Form 9 — 소방시설 설치 및 관리에 관한 법률 시행규칙
287831 · 2026-07-01
■ Enforcement Rules of the Act on the Installation and Management of Firefighting Facilities [Attachment Form No. 9] <Amended Dec. 1, 2025> (Page 1 of 8)
[ ] Operational Inspection, Comprehensive Inspection ([ ] Initial Inspection, [ ] Other Comprehensive Inspection)
Report on Results of Self-Inspection of Firefighting Facilities, etc.
※ [ ].
─────┬────────────────┬───────────────────────────────────────────
Specific Fire Safety│Name (Trade Name) │Target Classification (Use)
Target Object├────────────────┴───────────────────────────────────────────
│Location
─────┴────────────────────────────────────────────────────────────
─────┬────────────────────────────────────────────────────────────
InspectionPeriod│ Year month day ~ Year month Days (Total Days of Inspection: day )
─────┼────────────────────────────────────────────────────────────
Inspector │ [ ]Related Party (Name: , Phone number: )
│ [ ]Fire Safety Manager (Name: , Phone number: )
│ [ ]Fire Facility Management Operator (Company name: , Phone number: )
├─────────┬──────────────────────────────────────────────────
│Email │Under Article 14 of the Administrative Procedures Act, I consent to the service of documents via an information and communications network
│Consent to Delivery │I agree.
│ ├──────────────────────────────────────────────────
│ │[ ] Agree [ ] Disagree
│ ├──────────────────────────────────────────────────
│ │ RelatedParty (Signature or seal)
│ ├──────────────────────────────────────────────────
│ │Email Address @
─────┼─────────┼──┬─────┬────┬────────────────────────────────────
InspectionPersonnel│Classification │Name│QualificationClass │QualificationNumber│Inspection Participation Date (Period)
├─────────┼──┼─────┼────┼────────────────────────────────────
│Main inspection personnel │ │ │ │
├─────────┼──┼─────┼────┼────────────────────────────────────
│Auxiliary Inspection Personnel │ │ │ │
├─────────┼──┼─────┼────┼────────────────────────────────────
│Auxiliary Inspection Personnel │ │ │ │
├─────────┼──┼─────┼────┼────────────────────────────────────
│Auxiliary Inspection Personnel │ │ │ │
├─────────┼──┼─────┼────┼────────────────────────────────────
│Auxiliary Inspection Personnel │ │ │ │
├─────────┼──┼─────┼────┼────────────────────────────────────
│Auxiliary Inspection Personnel │ │ │ │
─────┴─────────┴──┴─────┴────┴────────────────────────────────────
Under Article 23(3) of the Act on the Installation and Management of Firefighting Facilities and Article 23(1)
and (2) of its Enforcement Rules, I hereby submit the report on the results of the self-inspection of firefighting facilities.
Year month day
Fire Facility Management Provider, Fire Safety Manager, or Person Responsible: (Signature or seal)
To the Person Responsible, Head of ○○ Fire Headquarters, or Fire Station Chief
──────────────┬───────────────────────────────────────────────────
Classification │Attached Documents
──────────────┼───────────────────────────────────────────────────
Firefighting facility management business operator or │Firefighting facility inspection checklist prescribed and notified by the Commissioner of the National Fire Agency
Submitted by Fire Safety Manager │
to the Person Responsible │
──────────────┼───────────────────────────────────────────────────
Submitted by the Person Responsible to the Head of │1. Confirmation of Inspection Personnel Deployment (Submit only if the inspection was conducted by a fire safety facility management company) 1 copy
Fire Headquarters or the Fire Station Chief │2. Implementation Plan for Self-Inspection Results of Firefighting Facilities, etc. (Form No. 10)
━━━━━━━━━━━━━━┷━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
Important Notes
───────────┬──────────────────────────────────────────────────────
「Firefighting Facilities Installation and │1. If the person responsible for premises fails to conduct self-inspection of firefighting facilities or to arrange for regular inspection by a service provider,
Act on the Installation and Management of Firefighting Facilities │that person is subject to imprisonment for not more than one year or a fine not exceeding 10 million won.
Article 58, subparagraph 1 and │2. If the person responsible for premises fails to report the results of self-inspection or reports false results,
Article 61, Paragraph 1, Subparagraph 8 │an administrative fine not exceeding 3 million won may be imposed.
───────────┴──────────────────────────────────────────────────────
210mm×297mm[White paper (80g/㎡) or medium paper (80g/㎡)]
(Page 2 of 8)
Specific Fire Safety Target Information
※ [ Mark the relevant box with a √.
