ENFORCEMENT DECREE OF THE FIRE SERVICES ACT
10448 · 1998-01-01
ENFORCEMENT DECREE OF THE FIRE SERVICES ACT
Presidential Decree No. 15581, Dec. 31, 1997
Wholly Amended by Presidential Decree No. 13701, Jul. 28, 1992
Amended by Presidential Decree No. 14334, Jul. 20, 1994
Presidential Decree No. 14446, Dec. 23, 1994
Presidential Decree No. 14747, Aug. 10, 1995
Presidential Decree No. 15389, Jun. 11, 1997
Presidential Decree No. 15485, Sep. 27, 1997
Presidential Decree No. 15598, Dec. 31, 1997
Presidential Decree No. 15581, Dec. 31, 1997
CHAPTER Ⅰ GENERAL PROVISIONS
법령보기 화면
Article 1 (Purpose)
The purpose of this Decree is to provide for matters delegated in the
Fire Services Act
(hereinafter referred to as the “Act”) and necessary matters regarding its enforcement.
법령보기 화면
Article 2 (Definitions)
For the purpose of this Decree, the definitions of terms used in this Decree shall be as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
1.
The term “floor area” means the floor area calculated as referred to in
Article 119 (1) 3 of the Enforcement Decree of the Building Act
;
2.
The term “total floor area” means the sum of the floor area;
2-2. The term “number of floors” means the calculated number as referred to in
Article 119 (1) 9 of the Enforcement Decree of the Building Act
;
3.
The term “underground floor” means the underground floor as referred to in subparagraph 4 of
Article 2 of the Building Act
; and
4.
The term “windowless floor” means above-ground floors where the sum of the area of the opening falling under one of the followings is not more than one-thirtieth of the floor area of that floor:
(a)
The size of the opening shall be able to inscribe a circle of not less than fifty centimeters in diameter;
(b)
The height from the floor to the bottom of the opening of that floor shall be not more than 1.2 meters;
(c)
It shall face a road or an open space allowing entry of automobiles;
(d)
Window safety bars or other obstacles shall not be installed to ensure easy evacuation from the building in case of fire; and
(e)
It shall be prone to easy destruction and opening from either the outside or the inside;
5.
The term “evacuation floor” means a floor having an entrance and exit door leading directly to the ground level;
6.
The term “main structural parts” means the main structural parts as referred to in subparagraph 6 of
Article 2 of the Building Act
;
7.
The term “fire proof structure” means a fire proof structure as referred to in subparagraph 7 of
Article 2 of the Building Act
;
8.
The term “fire prevention structure” means a fire prevention structure as referred to in subparagraph 8 of
Article 2 of the Enforcement Decree of the Building Act
;
9.
The term “ incombustible materials” means the incombustible materials as referred to in subparagraph 8 of
Article 2 of the Building Act
;
10.
The term “semi-incombustible materials” means semi-incombustible materials as referred to in subparagraph 11 of
Article 2 of the Enforcement Decree of the Building Act
; and
11.
The term “noncombustible materials” means noncombustible materials as referred to in subparagraph 9 of
Article 2 of the Enforcement Decree of the Building Act
.
CHAPTER Ⅱ PREVENTION OF FIRE
법령보기 화면
Article 3 (Special Areas)
Special areas as referred to in subparagraph 5 of the
Fire Services Act
are in Appendix 1.
법령보기 화면
Article 4 (Range of Object for Approval of Construction Permit, etc.)
(1)
The range of the object for approval of the construction permit and usage approval as referred to in
Article 8 (2) of the Act
are as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995>
1.
In buildings that shall be granted permission, special areas falling under any of the following (including consultation or approval as provided in
Article 25, (1) of the Building Act
and
Article 33 of the Housing Construction Promotion Act
and notification as provided in Article 5-2 (2) or (3) School Facilities Projection Promotion Act are included) as referred to in
Article 8 of the Building Act
:
(a)
Those which are not less than 400 square meters in total floor area;
(b)
A garage, parking place, or a similar facility which does not fall under preceding clause (a) but falls under any of the following:
(ⅰ)
Those having a floor with a floor area of not less than 200 square meters among the floors used as a garage or a parking place; and
(ⅱ)
A parking facility with machine equipment such as an elevator etc., which can park not less than 20 cars;
(c)
Airplane hangars which do not fall under preceding clause (a);
(d)
Hazardous materials manufacturing places or handling places (including manufacturing, storing and transporting facilities. Hereinafter referred to as “manufacturers, etc.”) which do not fall under preceding clause (a); and
(e)
Those which do not fall under preceding clauses (a) through (d) inclusive, and have a floor with a floor area of not less than 150 square meters (not less than 100 square meters in the case of performance halls) among the underground floors or the windowless floors;
2.
Gas facilities falling under the Appendix 1; and
3.
Underground entrances falling under the Appendix 1 (except those constructed in buildings as referred to in subparagraph 1).
