■ Rules on Building Equipment Standards, etc. [Appendix 1-3] <Amended Aug. 27, 2021>
Method for Calculating Installation Length and Installation Standards for Natural Ventilation Systems (Related to Article 11, Paragraph 2)
1. Calculation of Volume of Target Household
- To calculate the ventilation volume capable of satisfying the required ventilation rate
To the entire unit of a multi-unit dwelling where a natural ventilation system is to be installed,
Calculate room volumes.
2. Calculation formulas for installation lengths for the entire unit and per room Installation standards
- The installation lengths of natural ventilation systems for the entire unit and per room are Korean Industrial Standards
and
Using the evaluation results obtained by the ventilation volume measuring device of the natural ventilation system
and must be installed with an installation length L value or greater calculated according to the following formula
...while doing so, weights by generation and actual characteristics must be considered.
Here, : Installation length for the entire unit or per room (Effective opening length
This standard, m)
: Entire household or actual volume (m3)
: Required ventilation rate (0.5 times/h)
: Evaluated by a ventilation volume measuring device of a natural ventilation system
Ventilation rate (m3/h·m) at a reference pressure difference (2 Pa)
: Weights by Generation and Real Characteristics**
<Remarks>
* Generally, the part joined to the window frame (endcap) and the actual air inflow
is formed, effective
The opening length (installation length) is the actual opening excluding the part joined to the window frame.
Calculate based on the curved part.
** By unit and room characteristics considering building types and unit design conditions
The weights are as follows.
┌─────┬────────────────┬───┐
│Category │condition │Weight│
├─────┼────────────────┼───┤
│Generation Condition │1 If one side faces the outside │1.5 │
│ ├────────────────┼───┤
│ │2 The two faces are parallel to the exterior. │1 │
│ │U │ │
│ ├────────────────┼───┤
│ │2 The face is not parallel to the exterior │1.2 │
│ │is the case │ │
│ ├────────────────┼───┤
│ │When 3 or more sides face the outside │1 │
├─────┼────────────────┼───┤
│Real Condition │When the target thread is directly facing the outside │1 │
│ │U │ │
│ ├────────────────┼───┤
│ │The target thread does not directly face the outside │1.5 │
│ │is the case │ │
└─────┴────────────────┴───┘
However, if the generation condition and the actual condition overlap, the one with the higher weight shall be applied
is based on the principle.
***
The above calculation formula cannot be applied, and the deliberation of the Local Architectural Committee
must pass through.