──────────────────────────────────────────────────────
1. Fire Safety Information
──────┬───────────────────────────────────────────────
Representative │ [ ]Owner, [ ]Administrator, [ ]Occupant / Name: , Phone number:
──────┼───────────────────────────────────────────────
FireSafety │ [ ] Special Grade, [ ]Level 1, [ ]Level 2, [ ]Level 3
ManagementGrade │
──────┼───────────────────────────────────────────────
Fire Safety │ [ ] Firefighting Technical Qualification, [ ]Fire Safety Manager's Handbook, [ ] Supervision of Outsourced Duties, [ ]Concurrent position, [ ]Other
Administrator │Name: , Phone number: , Date of last training completion: Year month day
──────┼───────────────────────────────────────────────
Firefighting Plan│ [ ] Prepared ([ ] Retained [ ] Not Retained), [ ] Not Prepared
──────┼───────────────────────────────────────────────
Self-check │ Operation Check ([ ] Conducted [ ] Not Conducted), Comprehensive Inspection ([ ] Conducted [ ] Not Conducted)
(Previous Year) │
──────┼───────────────────────────────────────────────
Education & Training │ Fire Safety Education ([ ] Conducted [ ] Not Conducted), Fire Drill ([ ] Conducted [ ] Not Conducted)
──────┼───────────────────────────────────────────────
FireInsurance │ [ ]Sign up, [ ]Not registered
│Insurer: , Coverage Period: Year month day ~ Year month day
│Insured Amount: Bodily Injury ( Ten Million Won) Property Damage ( Ten Million Won)
──────┼───────────────────────────────────────────────
Multi-use │[ ]Rest Area Food Service Business( Opening) [ ]Bakery Business( Opening) [ ]General Restaurant Business( Opening)
Business Status │[ ]Karaoke Bar Business( Opening) [ ]Entertainment Bar Business( Opening) [ ]Movie Theater( Opening)
│[ ]Video Appreciation Business( Opening) [ ]Video Small Theater Business( Opening) [ ]Complex Video Provision Business( Opening)
│[ ] Academy ( Opening) [ ]Reading Room( Opening) [ ]Bathhouse Business( Opening)
│[ ]Jjimjilbang Business( Opening) [ ]Game Provision Business( Opening) [ ]Internet Computer Game Facilities
│[ ]Complex Distribution Game Provision Business( Opening) [ ]Singing Practice Room Business( Opening) provided( Opening)
│[ ]Postpartum Care Business( Opening) [ ]Goshiwon Business( Opening) [ ]Pistol Shooting Range( Opening)
│[ ]Virtual Experience Sports Facility Business( Opening) [ ]Massage Parlor( Opening) [ ]Telephone booth business( Opening)
│[ ]Video chat room business( Opening) [ ] Sleeping Room Business ( Opening) [ ] Colatheque Business ( Opening)
│[ ]Not applicable
──────┴───────────────────────────────────────────────
2. Building Information
──────┬─────────────────┬───────┬─────────────────────
Building Permit Date│ Year month day │Date of Approval │ Year month day
──────┼────────┬────────┼───────┼──────┬──────────────
Gross Floor Area │ ㎡ │Building Area │ ㎡ │Number of Households │
──────┼────────┴────────┼───────┼──────┼────┬─────────
Number of floors │ Ground Floor / Basement floor │high This │ m │Number of Buildings│ buildings
──────┼─────────────────┴───────┴──────┴────┴─────────
Building Structure│ [ ]Concrete structure, [ ]Steel structure, [ ]Masonry, [ ]wooden structure, [ ]Other
──────┼─────────────────────────┬──────┬──────────────
Roof Structure │ [ ]Slab, [ ]Tile, [ ]Slate, [ ]Other │Ramp │ locations
──────┼─────────────────────────┴──────┴──────────────
Stairs │ [ ] Direct Stairs (or Evacuation Stairs) ( locations), [ ]Special Evacuation Stairs ( Opening)
──────┼───────────────────────────────────────────────
Elevator │ [ ] Passenger Elevator ( units), [ ] Emergency Elevator ( units), [ ] Evacuation Elevator ( )
──────┼───────────────────────────────────────────────
Parking Lot │ [ ]Indoor([ ]Underground [ ]Ground [ ]Piloti [ ]Mechanical), [ ]Rooftop, [ ]Outdoor
──────┴───────────────────────────────────────────────
(Page 3 of 8)
Status of Firefighting Facilities, etc.
※ [ In [], mark the relevant facility with a √, and in the Inspection Result column, indicate Good ○, Poor ×, or mark / for unapplicable items. (side 1)
──────────────────────────────────────────────────────────
1. Results of Firefighting Facility Inspection
┌──┬────────────────────┬────┬───┬──────────────────┬────┐
│Classification│해 PER Description non │InspectionResult│Classification │해 PER Description non │InspectionResult│
├──┼────────────────────┼────┼───┼──────────────────┼────┤
│Extinguishment│ [ ] Fire extinguishing equipment and automatic fire extinguishing devices │ │Evacuation │ [ ]Evacuation Equipment │ │
│Equipment│ [ ] Fire Extinguishing Equipment (Fire Extinguisher, Automatic Diffusion, Portable) │ │structure │ [ ] Air Safety Mat · Escape Ladder │ │
│ │ [ ]Residential Kitchen Automatic Fire Extinguishing System │ │equipment │ Descent Devices (including Simple Descent Devices), Slides, Rescue Chutes│ │