(2)
In a case where the administrative agency, having the authority of the construction permits or approval of use under
Article 8 (1) of the Act
, requests the consent of the permission or the approval of use from the chief of fire headquarters or the chief of fire station (hereinafter referred to as the “chief of fire station”), a request form shall be submitted with all the forms prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(3)
In cases where the fire fighting property falls under any of the following and is applicable to the fire safety systems standards, notwithstanding the provisions of paragraph (1), consent shall not be granted by the chief of fire station:
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
1.
Fire fighting property among that falling under paragraph (1) 1 (a) and (e) with a total floor area of less than 1000 square meters equipped only with fire extinguishing equipments, emergency alarm systems, emergency ground fault alarm devices, evacuation equipment, rescue equipment, emergency exit lights, or emergency exit signs under the
Articles 28
(1),
29
(1) and (3), and
30
(1) through (3) inclusive ; and
2.
Fire fighting property without having alteration to the fire safety systems when alternating its purpose of use or a property that has only minor construction prescribed by the Ministerial Decree of Home Affairs.
(4)
The notification period of consent for the construction permission and approval of use as referred to in
Article 8 (3) of the Act
shall be within 2 days.
<Added by Presidential Decree No. 14747, Aug. 10, 1995>
법령보기 화면
Article 4-2 (Scope of Multi-Usage Businesses)
For the purpose of
Article 8-2 (1) of the Act
, the term “businesses as prescribed by the Presidential Decree” means the following businesses (hereinafter referred to as the “multi-usage businesses”):
1.
The businesses, among general restaurants established on underground floors, of which the total floor area used for business is not less than 66 square meters, singing practice studios, video cafes, singing and pub parlors or amusement parlors; and
2.
The businesses, among those similar to the businesses as referred to in subparagraph 1, where a fire is likely to break out or a fire, if any, is likely to be accompanied by any injury to life, as determined by the Ministerial Decree of Home Affairs after consultation by the Minister of Home Affairs with the head of the central administrative agency taking charge of the affairs of permission, license, registration, or report for such businesses.
[This Article Added by Presidential Decree No. 15485, Sep. 27, 1997]
법령보기 화면
Article 4-3 (Types of Fire Fighting and Fire Protection Facilities, etc.)
The types of fire fighting and fire protection facilities as referred to in
Article 8-2 (1) of the Act
shall be as follows:
1.
Fire fighting facilities:
(a)
Fire fighting equipment: fire extinguishers (manual or automatic), handy portable fire extinguishing tools using fire extinguishing agents, and simple sprinkler equipment;
(b)
Evacuation equipment: guiding lights and guiding signs, emergency lights, and escape hatches; and
(c)
Alarm equipment: emergency bell equipment, emergency broadcasting equipment, and gas leakage alarm;
2.
Fire protection facilities: fire doors, and emergency exit (emergency escape exit); and
3.
Other facilities: Image and sound circuit breaker, earth leakage circuit breaker, and fire route.
[This Article Added by Presidential Decree No. 15485, Sep. 27, 1997]
법령보기 화면
Article 5 (Fire Safety Inspections, etc.)
(1)
The chief of fire station shall make a monthly and yearly plan for the purpose of conducting a general inspection of the fire safety as referred to in
Article 5 or 69 (2) of the Act
and the hazardous materials manufacturing places as referred to in
Article 24 (1) of the Act
, and shall conduct inspections accordingly to these plans.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(2)
In cases there are not less than two fire fighting properties in the same district or the property is a building complexes when conducting the fire safety inspection as referred to in paragraph (1), the inspections shall be conducted simultaneously.
(3)
A person conducting the inspection as referred to in paragraph (1) shall record the inspection results on a form prescribed by the Ministerial Decree of Home Affairs, sign or seal it, and distribute one copy without delay to the persons concerned of the fire fighting property.
(4)
The qualifications of an inspector, types of inspection, matters to be inspected, method and frequency of inspections as referred to in paragraph (1) shall be prescribed by the Ministerial Decree of Home Affairs.
법령보기 화면
Article 5-2 (Special Areas in which Fire Drill and Education shall be Conducted)
Special areas in which fire drill and education shall be conducted as referred to in
Article 8-3 of the Act
shall be special areas where a fire safety manager should be appointed under
Article 6
:
Provided
, That this shall not apply in special areas where there are not more than ten persons regularly working or living (in case of lodging facilities other than an officetel, referring only to regular working persons).
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 6 (Special Area in which Fire Safety Managers shall be Appointed)
Special areas in which fire safety managers (including joint fire safety managers under
Article 10 (1) of the Act
; hereinafter, the same shall apply) shall be appointed under
Article 9 (1) of the Act
shall be divided into first class fire fighting property for fire safety management and second class fire fighting property for fire safety management as in the Appendix 2.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 7 (More than Two Special Areas in Same Place)
In cases where there are more than two special areas as referred to in
Article 6
in the same place and the person having authority over their fire safety management is the same, they shall be considered as one special area in the application of
Article 6
, but in cases where the classes of the fire fighting properties are different the higher class shall apply.
