■ Rules on Building Equipment Standards, etc. [Appendix 1-4] <Amended Aug. 7, 2024>
Installation Standards for Natural Ventilation Facilities in Newly Constructed Multi-Unit Housing, etc. (Related to Article 11, Paragraph 3)
Pursuant to Article 11, Paragraph 1, the design, construction, and performance evaluation methods for natural ventilation systems installed in newly constructed multi-unit housing, etc. are as follows:
It must comply with the standards of .
1. The natural ventilation system installed in the unit shall be configured to supply outside air as uniformly as possible to all rooms within the unit
must be installed.
2. In order to control the ventilation volume of the household, the natural ventilation system must be equipped with a system capable of controlling the ventilation volume, and the maximum opening
Based on the ventilation volume in the START state, it must be installed with an installation length greater than or equal to that specified in Appendix 1-3.
3. Natural ventilation systems [describe] excessive outside air that may occur due to sudden external winds and an increase in the pressure difference between the inside and outside
It must be equipped with a structure and form capable of minimizing the impact of fluctuations in outside air, such as the inflow of START.
4. The materials of each part of the natural ventilation system shall maintain sufficient durability and strength so that changes in structure and performance during operation
type, and discomfort that may occur due to surface condensation and the direct influx of outside air (cold drawer
It must be equipped with materials and a structure capable of preventing (etc.).
5. Natural ventilation systems shall be equipped with air filters that meet all of the requirements of the following items.
a. The performance of removing or filtering particulate and gaseous pollutants contained in the incoming outside air is a certain number
should be above standard
b. The particle capture rate according to the Korean Industrial Standard (KS B 6141) shall be 70 percent or higher as measured by the mass method.
. It must have a structure that is easy to clean or replace
6. In determining the efficiency and performance, etc., of equipment, devices, apparatus, and products constituting a natural ventilation system, [not specified in this rule]
shall conform to the Korean Industrial Standards for the relevant items.
7. Install in a location that does not impede the use of the target space even when the natural ventilation system is operated continuously
must be installed.
8. Delete <2024. 8. 7.>
9. Natural ventilation systems should be installed in a location where external contaminants are not introduced as much as possible, and fire, etc. In case of emergency
must be secured.
10. A natural ventilation system capable of preheating outside air introduced indoors has a structure that is as energy-efficient as possible
.
11. Natural ventilation systems shall be configured as a system that facilitates easy maintenance, such as periodic inspection and maintenance of key parts, and the product's
Maintenance-related details must be specified in the specifications and technical documents, and the user manual containing maintenance-related details
must be provided.
12. Natural ventilation equipment shall be installed at a vertical height of at least 1.2 meters from the floor of the room where it is installed, and two or more
When installing natural ventilation systems vertically, a vertical spacing of at least 1 meter must be secured.