│ │ [ ]Commercial Kitchen Automatic Fire Extinguishing System │ │ │ [ ]Multiple Personnel Evacuation Equipment │ │
│ │ [ ]Cabinet-type automatic fire extinguishing device │ │ │ [ ] Elevating-Type Evacuation Device │ │
│ │ [ ]Gas·Powder·Solid Automatic Fire Extinguishing Device │ │ │ Downward-type escape ladder │ │
│ ├────────────────────┼────┤ ├──────────────────┼────┤
│ │ [ ] Indoor Fire Hydrant System │ │ │ [ ]Lifesaving Equipment │ │
│ │ │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ] Exit Lights │ │
│ │ [ ]Sprinkler System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Guide Marker │ │
│ │ [ ]Simplified Sprinkler System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Evacuation guidance line │ │
│ │ [ ] Early Fire Suppression Sprinkler System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Emergency Lighting │ │
│ │ [ ]Water Spray Fire Extinguishing System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Portable Emergency Light │ │
│ │ [ ] Fine mist fire extinguishing system │ ├───┼──────────────────┼────┤
│ ├────────────────────┼────┤Extinguishment │ [ ]Water Supply and Firefighting Equipment │ │
│ │ [ ] Foam Fire Extinguishing System │ │water ├──────────────────┼────┤
│ ├────────────────────┼────┤equipment │ [ ] Firefighting water tank and reservoir │ │
│ │ [ ]Carbon Dioxide Fire Extinguishing System │ ├───┼──────────────────┼────┤
│ ├────────────────────┼────┤Extinguishment │ [ ]Living Room Smoke Control Equipment │ │
│ │ [ ]Halon Fire Extinguishing System │ │Activity ├──────────────────┼────┤
│ ├────────────────────┼────┤equipment │ [ ] Smoke control equipment for ancillary rooms │ │
│ │ [ ] Halogen Compound and Inert Gas Fire Extinguishing System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ] Fire Department Connection System │ │
│ │ [ ] Powder Fire Extinguishing System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ] Connected Sprinkler System │ │
│ │ [ ]Reinforced Liquid Fire Extinguishing Equipment │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Emergency Outlet Equipment │ │
│ │ [ ]Solid Aerosol Fire Extinguishing System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Wireless Communication Auxiliary Equipment │ │
│ │ [ ]Outdoor Fire Hydrant System │ │ ├──────────────────┼────┤
│ │ │ │ │ [ ] Combustion Prevention Equipment │ │
├──┼────────────────────┼────┼───┼──────────────────┼────┤
│Alert│ [ ]Standalone Alarm Type Detector │ │Other │ [ ] Fire door, automatic fire shutter │ │
│Equipment├────────────────────┼────┤ │ │ │
│ │ [ ]Emergency Alarm System │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ]Emergency Exit, Evacuation Route │ │
│ │ [ ]Automatic fire detection system and visual alarm │ │ │ │ │
│ ├────────────────────┼────┤ │ │ │
│ │ [ ]Fire Alarm System │ │ │ │ │
│ ├────────────────────┼────┤ │ │ │
│ │ [ ]Emergency Broadcasting Equipment │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ] Flame Yeom │ │
│ │ [ ] Retardancy │ │ │ │ │
│ ├────────────────────┼────┼───┼──────────────────┴────┤
│ │ [ ] Automatic Fire Notification System │ │Remarks │ │
│ ├────────────────────┼────┤ │ │
│ │ [ ]Leakage Alarm │ │ │ │
│ ├────────────────────┼────┤ │ │
│ │ [ ]Gas Leak Alarm │ │ │ │
└──┴────────────────────┴────┴───┴───────────────────────┘
2. Results of Inspection of Safety Facilities, etc. (Multi-use Establishments)
┌──┬────────────────────┬────┬───┬──────────────────┬────┐
│Classification│해 PER Description non │InspectionResult│Classification │해 PER Description non │InspectionResult│
├──┼────────────────────┼────┼───┼──────────────────┼────┤
│Extinguishment│ [ ] Fire Extinguisher or Automatic Diffusion Fire Extinguisher │ │Emergency Exit│ [ ]Fire door │ │
│equipment├────────────────────┼────┤ ├──────────────────┼────┤
│ │ [ ]Simplified Sprinkler System │ │ │ [ ]Emergency Exit (Emergency Escape Exit) │ │
├──┼────────────────────┼────┼───┼──────────────────┼────┤
│Alert│ [ ] Emergency alarm system or │ │Other │ [ ]Internal Evacuation Route within Business premises │ │
│Equipment│ Automatic Fire Detection System │ │ ├──────────────────┼────┤
│ │ │ │ │ [ ]Video and Audio Blocking Device │ │
│ ├────────────────────┼────┤ ├──────────────────┼────┤
│ │ [ ]Gas Leak Alarm │ │ │ [ ] Earth Leakage Circuit Breaker │ │
├──┼────────────────────┼────┤ ├──────────────────┼────┤
│Evacuation│ [ ]Evacuation Equipment │ │ │ [ ]Window │ │
│structure│ │ │ ├──────────────────┼────┤
│Equipment├────────────────────┼────┤ │ [ ] Evacuation Guide Map, Evacuation Guide Video │ │
│ │ [ ]Evacuation guidance line │ │ ├──────────────────┼────┤
│ ├────────────────────┼────┤ │ [ ] Flame-retardant items │ │
│ │ [ ] Exit lights, exit signs, or emergency lighting │ ├───┼──────────────────┴────┤
│ ├────────────────────┼────┤Remarks │ │
│ │ [ ]Portable Emergency Light │ │ │ │
└──┴────────────────────┴────┴───┴───────────────────────┘
(Page 4 of 8)