법령보기 화면
Article 8 (Special Area in which Joint Fire Safety Management shall be Conducted)
For the purpose of
Article 10 (1) 3 of the Act
, the term “other fire fighting property prescribed by the Presidential Decree” means building complex in the Appendix 1 with a total floor area of not less than 5,000 square meters or with not less than five floors, and markets.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
법령보기 화면
Article 9 (Appointment of Fire Safety Manager)
(1)
The fire safety manager who shall be appointed for the first class objects for fire safety management in the Appendix 2 under
Article 6
shall be appointed from persons falling under any of the following subparagraphs:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Persons with a fire safety systems manager license or fire safety systems engineer license;
2.
Persons with a first class industrial safety engineer license who have not less than two years of working experience related to fire prevention control;
3.
A hazardous materials handling professional technician, or persons with hazardous materials handling technician who are appointed as a hazardous materials safety manager (limited to the manufacturing places as referred to in
Article 23
(1));
4.
Persons appointed as the person in charge of safety management (hereinafter referred to as “gas-related safety manager”) as referred to in
Article 11 (1) of the Enforcement Decree of the High-Pressure Gas Safety Control Act
, Article 7 (1) of the Enforcement Decree of the Safety Control and Business Regulation of Liquified Petroleum Gas Act, or Article 24 (1) of the Enforcement Decree of Urban Gas Business Act (limited to facilities storing or handling not less than one thousand tons of combustible gas);
5.
Persons having work experience of not less than five years as a fire service official;
6.
Persons who have not less than two years of actual work experience related to fire safety management and have majored in fire safety management and have graduated from a technical college or an educational institution the same as or higher than this;
7.
Persons who have more than three years of actual work experience related to fire safety management and have completed not less than twelve credits of course work in fire safety management related classes and graduated from a four-year university or above, or have graduated majoring in a field related to fire safety management; and
8.
Persons falling under paragraph (2) 3, 5 or 8 through 12 inclusive and having completed the course prescribed by the Ministerial Decree of Home Affairs and recognized their qualifications among the persons having not less than 5 years work experience related to fire safety management determined and notified by the Minister of Home Affairs.
(2)
The fire safety manager who are supposed to be at the second class fire safety objects of the Appendix 2 under
Article 6
shall be appointed from the persons falling under any of the following subparagraphs:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Deleted;
<by Presidential Decree No. 14334, Jul. 20, 1994>
2.
Persons having qualifications as industrial safety engineers, architectural engineer, or electrical engineers, or persons appointed as responsible for gas-related safety control (limited to facilities storing or handling not less than 100 tons and less than 1000 tons of combustible gas);
3.
Persons having qualifications as hazardous materials handling technicians;
4.
Persons appointed as security inspector having qualifications as mine security engineers;
5.
Persons having completed the course related to fire safety control management prescribed by the Ministerial Decree of Home Affairs;
6.
Persons having majored in fire safety management and graduated from a technical college or any educational institution which is equivalent to the college or above;
7.
Persons having taken more than six credit hours of course work in fire safety management related courses and graduated from four year college or educational institutions higher than this, or who have majored in a field related to fire safety management and graduated the four year college;
8.
Persons having work experience of not less than one year as a fire service officials.
8-2. Persons having work experience of more than one year in fire suppression or assistance work at a fire headquarters or a fire station;
9.
Persons having work experience of not less than five years as volunteer fire fighters or private fire fighters;
9-2. Persons having work experience of not less than two years as fire fighters in military units (including foreign military units in Korea);
10.
Persons having work experience of not less than five years as fire fighters of a self fire fighting unit as referred to in
Article 23 of the Act
;
11.
Persons having work experience of not less than three years in the safety inspection business employed as a security guard under Article 7 of the Enforcement Decree of the Presidential Security Service Act;
12.
Persons having work experience of not less than five years as a police official; and
13.
Persons falling under any of the subparagraphs of paragraph (1).
(3)
In special areas determined and noticed publicly by the State, local government, or the Minister of Home Affaires notwithstanding paragraphs (1) and (2) used by a government agency for public purposes or for official purpose, a person having managing or supervising status shall be appointed as the fire safety manager. In such cases, the appointment of the fire safety manager may be replaced by designating the status.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995>
(4)
For the purpose of the text of paragraph (3), the term “persons having management or supervision status” means persons actually in charge of the management of the special area.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995>
(5)
In cases where the person concerned in special areas permitted a registered person of the fire protection systems inspection business to conduct fire prevention control responsibilities under
Article 33 of the Act
, he may appoint a person among the staff assigned to the special area, notwithstanding the preceding paragraphs (1) and (2), who is able to supervise the fire prevention control business executed by the fire protection systems inspection businessman as a fire safety manager.
<Added by Presidential Decree No. 14747, Aug. 10, 1995>
(6)
The fire safety related courses and the fire safety-related college majors as referred to in paragraphs (1) 7 and (2) 7 shall be prescribed and noticed publicly by the Minister of Home Affairs, and matters necessary for determining fees to submitted by persons desiring to receive recognition of qualification or ways to give lectures, duration, course subject and the lecture itself as referred to in paragraphs (1) 8 and (2) 5 shall be determined by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
법령보기 화면
Article 10 (Fire Safety Plan)
(1)
The fire safety plan as referred to in
Article 9 (2) 1 of the Act
shall include the following matters:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995>
1.
