │
│Open perpendicular to the arc │
│Horizontal Distance │
└──────────────────────┘
3. Pivot transverse window: (W×ℓ1)+(W×ℓ2)
┌──────────────────────┐
│W : Window width │
│ℓ1 : Upper window opening to the interior │
│의 길이방향으로 평행하게 │
│Open Pure Distance │
│ℓ2 : Lower window opened to the outside │
│As a START, parallel to the window frame │
│Open horizontal projection distance │
└──────────────────────┘
4. Casement : W×ℓ2
┌─────────────────────┐
│W : Window width │
│ℓ2: Open parallel to the window frame │
│Pure horizontal transparent area │
└─────────────────────┘
5. Middle Window: When the window opens to the outside: W×ℓ
If the window opens inward: W×ℓ1
(However, if the window is close to the ceiling: W×ℓ2)
┌────────────┐
│W : Window width │
│ℓ : Open to the outside │
│Longitude of auxiliary windows │
│Open in parallel with START │
│-designated pure distance │
│ℓ1 : Image opened towards the interior│
│Length direction of window and door │
│opened net distance │
│ℓ2 : Open parallel to the window frame│
│Purely Horizontal Projection │
│Area │
│* Window on ceiling (or semi-ceiling) │
│If close to START │
│ From the top of the window to the ceiling surface │
│Distance≤ℓ1 │
└────────────┘