3. Detailed Status of Firefighting Facilities, etc.
3-1. Fire extinguishing equipment, automatic fire extinguishing devices
──────┬─────────┬──────────┬─────┬────┬───────────
Classification │[ ] Fire Extinguisher │[ ] Simple fire extinguisher │[ ] Auto │[ ] Auto│Remarks
├────┬────┼─────┬────┤Diffusion Fire Extinguisher│Fire extinguishing device│
│[ ] Powder│[ ] Other│[ ] Throwing│[ ] Other│ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
Total│ │ │ │ │ │ │
Building Name │ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┼────┼────┼─────┼────┼─────┼────┼───────────
│ │ │ │ │ │ │
──────┴────┴────┴─────┴────┴─────┴────┴───────────
3-2. Water-based Fire Extinguishing Systems (General Requirements)
───┬──────┬───────────────────────────────────────
Water Source│Main Water Supply │? Type of equipment: [ ] Indoor fire hydrant system, [ ] Outdoor fire hydrant system, [ ] Sprinkler system,
│ │[ ]Simplified sprinkler system, [ ]Sprinkler system for early fire suppression, [ ]Water spray fire extinguishing
│ │Equipment, [ ] Fine mist fire extinguishing system, [ ] Foam fire extinguishing system
│ │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│ │? Suction Method: [ ] Positive Pressure, [ ] Negative Pressure ? Valid Quantity: ( )㎥
├──────┼───────────────────────────────────────
│Auxiliary Water Supply │? Installation Location: Building Name ( ) Room Name ( ), ? Valid Quantity: ( )㎥
───┼──────┼───────────────────────────────────────
pressurization│[ ] Elevated Water Tank │? Type of equipment: [ ] Indoor fire hydrant system, [ ] Outdoor fire hydrant system, [ ] Sprinkler system,
Water Supply│ │[ ]Simplified sprinkler system, [ ]Sprinkler system for early fire suppression, [ ]Water spray fire extinguishing
Device│ │Equipment, [ ] Fine mist fire extinguishing system, [ ] Foam fire extinguishing system
│ │
│ │? Installation Location: Dongmyeong( ) Room Name ( ), ? Effective head: ( )m
├──────┼───────────────────────────────────────
│[ ]Pressure tank │? Type of equipment: [ ] Indoor fire hydrant system, [ ] Outdoor fire hydrant system, [ ] Sprinkler system,
│ │[ ]Simplified sprinkler system, [ ]Sprinkler system for early fire suppression, [ ]Water spray fire extinguishing
│ │Equipment, [ ] Fine mist fire extinguishing system, [ ] Foam fire extinguishing system
│ │
│ │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│ │? Tank Capacity: ( )ℓ, Water tank pressurization:( )MPa
│ │? Automatic Air Compressor Capacity:( )㎥/min, Power:( )Kw
├──────┼───────────────────────────────────────
│[ ]Pressurized water tank │? Type of equipment: [ ] Indoor fire hydrant system, [ ] Outdoor fire hydrant system, [ ] Sprinkler system,
│ │[ ]Simplified sprinkler system, [ ]Sprinkler system for early fire suppression, [ ]Water spray fire extinguishing
│ │Equipment, [ ] Fine mist fire extinguishing system, [ ] Foam fire extinguishing system
│ │
│ │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│ │? Tank Capacity: ( )ℓ, Water tank pressurization:( )MPa
│ │? Type of pressurized gas: [ ] Air [ ] Non-combustible gas( )
───┴──────┴───────────────────────────────────────
Remarks
1. You may only fill out this for firefighting facilities installed in the relevant specific firefighting target building.
2. [ ], mark the relevant facility with a √ and enter the detailed status and installed quantity.
3. If there is insufficient input space, you can add forms to fill it out.
──────────────────────────────────────────────────
(Page 5 of 8)
───────┬──────┬───────────────────────────────────────
pressurization │[ ] Pump Type │? Type of equipment: [ ] Indoor fire hydrant system, [ ] Outdoor fire hydrant system, [ ] Sprinkler system,
Water Supply │ │[ ]Simplified sprinkler system, [ ]Sprinkler system for early fire suppression, [ ]Water spray fire extinguishing
Device │ │Equipment, [ ] Fine mist fire extinguishing system, [ ] Foam fire extinguishing system
│ │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ │? Main Pump Total Head: ( )m, discharge volume:( )ℓ/min
│ │ [ ] Electric Motor [ ] Internal Combustion Engine(Fuel:[ ] Diesel [ ] Others
│ │? Spare pump Total Head: ( )m, discharge volume:( )ℓ/min
│ │ [ ] Electric Motor [ ] Internal Combustion Engine(Fuel:[ ] Diesel [ ] Others
│ │? Pressure Maintenance Pump Total Head: ( )m, discharge volume:( )ℓ/min
│ │? [ ] Water Priming Device (Effective Water Volume: ( )ℓ, water supply piping: ( )㎜
│ │? Starting Device: [ ] Pressure Switch Starting Device, [ ] ON/OFF Type
│ │ [ ]Pressure Chamber(Volume:( )ℓ, operating pressure:( )MPa
│ │ [ ] Pressure switch for starting ([ ] Bourdon tube type [ ] Electronic type [ ] Others)
│ │? [ ] Pressure reducing device [ ] Above ground/[ ] Underground ( )Floor, Installation Location:( )
───────┼──────┴───────────────────────────────────────
Fire Department Connection Inlet │[ ] Indoor Fire Hydrant System [ ] Outdoor Fire Hydrant System [ ] Sprinkler System [ ] Simplified Sprinkler System
│[ ] Early Fire Suppression Sprinkler System [ ] Water Spray Fire Extinguishing System [ ] Fine Mist Fire Extinguishing System [ ] Foam Fire Extinguishing System
│? Installation Location:( ), [ ] Two-Inlet Type ( ) units / [ ] Single-Inlet Type ( )ea
───────┼──────────────────────────────────────────────
EmergencyPower │ [ ]Self-generating power facility([ ]Firefighting exclusive [ ]Dual-use for firefighting loads [ ]Firefighting power preservation type [ ]Others( ))
│ [ ]Emergency Power Receiving Equipment [ ]Battery Equipment [ ]Electric Storage Device
│? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
───────┴──────────────────────────────────────────────