Self-inspection plan for the purpose of fire prevention;
2.
Check-up and maintenance plan for the fire fighting facilities according to the type of fire fighting property;
3.
Evacuation plan (including the location of the evacuation floor, the location of the safety compartment, the location of evacuation equipment and the designation of the evacuation route);
4.
The maintenance and management plan for the fireproof section, the fire control section, the fire resistant interior finish (this means the interior finishing material made of incombustible material, semiincombustible material or noncombustible material as referred to subparagraphs 9 through 11 inclusive in
Article 2
), and flame retardant and other fire protection structures and equipment;
5.
Matters pertaining to the storing or handling of hazardous materials (except for the manufacture, etc., whose safety provisions are referred to in
Article 22 of the Act
);
6.
The plan for accommodating persons;
7.
Fire drill and education plan (limited to the special areas where fire drill and education shall be conducted under
Article 5-2
;
8.
Matters pertaining to the organization of the private fire fighting unit and the duties of its members (limited to special areas where fire drill and education shall be conducted under
Article 5-2
;
9.
Deleted;
<by Presidential Decree No. 14334, Jul. 20, 1994>
10.
With regard to the fire fighting property under construction such as extension, improvement, rebuilding, relocation, or large-scale repairs, matters pertaining to the fire safety management of the construction site;
11.
Matters pertaining to the division of fire safety management responsibilities (limited to cases of not less than two special areas within the same area); and
12.
Other matters ordered by the chief of fire station of the relevant jurisdiction.
(2)
The self-inspection plan as referred to in paragraph (1) 1 shall include inspection plans for the following matters:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
1.
The structure, purpose of use, fire safety system, evacuation notification systems, evacuation exits, safety section, fireproof section, fire-control section, fire protection interior and property subject to flame retardant treatment;
2.
The location and structure of the manufacture, etc., fire safety systems, and the manufacturing, storing and handling situations of hazardous materials (except for manufacturers, etc., whose fire prevention regulations are prescribed as referred to in
Article 22 of the Act
);
3.
Matters pertaining to the training of the private fire safety unit or self-organized private fire brigade; and
4.
Other matters necessary for the prevention of fire, extinguishing of fire, and prevention of combustion.
(3)
The chief of fire station shall give guidance with respect to the making of the fire safety plan and its execution.
(4)
The manufacturers, etc., where the fire prevention regulations should be made under
Article 22 of the Act
may have the fire safety plan as referred to in paragraph (1) included in its regulations.
법령보기 화면
Article 11 (Flame Retardant in Special Areas)
(1)
For the purpose of
Article 11 (1) of the Act
, the term “special areas prescribed by the Presidential Decree” means special areas as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Buildings except apartments, that have not less than eleven floors;
2.
Massage parlors, health clubs, special baths, viewing assembly and sports facilities (limited to the interior of buildings, with the exception of swimming pools), hotels among general lodging facilities, tourist lodging facilities, general hospitals, broadcasting stations, film studios and exhibition galleries;
3.
Inns established in buildings of not less than three floors and having not less than thirty rooms;
4.
Multi-usage businesses as referred to in
Article 4-2
; and
5.
Deleted.
<by Presidential Decree No. 14747, Aug. 10, 1995>
(2)
For the purpose of
Article 11 (1) of the Act
, the term “materials prescribed by the Presidential Decree” means the things as follows:
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
1.
Curtains (referring to curtains, dark curtains, stage curtains, and curtains used for partition, made mainly of paper, synthetic resin, or fibers, which are installed in the interior of a room such as windows or walls, etc.);
2.
Interior decorations (referring to articles made mainly of paper,
synthetic resin or fibers, and plywood or wood, which are adhered to or established on the decorated interior of buildings as referred to in
Article 61 of the Enforcement Decree of the Building Act
:
Provided
, That wall paper shall be excluded);
3.
Carpets; and
4.
Plywood used as partition plates (including that used for simple partition plates), plywood or fiberboards for use in exhibition halls, and plywood or fiberboards used as scenery.
(3)
The standard of the fire retardant capability as referred to in
Article 11 (2) of the Act
shall be determined and notified by the Minister of Home Affairs according to the type of things within the numerical value of the following figures:
1.
Within twenty seconds from the moment the flame of the burner is removed until the moment the flame is applied and the burning goes out;
2.
Within thirty seconds from the moment the flame of the burner is removed until the moment the flame is not put on and the burning goes out;
3.
The carbonized area is within fifty square centimeters and the carbonized length is within twenty centimeters; and
4.
The number of contacts with the flame being not less than three times until the thing is completely melted by the flame.
(4)
In addition to the fire retardant articles as referred to in paragraph (2), the chief of the competent fire station may recommend the usage of fire retardant products, for bed clothes, kitchen wall paper and vinyl wall paper of which the process for fire retardant is deemed necessary.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(5)
Plywood, wood and fiberboards, among articles as referred to in paragraph (2), which are not processed for fire retardant in the course of manufacturing, may be post-processed for fire retardant at a place where they are installed.
