■ Rules on Building Equipment Standards, etc. [Appendix 1-5] <Amended Apr. 9, 2020>
Installation Standards for Mechanical Ventilation Facilities in Newly Constructed Multi-Unit Housing, etc. (Related to Article 11, Paragraph 3)
In order to secure the ventilation frequency of newly constructed multi-unit housing, etc. pursuant to the provisions of Article 11, Paragraph 1, ...
The design, construction, and performance evaluation methods of mechanical ventilation systems shall comply with the standards of each of the following subparagraphs.
must.
1. The ventilation standard for mechanical ventilation systems is the number of indoor air exchanges per hour (final
The total hourly volumetric airflow supplied from the air intake to the interior of the unit is the total interior volume.
It must be indicated as the ventilation rate divided by ).
2. When supplying outside air to two or more rooms within a household with a single mechanical ventilation system
The ventilation volume must be greater than or equal to the sum of the ventilation volumes required for each room.
3. To control the ventilation volume of the household, the rated airflow of the ventilation equipment is set to minimum, appropriate, and maximum 3
It must be equipped with a system capable of adjusting to the START stage or higher, and the necessity of an appropriate stage
The ventilation volume is the airflow capable of ventilating households in newly constructed multi-unit housing, etc., at 0.5 times per hour.
Must be provided.
4. The air supply system or air exhaust system shall [contain] the sum of all pressure losses, including partial losses
The air supply capacity or air exhaust capacity calculated in consideration of the ventilation standards of Article 11, Paragraph 1 is...
can be secured.
5. Mechanical ventilation facilities for all households in newly constructed multi-unit housing, etc., pursuant to the provisions of Article 11, Paragraph 1
It must be able to operate 24 hours a day to satisfy the ventilation rate.
6. The materials of each part of the mechanical ventilation system shall maintain sufficient durability and strength during operation
shall ensure that there is no deformation in structure and performance during.
7. Mechanical ventilation equipment shall be equipped with a system corresponding to any of the following items.
a. Ventilation combining a fan supplying outside air and a fan exhausting indoor air
System
B. Ventilation combining a blower supplying outside air and an exhaust vent discharging indoor air
System
. It is
Ventilation System
8. An air supply system that supplies outside air or an air intake into which outside air is introduced
Must be equipped with an air filter or dust collector, etc. that meets all of the requirements of each of the following items.
However, in the case where a ventilation system pursuant to Subparagraph 7(c) is installed, in accordance with Subparagraph 5 of Annex 1-4
.
a. When the performance for removing or filtering particulate or gaseous pollutants is above a certain level
thing
b. It shall have a structure that facilitates easy maintenance, such as cleaning and replacement of filtration devices, etc.
In the case of air filters, the particle capture rate according to the Korean Industrial Standard (KS B 6141) is
Measured by the method, be 60 percent or higher
9. The efficiency and performance, etc. of equipment, devices, apparatus, and products constituting mechanical ventilation systems
In making a judgment, regarding matters not specified in this rule, for the relevant item
Must conform to Korean Industrial Standards.
10. Mechanical ventilation equipment shall be installed in a location that maximizes ventilation efficiency, and
To minimize the impact of fluctuations in outside air, air intakes or exhaust vents, etc.
A buffer device or a grill-type wire mesh, etc., must be installed at .
11. Mechanical ventilation equipment includes the air exhaust device above the kitchen gas stove and the air exhaust blower in the bathroom
It can be installed together with rapid ventilation equipment such as .
12. The air intakes and exhausts, the air supply system, and the air exhaust system shall be mechanical ventilation equipment
does not interfere with the use of the target space
.
13. The measurement of noise generated from mechanical ventilation systems shall be in accordance with the Korean Industrial Standard (KS B 6361)
. The measurement location shall be a representative length of 1 meter (vertical or horizontal
section, and the ambient noise (the noise subject to measurement
) must be corrected. However, ventilation equipment
If the main unit (noise source) is installed outside the living space, the representative length is 1 meter (vertical and
is measured at the horizontal bottom) and becomes 50dB or less, or the central part inside the living space
Must be 40dB or less when measured at a height of 1.0 to 1.2 meters from the floor.
14. External air intakes and exhausts shall be 1.5 mi to prevent cross-contamination
or the directions of the air intake and exhaust ports relative to each other
It must also be installed in a location where it is safe, and capable of preparing for safety in case of emergencies such as fire.
Structure and performance must be ensured.
15. When installing a heat recovery ventilation system for energy saving in mechanical ventilation systems
, the effective ventilation of a heat recovery type ventilation system tested according to the Korean Industrial Standard (KS B 6879)
The amount must be at least 90 percent of the indicated capacity, and the inside and outside of the heat recovery ventilation system
must ensure structure and performance capable of minimizing water condensation
.
16. Mechanical ventilation equipment includes blowers, heat recovery ventilation units, air filters, air passages,
Regular inspection and maintenance of major parts, such as air intakes and exhausts, and other equipment
It must be configured as a system that facilitates easy maintenance, and the product specifications and technical specifications must include maintenance
related content must be specified, and the user manual containing maintenance-related content
Must present.
17. Mechanical ventilation equipment, such as ventilation fans, shall not be operated depending on outdoor weather conditions
Even if a mixed-type ventilation system capable of simultaneous operation of natural and mechanical ventilation is designed...
], cases objectively proven to be able to secure the necessary ventilation volume [
, it may be recognized as being equipped with mechanical ventilation facilities. In this case, to be operated simultaneously
Natural ventilation facilities and mechanical ventilation facilities capable of meeting the ventilation standards of Article 11, Paragraph 1, respectively
must be able to satisfy.
18. Centralized air conditioning system (appropriately controlling indoor temperature, humidity, and cleanliness, etc.
In cases where equipment serving the role of maintaining (referring to facilities that perform the role of maintaining) is installed, in accordance with the standards of each of the following items
must also be compliant.
a. The air conditioning system shall be capable of continuous ventilation 24 hours a day. However, major ventilation
By installing a separate ventilation system separated from the facility in parallel, local contamination present indoors
In the case of configuring a system capable of rapidly discharging pollutants generated from the source
is not so.
B. Management capable of controlling the control and operating status of centrally managed air conditioning equipment
There shall be a seal or function