3-3. Water-based Fire Extinguishing System (Individual Items)
───────┬──────────────────────────────────────────────
[ ]Indoor │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
Fire Hydrant │ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Number of installations on the floor with the most installations: ( )dog
───────┼──────────────────────────────────────────────
[ ] Outdoor │? Installation count: ( )dog
Fire Hydrant │
───────┼──────────────────────────────────────────────
[ ] Sprink │? Type: [ ] Wet [ ] Negative-Pressure [ ] Preaction [ ] Dry [ ] Deluge
ler System │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┼──────────────────────────────────────────────
[ ] Simplified Sprink│? Type: [ ] Pump [ ] Cabinet [ ] Municipal Water Supply
ler System │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┼──────────────────────────────────────────────
[ ] Fire │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
For early suppression │ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┼──────────────────────────────────────────────
[ ] Water Spray │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
FireExtinguishingSystem │ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┼──────────────────────────────────────────────
[ ] Fine spray │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
FireExtinguishingSystem │ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┼──────────────────────────────────────────────
[ ] po │[ ] Foam water sprinkler system [ ] Foam head system [ ] Fixed foam discharge system [ ] Others( )
FireExtinguishingSystem │? Fire extinguishing agent [ ] Protein foam [ ] Synthetic surfactant foam [ ] Aqueous film-forming foam [ ] Alcohol-resistant foam
│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
───────┴──────────────────────────────────────────────
3-4. Gas-based Fire Extinguishing System (Individual Items)
─────────┬────────────────────────────────────────────
[ ]Carbon Dioxide │[ ] Total Flooding [ ] Local Application [ ] Hose Reel / [ ] High-Pressure [ ] Low-Pressure / [ ] Stored-Pressure [ ] Pressurized
[ ]Halon │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
[ ]Halogen Compound │? Storage container installation location: [ ] Above ground/[ ] Underground ( )Floor, [ ]Exclusive Room [ ]Other( )
and inert gas │ Quantity: ( )[ ]㎏,[ ]㎥ ( )ℓ ( )dog
[ ]Powder │? Fire Extinguishing Agent [ ] Carbon Dioxide [ ] Halon 1301 [ ] Halon 2402 [ ] Halon 1211 [ ] Halon 104
[ ] Wet Chemical Extinguishing Agent │ [ ]FC-3-1-10 [ ]HCFC BLEND A [ ]HCFC-124 [ ]HFC-125 [ ]HFC-227ea
[ ]Solid Aerosol │ [ ]HFC-23 [ ]IG-541 [ ]IG-100 [ ] Others( )
│ [ ]Type 1 Powder [ ]Type 2 Powder [ ]Type 3 Powder [ ]Type 4 Powder
─────────┴────────────────────────────────────────────
(Page 6 of 8)
3-5. Alarm System
────────┬─────────────────────────────────────────────────
[ ] Standalone Alarm Type│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
Detector │? Main Power [ ] Commercial Power [ ] Battery
────────┼─────────────────────────────────────────────────
[ ] Emergency Alarm │[ ]Emergency Bell System [ ]Automatic Siren System
equipment │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Control device installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )Floor Real Name( )
────────┼─────────────────────────────────────────────────
[ ] Automatic Fire │? Receiver Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )Floor Real Name( )
Detection System │? Alarm Type [ ] All-floor Alarm [ ] Priority Alarm, Visual Alarm [ ] Yes [ ] No
│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
│ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Detector Type [ ] Heat [ ] Smoke [ ] Other ([ ] Flame [ ] Analog [ ] Combined)
────────┼─────────────────────────────────────────────────
[ ] Fire Alarm │? Receiver Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )Floor Real Name( )
Equipment │? Alarm Type [ ] All-floor Alarm [ ] Priority Alarm, Visual Alarm [ ] Yes [ ] No
│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
│ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Detector Type [ ] Heat [ ] Smoke [ ] Other ([ ] Flame [ ] Analog [ ] Combined)
────────┼─────────────────────────────────────────────────
[ ] Emergency Broadcast │[ ] Dedicated [ ] Dual Use / [ ] All-floor Alarm [ ] Priority Alarm
Equipment │? Amplifier Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
────────┼─────────────────────────────────────────────────
[ ] Integrated Monitoring │? Main receiver installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
Facilities │? Subsidiary receiver installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│? Information and Communications Network [ ] Optical Cable [ ] Others( ) / Reserve Line [ ] Yes [ ] No
────────┼─────────────────────────────────────────────────
[ ] Automatic Fire │? Alarm detector installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
Fire Notification System │
────────┼─────────────────────────────────────────────────
[ ] Leakage Alarm│? Receiver Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│? Receiver Type [ ]Class 1 [ ]Class 2, Circuit Breaker [ ]None [ ]Yes(Installation Location: )
────────┼─────────────────────────────────────────────────
[ ] Gas Leak │? [ ] Standalone type [ ] Separated type, Type of gas used [ ]LNG [ ]LPG, Number of boundary zones: ( )dog
Alarm │? Receiver Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( ) Floor, Room Name ( )
│? Circuit breaker [ ] None [ ] Yes(Installation location: )
────────┴─────────────────────────────────────────────────
3-6. Evacuation and Rescue Facilities