<Added by Presidential Decree No. 15485, Sep. 27, 1997>
CHAPTER Ⅲ HANDLING OF HAZARDOUS MATERIALS
Section 1 Common Provisions
법령보기 화면
Article 12 (Hazardous Materials and Special Combustible Materials)
(1)
For the purpose of
Article 2 (4) of the Act
, the term “things ignitable or flammable prescribed by the Presidential Decree” means items of the Appendix 3.
(2)
For the purpose of
Article 27 of the Act
, the term “other things determined by the Presidential Decree” means the items of the Appendix 4 that spread quickly if a fire arises (hereinafter referred to as “special combustible materials”).
법령보기 화면
Article 13 (Designated Quantities of Hazardous Materials)
The designated quantities of hazardous materials as referred to in
Article 15 (1) of the Act
shall be the quantities prescribed in the Appendix 3.
법령보기 화면
Article 14 (Hazardous Materials Manufacturers, etc.)
(1)
For the purpose of
Article 15 (1) of the Act
, the term “hazardous materials manufacturers, etc.” means places with a chain of facilities (including manufacturing facilities, handling facilities and storage facilities) for the purpose of manufacturing hazardous materials of not less than the designated quantities per day.
(2)
The manufacturing and handling facilities of the hazardous materials as referred to in paragraph (1) mean a chain of facilities established for the use of hazardous materials in working or other manufacturing processes, and the storage facilities of the hazardous materials mean storage facilities as referred to in
Article 16
.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 15 (Hazardous Materials Handling Places)
The hazardous materials handling place as referred to in
Article 15 (1) of the Act
are classified as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Gas stations: Hazardous materials handling establishments directly supplying in the fuel tanks of automobiles or ships or selling to actual consumers the hazardous materials through fixed oil supplying equipment;
2.
Sales handling establishments:
(a)
Petroleum sales handling establishments: A hazardous materials handling establishments constructing storing facilities of hazardous materials (limited to kerosene or diesel gasoline) of less than thirty times the designated quantity (limited to the indoor tank storage facilities or underground tank storage facilities, and the storage capacity shall be less than ten times the designated quantity in the case of indoor tank storage facilities) and for the purpose of selling to actual consumers at the store:
Provided
, That in cases of business by National Agricultural Cooperatives Federation or the Unit Agricultural Cooperative Association and in the case of the area of the
Myeon
not establishing a gas station, the hazardous materials that may be stored or handled are gasoline, kerosine, or diesel gasoline; and
(b)
Special hazardous materials sales handling establishments: A hazardous materials handling establishments constructing storage facilities for hazardous (limited to hazardous materials except gasoline, kerosine or diesel gasoline) of less than five times the designated quantity (in the case of storing the hazardous materials of Category No. 4 or Category No. 6 in the Appendix 3 in underground tank storage facilities, the designated quantity is less than 10 times) and for the purpose of selling to actual consumers at the store;
3.
Tank truck sales handling establishments: Hazardous materials handling establishments conducting sales of hazardous materials through mobility to actual consumers using a tank storage capacity (limited to not more than three kilo liters in storage capacity) with an oil supply valve lubricator the attached by a person with an establishment permit for an gas stationer a petroleum sales handling establishments;
4.
Deleted;
<by Presidential Decree No. 14334, Jul. 20, 1994>
5.
General handling place: A hazardous materials handling place, not falling under the preceding subparagraphs 1 through 3 and being not a hazardous materials manufacturing facility inclusively, with the facility to handle and store hazardous materials of not less than the designated quantity per day for the purpose of using the hazardous materials to produce, process, or clean general goods or of consuming in a burner; and
6.
Storage handling establishments: A hazardous materials handling establishment as referred to in
Article 16
that are handling place not falling under subparagraphs 1 through 3 inclusive and 5 and is not a hazardous materials manufacturers facility.
법령보기 화면
Article 16 (Classification of Storing Facilities)
The storage facilities of hazardous materials as referred to in
Article 15 (1) of the Act
mean facilities storing hazardous materials of not less than the designated quantity (referring to facilities storing hazardous materials of not less than half the designated quantity, in case of tank truck storage facilities), and the storing facilities are classified as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Indoor storing facilities: Storage facilities storing hazardous materials in a storehouse;
2.
Outdoor tank storage facilities: Storage facilities storing hazardous materials in an outdoor tank:
Provided
, That storage facilities of subparagraphs 4 through 6 inclusive are excluded;
3.
Indoor tank storage facilities: Storage facilities storing hazardous materials in indoor tanks:
Provided
, That storage facilities of subparagraphs 4 through 6 inclusive are excluded;
4.
Underground tank storage facilities: Storage facilities storing hazardous materials in tanks buried underground:
Provided
, That storage facilities of subparagraph 5 are excluded;
5.
Handy tank storage facilities: Storage facilities storing hazardous materials in handy tanks;
6.
Tank truck storage facilities: Storage facilities storing hazardous materials in tanks fixed to vehicles (including tow trucks);
7.
