Annex 1 — 건축물의 설비기준 등에 관한 규칙
279459 · 2025-10-31
■ Rules on Standards for Building Facilities, etc. [Appendix 1-6] <Amended Aug. 27, 2021>
Multi-use facilities requiring the installation of mechanical ventilation systems and the required ventilation volume for each facility
(Related to Article 11, Paragraph 5)
1. Multi-use facilities required to install mechanical ventilation equipment
A. Underground Facilities
1) All underground stations (entrance passages, waiting rooms, platforms and transfer passages and associated facilities
Includes)
2) Underground shopping malls with a gross floor area of 2,000 square meters or more (facilities in the basement attached to a ground-level building and
The total floor area of two or more consecutive underground shopping arcades is 2,000 square meters or more
(including cases)
B. Cultural and Assembly Facilities
1) Pursuant to Item 5(d) of Annex 1 of the Enforcement Decree of the Building Act, with a gross floor area of 2,000 square meters or more
Exhibition Hall (Limited to indoor exhibition halls)
2) "Act on the Establishment and Support of Sound Family Rituals" with a gross floor area of 2,000 square meters or more
에 따른 혼인예식장
3) A performance venue pursuant to Article 2, Subparagraph 4 of the “Performance Act” with a gross floor area of 1,000 square meters or more (indoor
Limited to performance venues)
4) "Setup of sports facilities" with a floor area used for spectator seating of 1,000 square meters or more
Sports facilities pursuant to Article 2, Subparagraph 1 of the Act on the Treatment and Use of Sports Facilities
5) A film award pursuant to Article 2, Item 10 of the Act on the Promotion of Films and Video Materials
Yeonggwan
. Sales facility
1) Large-scale store pursuant to Article 2, Subparagraph 3 of the Distribution Industry Development Act
2) Article 2, Paragraph 7 of the “Act on Promotion of Game Industry” with a gross floor area of 300 square meters or more
따른 인터넷컴퓨터게임시설제공업의 영업시설
ra. Transportation Facilities
1) Among port facilities pursuant to Article 2, Subparagraph 5 of the "Port Act," those with a gross floor area of 5,000 square meters or more
Waiting Room
2) Among passenger automobile terminals pursuant to Article 2, Subparagraph 5 of the "Passenger Automobile Transportation Business Act," annual
Waiting room with an area of 2,000 square meters or more
Among railway facilities pursuant to Article 3, Subparagraph 2 of the Framework Act on the Development of the Railway Industry, the gross floor area of 2,000
m²m² or more
4) Among airport facilities pursuant to Article 2, Subparagraph 7 of the "Airport Facilities Act," those with a gross floor area of less than 1,500 square meters
Passenger Terminal
E. Medical facilities: facilities with a gross floor area of 2,000 square meters or more or 100 or more beds
Medical institution pursuant to Article 3 of the Medical Service Act
B. Educational and Research Facilities
1) Libraries pursuant to Article 2, Subparagraph 1 of the “Libraries Act” with a gross floor area of 3,000 square meters or more
2) "Act on the Establishment and Operation of Private Educational Institutions and Private Tutoring" with a gross floor area of 1,000 square meters or more
rate” academy pursuant to Article 2, Subparagraph 1
Company. Facilities for the Elderly and Disabled
1) Children pursuant to Article 2, Subparagraph 3 of the "Infant and Toddler Care Act" with a gross floor area of 430 square meters or more
ThisHouse
2) Elderly persons pursuant to Article 34, Paragraph 1, Subparagraph 1 of the "Elderly Welfare Act" with a gross floor area of 1,000 square meters or more
Human nursing facility
A. Office facilities: Those with a gross floor area of 3,000 square meters or more, as specified in Annex 1, Item 14 of the Enforcement Decree of the Building Act.
에 따른 업무시설
J. Automobile-related facilities: Under Article 2, Paragraph 1 of the "Parking Lot Act" with a gross floor area of 2,000 square meters or more
(limited to indoor parking lots, and machinery pursuant to Article 2, Subparagraph 3 of the same Act
-type parking lots are excluded)
D. Funeral Home: A facility with a gross floor area of 1,000 square meters or more subject to Article 28-2 of the "Act on Funeral Services, etc."
Funeral homes pursuant to Paragraph 1 and Article 29 (limited to cases where installed underground)
K. Other facilities
1) Pursuant to Article 2, Paragraph 1, Subparagraph 3 of the "Public Health Management Act" with a gross floor area of 1,000 square meters or more
Business facilities of other bathhouse businesses
2) Postpartum facilities pursuant to Article 2, Item 10 of the “Maternal and Child Health Act” with a gross floor area of 500 square meters or more
Postpartum Care Center
3) Article 2 of the “Children’s Play Facilities Safety Management Act” with a gross floor area of 430 square meters or more
2
2. Required ventilation volume for each facility
┏━━━━━━━━━━━━━━┯━━━━━━━━━━━┯━━━━━━━━━━━━━┓
┃Classification │Required ventilation (㎥/person·h) │Remarks ┃
┠──────┬───────┼───────────┼─────────────┨
┃A. Underground Facilities│1) Underground Station │25 or more │ ┃
┃ ├───────┼───────────┼─────────────┨
┃ │2) Underground Shopping Arcade │36 or more │Store (Shop) Standard ┃
┠──────┴───────┼───────────┼─────────────┨
┃B. Cultural and Assembly Facilities │29 or later │ ┃
┠──────────────┼───────────┼─────────────┨
┃. Sales facility │29 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃ra. Transportation Facilities │29 or later │ ┃
┠──────────────┼───────────┼─────────────┨
┃E. Medical Facilities │36 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃B. Educational and Research Facilities │36 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃Company. Facilities for the Elderly and Disabled │36 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃A. Office Facilities │29 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃. Automotive-related facilities │27 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃Car. Funeral Home │36 or more │ ┃
┠──────────────┼───────────┼─────────────┨
┃K. Other facilities │25 or more │ ┃
┗━━━━━━━━━━━━━━┷━━━━━━━━━━━┷━━━━━━━━━━━━━┛
Remarks
a. When calculating the gross floor area or floor area in Subparagraph 1, facilities installed in the indoor space
It is calculated based on the gross floor area or floor area occupied.
B. The required ventilation volume is calculated based on the time of day with the highest expected number of users.
. In the case of rooms used for special purposes, such as operating rooms, among medical facilities, the relevant central administration
The head of the regular institution may determine otherwise.
d. The required ventilation volume for automobile-related facilities under Subparagraph (j) of Item 1 is the ventilation volume per unit area (㎥/㎡·h)
.