────────┬─────────────────────────────────────────────────
[ ] Evacuation Equipment │? Type: [ ]Escape Ladder [ ]Descent Device [ ]Multi-person Evacuation Equipment [ ]Elevator-type Evacuation Device [ ]Slide
│[ ] Evacuation Bridge [ ] Evacuation Trap [ ] Rescue Chute [ ] Simple Descent Device [ ] Air Safety Mat
│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
│ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
────────┼─────────────────────────────────────────────────
[ ] Life Rescue │? Type: [ ] Heat-resistant suit / Fire-resistant suit [ ] Self-contained breathing apparatus [ ] Artificial resuscitation
Mechanism │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
│ Building Name ( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floors ~ [ ]Ground Floor/[ ]Basement( )Floors
│? Object Usage: [ ] Hospital with 5 or more floors [ ] Tourist Hotels with 7 or More Floors [ ] Installation of Carbon Dioxide Fire Extinguishing Systems
│[ ] Underground Stations·Department Stores·Large Stores·Shopping Centers·Underground Shopping Malls·Movie Theaters
────────┼─────────────────────────────────────────────────
[ ] Guide light │? Type: [ ] Exit Light [ ] Corridor Light [ ] Auditorium Exit Light [ ] Exit Sign [ ] Evacuation Guidance Line
│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
────────┼─────────────────────────────────────────────────
[ ] Emergency Lighting│? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Emergency Power [ ] Self-generating Power System [ ] Battery System [ ] Built-in Type
────────┼─────────────────────────────────────────────────
[ ] Portable │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
Emergency Lighting │? Power [ ]Battery type [ ]Rechargeable Battery type
────────┴─────────────────────────────────────────────────
3-7. Firefighting Water Supply Equipment
────────┬─────────────────────────────────────────────────
[ ] Water Supply │? Installation Location:( ), Fire hydrant nominal diameter: ( )㎜
Firefighting Water │
────────┼─────────────────────────────────────────────────
[ ] Firefighting Water Tank │[ ] Dedicated [ ] Dual-use/[ ] Absorption type [ ] Pressurized type/[ ] General tank [ ] Others/Effective water volume:( )㎥
│? Pressurized water supply device Total Head: ( )m, discharge amount:( )ℓ/min, [ ]Electric Motor/[ ]Internal Combustion Engine(Fuel:[ ]Diesel [ ]Others)
│? [ ] Water priming device effective water quantity: ( )ℓ, water supply piping: ( )㎜
│? Start switch installation location: [ ] Near water intake [ ] Fire control room [ ] Other( )
│? Water intake diameter: ( ) mm, Suction Pipe Inlet: Width ( ) cm, Height ( )cm/diameter ( )㎝
────────┴─────────────────────────────────────────────────
(Page 7 of 8)
3-8. Firefighting Activity Facilities
───┬───┬────────────────────────────────────────────
[ ] │[ ] │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
Smoke Control│Living Room │? Method: [ ] Independent [ ] Joint [ ] Interconnected [ ] Other ( )
Equipment│ │? Activation Device [ ]Automatic (Detector Interlock) [ ]Manual [ ]Remote
│ │? Maximum Smoke Control Zone Area: ( ) m² / Structure [ ] Fire-Resistant [ ] Non-combustible [ ] Other: )
│ │Smoke Control Area Door [ ] Normally Closed (Automatic Closing Device) [ ] Normally Open (Closed by Detector)
│ │? Supply Air Blower Location: Building Name ( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ │ Motor ( )㎾, air volume ( )㎥/min, static pressure ( )㎜Aq
│ │? Exhaust Blower Location: Building Name ( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ │ Motor ( )㎾, air volume ( )㎥/min, static pressure ( )㎜Aq
│ │? Outlet [ ] Ceiling surface [ ] Directly below ceiling [ ] Other( ) / Outdoor Outlet [ ] Rooftop [ ] Other( )
│ │ Duct Structure [ ] Fire-Resistant [ ] Noncombustible [ ] Other ( ) / Fire Compartment Damper [ ] Present [ ] Absent
│ │? Intake Air Exhaust [ ] Natural Exhaust [ ] Mechanical Exhaust [ ] Exhaust Port [ ] Smoke Control System
│ │? Supply Inlet [ ] Forced Inflow [ ] Natural Inflow [ ] Adjacent Zone Inflow
│ │ Duct Structure [ ] Fire-Resistant [ ] Noncombustible [ ] Other ( ) / Fire Compartment Damper [ ] Present [ ] Absent
├───┼────────────────────────────────────────────
│[ ] │? Installation Target: Building Name ( , , , , )
│Anteroom │ Special Evacuation Stairs ( ) locations, emergency elevators ( )to
│ │? Method [ ] Annex [ ] Stairwell and Annex [ ] Stairwell [ ] Emergency Elevator Landing
│ │? Starting Method [ ] All Floors [ ] Partial Floors( floors) / Damper-Open Detector [ ] Dedicated [ ] Combined Use
│ │? Supply air blower installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ │ Motor ( )㎾, air volume ( )㎥/min, static pressure ( )㎜Aq
│ │? Exhaust Blower Location: Building Name ( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ │ Motor ( )㎾, air volume ( )㎥/min, static pressure ( )㎜Aq
│ │Smoke Control Area Door [ ] Normally Closed (Automatic Closing Device) [ ] Normally Open (Closed by Smoke Detector)
│ │? Intake Air Exhaust [ ] Natural Exhaust [ ] Mechanical Exhaust [ ] Exhaust Port [ ] Smoke Control System
│ │? Overpressure Prevention Device [ ] Flap Damper [ ] Automatic Differential Pressure Damper (Overpressure-Regulating Type) [ ] Other [ ] N/A
───┴──┬┴────────────────────────────────────────────
[ ]Connect │[ ] Dedicated [ ] Dual-use([ ] Indoor fire hydrant system [ ] Sprinkler system [ ] Others: )
Water Pipe │? Installation Location: Dongmyeong( ) [ ]All Floors/[ ]Some Floors [ ]Ground Floor/[ ]Basement( )Floor ~ [ ]Ground Floor/[ ]Basement( )Floor
│? Hose Outlet Location [ ] Corridor/Passage [ ] Stairwell [ ] Near Stairs, etc.