Outdoor storage facilities: Storage facilities storing hazardous materials of sulphur among the hazardous materials of Category No. 2 of the Appendix 3, Petroleum No. 2, Petroleum No. 3, Petroleum No. 4 and animal and plant oils among the hazardous materials of Category No. 4, or hazardous materials of Category No. 6:
Provided
, That in the case of bonded areas as referred to in
Article 65 of the Customs Act
, hazardous materials prescribed by the Seoul Special Metropolitan City Mayor, Metropolitan City Mayor, or
Do
governor (hereinafter referred to as “ Mayor/
Do
governor”) in their jurisdictions may be stored;
8.
Ship tank storage facilities : (limited to ships not applicable to
Article 2 (1) of the Ship Safety Act
) Storage facilities of storing hazardous materials in tanks fixed in ships or barge; and
9.
Underground base rock storage facilities: Facilities of storing petroleum, etc. in a storage cave made by the excavating of underground base rocks.
법령보기 화면
Article 17 (Conversion of Hazardous Materials of not less than Two Types)
In case of manufacturing, storing, or handling not less than two types of hazardous materials that are less than the designated quantity in the same place or facility, and in cases where the added total of the quantity of each of the types manufactured, stored, or handled divided by the designated quantity of that item is not less than one, this shall be considered hazardous materials of not less than the designated quantity.
Section 2 Installation Permit, etc., of Manufacture, etc.
법령보기 화면
Article 18 (Installation Permit, etc.)
(1)
Persons desiring to receive a permit to install a manufacturer, etc., as referred to in
Article 16 (1) of the Act
shall submit an application form prescribed by the Ministerial Decree of Home Affairs to the Mayor/
Do
governor having a jurisdiction over the relevant area. The same shall also apply when desiring to obtain an alteration permit.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(2)
Deleted.
<by Presidential Decree No. 14747, Aug. 10, 1995>
(3)
The Mayor/
Do
governor, in cases where, as a result of inspection under
Article 19
on the manufacturer, etc., deems it conform to the facilities standards, shall issue a permit.
법령보기 화면
Article 19 (Inspection of Completion of Construction, etc.)
(1)
Persons desiring to receive an inspection of completion of construction (including inspection of completion of construction for a partial part in case partial use is necessary before completion of construction of the entire facility) for the manufacturers, etc., as referred to in
Article 17 (2) of the Act
shall submit a completion of construction inspection application form prescribed by the Ministerial Decree of Home Affairs to the Mayor/
Do
governor.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(2)
The installer of a manufacturer, etc. having hazardous materials tank shall apply for an inspection of completion of construction as referred to in paragraph (1) after receiving hazardous materials tank safety performance test by the Korea Fire Equipment Inspection Corporation as referred to in
Article 103 of the Act
, or Mayor/
Do
governor under
Article 17 (4) of the Act
or a hazardous materials tank safety performance inspector as referred to in
Article 18 (1) of the Act
prior to installing parts of the tank with pipes and other accessorized equipment on the tank.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(3)
The Mayor/
Do
governor, in cases where the installer of the manufacturer, etc. has obtained the safety performance inspection as referred to in paragraph (2), shall exempt the installer from the entire safety performance inspection.
(4)
The Mayor/
Do
governor, in cases where the manufacturer, etc. is not deemed to meet the facilities standard as a result of the inspection, shall order a corrective action by clearly expressing the reason for it.
법령보기 화면
Article 19-2 (Manufacturer, etc. to Need Request for Inspection)
(1)
For the purpose of the latter part of
Article 17 (2) of the Act
, the term “manufacturer, etc. as prescribed by the Presidential Decree” means a manufacturing place and handling place of manufacturing and handling the hazardous materials of not less than 3000 times the designated quantity per day (excluding the quantity stored in storage facilities as referred to in
Article 16
).
(2)
In case where the Mayor/
Do
governor requests the inspection under the provisions of the latter part of
Article 17 (2) of the Act
, he shall replace the inspection of completion as referred to in
Article 19
by examining the written result of inspection submitted by the Korea Fire Equipment Inspection Corporation or the related professional organization determined by the Ministerial Decree of Home Affairs (hereinafter, referred to as the “designated organization”), under the conditions as prescribed by the Ministerial Decree of Home Affairs.
[This Article Wholly Amended by Presidential Decree No. 15485, Sep. 27, 1997]
법령보기 화면
Article 19-3 (Self-Inspection of Manufacturer, etc.)
(1)
For the purpose of the former part of
Article 17-2 (2) of the Act
, the term “manufacturer, etc. as prescribed by the Presidential Decree” means the following:
1.
Hazardous materials manufacturer; and
2.
Handling place of handling the hazardous materials of not less than 10 times the designated quantity.
(2)
For the purpose of the proviso of
Article 17-2 (2) of the Act
, the term “hazardous material storage tanks as prescribed by the Presidential Decree” means the following:
1.
Outdoor storage tank covering one million liters or more in storage capacity; and
2.
Underground storage tank (limited to the manufacturer, etc. of which the total of storage capacity of each underground storage tank is twenty thousand liters or more).
[This Article Added by Presidential Decree No. 15485, Sep. 27, 1997]
Section 3 Hazardous Materials Safety Manager, etc., and Private Fire Brigades
법령보기 화면
Article 20 (Hazardous Materials Safety Managers in Regards to Gas Stations, etc.)