│? Fire Department Connection Inlet Location: ( ), Intermediate Water Tank Capacity: ( )㎥
│? Pressurized water supply device installation location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )floor, real name( )
│ Total Head: ( )m, discharge volume:( )ℓ/min
│ [ ] Electric Motor [ ] Internal Combustion Engine(Fuel:[ ] Diesel [ ] Others
│? Start Switch Installation Location [ ] Water Supply Inlet [ ] Fire Control Room [ ] Other( )
──────┼─────────────────────────────────────────────
[ ]Connect │? Installation Target: Building Name ( , , , , )
Spray │? Method [ ] Wet [ ] Dry / [ ] Basement [ ] Sales Facilities [ ] Gas Facilities [ ] Attached Connecting Passage
│? Fire Department Connection Inlet Location: ( ), Number of Water Supply Zones: ( )Area
──────┼─────────────────────────────────────────────
[ ]Emergency │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )Floor ~ [ ]Ground/[ ]Underground ( )floor
Outlet │[ ] 3-phase 380V [ ] Single-phase 220V / [ ] Grounded 2-pole plug connector [ ] Grounded 3-pole plug connector
──────┼─────────────────────────────────────────────
[ ]Wireless │? Installation Location: Dongmyeong( ) [ ]Aboveground/[ ]Underground ( )Floor ~ [ ]Ground/[ ]Underground ( )floor
CommunicationAid │[ ]Dedicated [ ]General / Method: [ ]Leaky Coaxial Cable [ ]Leaky Coaxial Cable and Antenna [ ]Antenna
│? Connection terminal installation location( ), ( )
──────┼─────────────────────────────────────────────
[ ]Combustion │? Objects of Protection [ ] For Electric Power Business [ ] For Telecommunications Business [ ] Others( )
Prevention │? Number of Water Supply Zones: ( ) Zones / Separation Between Zones [ ] Full [ ] Partial [ ] None
──────┼─────────────────────────────────────────────
Remarks │※ When describing the smoke control system, enter details for the zone having the largest area.
──────┴─────────────────────────────────────────────
(Page 8 of 8)
4. Details on Defects in Firefighting Facilities, etc.
───────┬────┬─────────────────────────────
equipment name │Inspection Item Number│Defect Details
───────┼────┼─────────────────────────────
FireExtinguishingSystem │ │
───────┼────┼─────────────────────────────
Alarm System │ │
───────┼────┼─────────────────────────────
Evacuation and Rescue Equipment│ │
───────┼────┼─────────────────────────────
Fire extinguishing water supply system│ │
───────┼────┼─────────────────────────────
Firefighting Activity Equipment│ │
───────┼────┼─────────────────────────────
Other │ │
━━━━━━━┿━━━━┿━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
Safety facilities, etc. │ │
───────┼────┴─────────────────────────────
Remarks │ For the inspection number, enter the number for each inspection item on the self-inspection checklist for fire fighting facilities, etc. .
───────┴──────────────────────────────────
(Page 9)
How to write
━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
※ This form is entered into a computer system, so please fill it out accurately and clearly using Korean characters or Arabic numerals.
※ When reporting inspection results for multiple targets inspected within the same period,
record and report them together on one form.
※ [ ], mark the relevant facility with a √ and enter the detailed status and installed quantity.
※ In preparing '3. Detailed Status of Firefighting Facilities, etc.,' enter only facilities installed in the relevant premises;
if many facilities are installed and the space is insufficient, additional pages may be added, and fields for facilities that are
not installed may be deleted (without changing the order of the facilities).
※ In the event that inspections could not be performed on any equipment due to unavoidable reasons, the
Write the relevant content in the 'Other' section.
1. “Name of specific fire safety target” refers to the building name, and “Classification of target” refers to the 「Enforcement Decree of the Act on Installation and Management of Firefighting Facilities」
For the classification of specific fire safety targets according to Attached Table 2, enter the road name address of the specific fire safety target for “Location.”
2. “Inspection period” refers to the entire period during which self-inspections of fire safety facilities, etc. were conducted, and the sum of the number of days actually inspected during the period
Enter in “Total Inspection Days”.
3. Under 'Inspector,' mark √ next to the responsible person, fire safety manager, or registered fire facility management provider who conducted the inspection, and enter
the details. Where consent is given to electronic service of documents, advance notices and orders to take corrective measures for defects
identified by inspection shall be served through an information and communications network instead of by post.
4. List all lead and assistant inspection personnel separately. Where additional assistant personnel are assigned under
item 1(a) or 1(b) of Annex 4 to the Enforcement Rules of the Act on the Installation and Management of Firefighting Facilities,
Additional auxiliary inspection personnel must also be listed.