(1)
For the purpose of
Article 20 (1) 1 of the Act
, the term “places prescribed by the Presidential Decree” means the following:
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
1.
Gas stations;
2.
Sales establishments (special hazardous materials sales handling establishments are limited to the case of selling only Category No. 4 hazardous materials); and
3.
Deleted.
<by Presidential Decree No. 14747, Aug. 10, 1995>
(2)
Deleted.
<by Presidential Decree No. 15485, Sep. 27, 1997>
(3)
For the purpose of
Article 20 (1) 3 of the Act
, the term “things prescribed by Presidential Decree” means power generating equipment in areas falling under any of the following subparagraphs of
Article 2 of the Act
on the Promotion of Electrification in Agricultural and Fishing Villages or manufacturers, etc. used for power generating equipment.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(4)
For the purpose of
Article 20 (1) 4 of the Act
, the term “hazardous materials as prescribed by the Presidential Decree” means hazardous materials as referred to in Category Nos. 4 and 6 of the Appendix 3, and hazardous materials as prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 21 (Manufacturers, etc. that shall Employ Hazardous Materials Facilities Safety Workers)
Manufacturers, etc. that shall employ hazardous materials facilities safety workers under
Article 21 (1) of the Act
shall be the manufacturers, etc. of handling hazardous materials of not less than 10,000 times the designated quantity:
Provided
, That the following manufacturer, etc. shall be excluded:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
The general handling places where boilers, burners, internal-combustion engines and any other similar equipments consume the hazardous materials;
2.
The storage handling places where tanks fixed to vehicles and others similar to these are used for filling the hazardous materials;
3.
The storage handling places where steel drums and other containers are used to store the hazardous materials;
4.
The general handling places where oil pressure equipment, lubrication equipment and other similar equipment are used to handle the hazardous materials;
5.
Manufacturers or general handling places falling under the
Mining Safety Act
; and
6.
Manufacturers or general handling places falling under the Control of Firearms, Swords and Explosives, etc. Act.
법령보기 화면
Article 22 (Manufacturers, etc. that shall have Fire Prevention Regulations)
Manufacturers, etc. that shall have the fire prevention regulations for the purpose of fire prevention under
Article 22 (1) of the Act
shall be manufacturers, etc. falling under any one of the following subparagraphs:
Provided
, That general handling places and storage handling places equipped only with indoor tank storage facilities (limited to the case of heating purpose) or underground tank storage facilities, and manufacturers, etc. having determined their security regulations as referred to in the
Mining Safety Act
are excluded:
<Amended by Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Manufacturers, etc. handling the hazardous materials of not less than 10 times the designated quantity;
2.
Storage handling establishments and general handling establishments handling the hazardous materials of not less than 30 times the designated quantity; and
3.
through 5. Deleted.
<by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 23 (Organization of Private Fire Brigades)
(1)
The manufacturer, etc. that shall form a private fire brigades (hereinafter referred to as the “private fire brigade”) under
Article 23 of the Act
are as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Manufacturers, etc. storing or handling the hazardous materials of Category No. 4 not less than 3,000 times the designated quantity (excluding manufacturers as referred to in subparagraph 5 of
Article 21
);
2.
General handling establishments storing or handling hazardous materials of Category No. 4 not less than 3,000 times the designated quantity (excluding general handling establishments as referred to in subparagraph 5 of
Article 21
); and
3.
Storage handling establishments storing or handling hazardous materials of Category No. 4 not less than 20,000 times the designated quantity.
(2)
Private fire brigades organized according to the standards of the following table shall be formed in manufacturers, etc. as referred to in paragraph (1) 1 or general handling establishments as referred to in paragraph (1) 2 (excluding general handling establishments as referred to in subparagraphs 1, 4, and 6 of
Article 21
; hereinafter in this paragraph the same shall apply):
Provided
, That for the purpose of preventing fires or other fire disasters, the organizing may be done differently under the Ministerial Decree of Home Affairs for manufacturer, etc. and general handling places concluding an agreement of settlement regarding mutual support with other manufacturer, etc. and general handling places.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(3)
In general handling places as referred to in paragraph (1) 2 (limited to general handling places as referred to in subparagraphs 1, 4, and 6 of
Article 21
) or storage handling places as referred to in paragraph (1) 3, a private fire brigade for fire fighting organized with one foam trailer with a diameter of the nozzle of the foam drainage hydrant being not less than 65 millimeters and the storage amount of foam fire extinguishing agents being not less than 400 liters, and not less than two operating personnel shall be organized.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(4)
Chemical fire engines as referred to in paragraph (2) shall have fire fighting capability and equipment (including individual equipments such as fire extinguishing agents and equipments and heat resistant uniforms) prescribed by the Ministerial Decree of Home Affairs.
(5)
Installers of manufacturer, etc., having organized self-units for fire fighting as referred to in paragraph (1) shall conduct self-training for fire fighting at least once every three months regularly.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(6)
The chief of fire station of the relevant jurisdiction shall guide and supervise matters regarding the operation of the self-unit for fire fighting.