5. Where a fire facility management provider has conducted an inspection, that provider shall, within 10 days from the date of completion,
submit the inspection results report to the responsible person with the inspection checklist designated and publicly notified by the Commissioner of the National Fire Agency.
6. When a responsible person receives the provider's inspection results or conducts the inspection directly, that person shall,
within 15 days after completion of inspection, prepare and attach an implementation plan (Form No. 10) for the inspection results and report
it in writing or via the electronic system designated by the Commissioner of the National Fire Agency to the competent head of fire headquarters or fire station. If a power of attorney is attached,
the fire facility management provider may submit the report on the person's behalf.
7. The representative of the “Fire Safety Information” shall fill out the personal details of the relevant person with management authority over the specific fire-protected building, and fire
The safety management grade shall indicate the grade pursuant to Annex 4 of the Enforcement Decree of the Act on the Prevention of Fire and Safety Management, and currently
Enter the information of the appointed fire safety manager.
8. Under 'Fire Safety Plan,' 'Self-Inspection (Previous Year)' and 'Education and Training (Previous Year),' enter
details of fire safety management duties performed under Article 24 of the Act on Fire Prevention and Safety Management.
9. If the premises are covered by fire insurance, mark the insured box under 'Fire Insurance' and
enter the policy information.
10. Under 'Status of Multi-Use Establishments,' for those currently occupying the premises, place a √ in the appropriate box and
enter the number of establishments; under 'Building Information,' enter building details such as the date of building permit.
Where two or more buildings were inspected within the same period and reported together, record the multi-use establishments by building
and the building information as follows.
────────────────────────────────────────────────────────
(Page 10)
━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
─────┬─────────────────────────────────────────
Multi-use│Building A
Business Status│[√]Rest Area Food Service Business ( 2 locations) [√]Game Provider( 1 location) [√]General Restaurant Business ( 1 location)
├─────────────────────────────────────────
│Building B
│[ ]Not applicable
├─────────────────────────────────────────
│Building C [√]Bakery Business ( 1 location) [√]General Restaurant Business ( 3 locations)
│[√]Rest Area Food Service Business ( 1 location) [√]Singing Practice Room Business ( 1 location) [√]Movie Theater( 1 location)
─────┴─────────────────────────────────────────
──────┬───────────────┬─────┬───────────────
Building Permit Date│Building A 2005 April 1day │Date of Approval│Building A 2006 April 1day
│Building B 2007 May 1day │ │Building B 2008 May 1day
──────┼───────────────┼─────┼───────────────
Total Area │Building A 20,000 ㎡ │Building Area │Building A 5,000 ㎡
(Number of households) │Building B 10,000 ㎡ │ │Building B 3,000 ㎡
──────┼───────────────┼─────┼───────────────
floor 수 │Building A Ground 5 Floors / Basement 2 Floors│high This │Building A 20m, Building B 15m
│Building B Ground 4 Floors / Basement 1 Floor│ │
──────┼───────────────┴─────┴───────────────
Building Structure│Building A [√] Concrete Structure; Building B [√] Steel Structure or Buildings A and B [√] Concrete Structure
──────┼─────────────────────┬───┬───────────
Roof Structure │Building A [√] Slab; Building B [√] Other │Ramp│Building A: 1 Location; Building B: 2 Locations
│ or Buildings A and B [√] Slab │ │or 1 Location Each in Buildings A and B
──────┼─────────────────────┴───┴───────────
Total 단 │Building A [√] Direct (or Evacuation) Stairs (1 Location), [√] Special Evacuation Stairs (1 Location)
│Building B [√] Direct (or Evacuation) Stairs (2 Locations)
──────┼─────────────────────────────────────
Elevators │Building A [√] Passenger Elevator ( 1 Unit), Not Applicable to Building B or Buildings A and B Each [√] Passenger Elevator ( 1 Unit)
──────┼─────────────────────────────────────
Parking Lot │Building A [√] Indoor ([√] Underground [ ]Ground [ ]Piloti [ ] Mechanical); Building B [√]Outdoor
│or Buildings A and B [√] Indoor ([√] Underground [ ]Ground [ ]Piloti [ ]Mechanical)
──────┴─────────────────────────────────────
* “Number of Households” is to be written together with the gross floor area only in the case of multi-unit housing.
11. The method for preparing the “Detailed Status of Firefighting Facilities, etc.” shall follow the method determined and notified by the Commissioner of the National Fire Agency.
12. “Detailed items regarding defects in fire fighting facilities, etc.” shall be prepared for each piece of equipment in the order of inspection number, provided that for two or more objects, the same
If inspections are conducted within the period and reported together, they may be prepared by building or by facility as follows
.
─────┬────┬───────────────
equipment name │Inspection Item Number│Defect Details
─────┼────┼───────────────
FireExtinguishingSystem│1-A-007 │Building A: 3 Powder Fire Extinguishers with Defective Pressure
│ │Building B: 4 Powder Fire Extinguishers with Defective Pressure
│ │Building C: 5 Powder Fire Extinguishers with Defective Pressure
─────┴────┴───────────────
─────┬────┬───────────────────────────
equipment name │Inspection Item Number│Defect Details
─────┼────┼───────────────────────────
FireExtinguishingSystem│1-A-007 │12 Powder Fire Extinguishers with Defective Pressure (Building A: 3; Building B: 4; Building C: 5)
─────┴────┴───────────────────────────
────────────────────────────────────────────────────