CHAPTER Ⅳ FIRE FIGHTING FACILITIES
Section 1 General Provisions
법령보기 화면
Article 24 (Types of Fire Fighting Facilities)
(1)
Fire fighting equipment means water and other machinery, tools, or equipment of the following that executes fire extinguishing, using fire-extinguishing agents and things having the corresponding fire extinguishing capability:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Fire extinguishing tools:
(a)
Manual fire extinguishers;
(b)
Automatic fire extinguishers; and
(c)
Handy portable fire extinguishing tools:
(ⅰ)
Handy portable fire extinguishing tools using fire extinguishing agents;
(ⅱ)
Extension Chile saltpeter or extension pearlite; and
(ⅲ)
Dry sand;
2.
Indoor fire hydrant equipment;
3.
Sprinkler equipment and simple sprinkler equipment;
4.
Water spraying fire extinguishing equipment, foam fire extinguishing equipment, carbon dioxide fire extinguishing equipment, halogen compound fire extinguishing equipment and powder fire extinguishing equipment (hereinafter referred to as “water spraying, etc. fire extinguishing equipment”); and
5.
Outdoor fire hydrant equipment and power generated fire fighting pump equipment.
(2)
Alarm equipments are machinery, tools, or equipment that notify the outbreak of fire and are as follows:
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
1.
Emergency bell equipment, automatic siren equipment and independent alarm sensors (hereinafter referred to as “emergency alarm equipment”);
2.
Emergency broadcast equipment;
3.
Short circuit alarm;
4.
Automatic fire detection equipment;
5.
Automatic prompt fire notification equipment; and
6.
Gas leakage alarm.
(3)
Evacuation equipments are things used for the purpose of evacuation in a case where fire breaks out and are the following:
1.
Slides, evacuation ladders, escape chutes, escape hatches, evacuation bridge, evacuation rope, air safety mats, and other evacuation tools;
2.
Life saving rescue equipments such as heat resistant uniforms, oxygen respiratory machine, artificial resuscitation equipments, etc.;
3.
Guiding lights and guiding signs; and
4.
Emergency lights.
(4)
Fire fighting water equipments are the ones to store fire fighting water necessary for the suppression of fires and are the following:
1.
Waterworks equipment for fire fighting water; and
2.
Fire fighting water tanks, water reservoir and other fire fighting water equipment.
(5)
Fire fighting activity equipments are the following:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
1.
Smokeproof equipment;
2.
Connecting water pipe equipment;
3.
Connecting water sprinkler equipment;
4.
Emergency electrical outlet equipment;
5.
Cordless communication assistance equipment; and
6.
Combustion prevention equipment.
법령보기 화면
Article 25 (Total Sectioning and Connecting Parts of Fire Fighting Properties)
(1)
In case where a fire fighting property with a fireproof structure is sectioned by a floor or wall of fireproof structure without an opening, those parts sectioned shall each be considered different fire fighting properties in the application of the provision of this Chapter.
(2)
In case not less than two fire fighting properties are connected by passageways, hallways, or pit, etc. (hereinafter referred to as “connecting passageways”) prescribed by the Minister of Home Affairs, the not less than two fire fighting properties that are connected shall be considered as one fire fighting property in the application of the provisions of this Chapter.
[This Article Wholly Amended by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 26 (Special Areas Applicable to Standards of Fire Fighting Facilities of Underground Streets)
In case where the underground floor of the special areas of the Appendix 1 is connected with the underground streets, the part of the said underground floor shall be considered the underground streets in the application of the provisions (except the provisions regarding fire fighting equipments) of this Chapter.
Section 2 Fire Fighting Properties where Fire Fighting Facilities shall be Installed
법령보기 화면
Article 27 (Fire Fighting Facilities of Special Areas)
On special areas of the Appendix 1 under
Article 30 (1) of the Act
, fire fighting facilities according to the installment object standards as referred to in
Articles 28
through
Article 32
inclusive shall be installed.
법령보기 화면
Article 28 (Fire Fighting Equipment)
(1)
The fire fighting properties where fire fighting tools shall be installed are as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Things where manual fire extinguishers or handy portable fire extinguishing tools shall be installed:
(a)
Things that are not less than 33 square meters in total floor area; and
(b)
Designated cultural heritages and gas facilities that do not fall under the clause of (a); and
2.
Things where automatic fire extinguishers shall be installed:
The sixth floor or higher for apartments that have not less than eleven floors.
(2)
The fire fighting properties where indoor fire hydrant equipment shall be installed are as follows:
Provided
, That this shall not apply to gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Fire fighting properties (excluding tunnels among underground streets) of which the total floor area is not less than 3,000 square meters, or all floors for those having a floor with a floor area of not less than 600 square meters among underground floors, windowless floors or floors with the fourth floor or higher;
1-2. Tunnels, among underground streets, which are not less than 1000 meters in length;
2.
All floors for neighborhood activity facilities, amusement facilities, sales facilities, lodging facilities, facilities for the old and young, medical facilities, business facilities, communications and photography facilities, factories, storage facilities, transportation vehicle related facilities, and complex buildings with a total floor area of not less than 1,500 square meters or those with a floor area of not less than 300 square meters among the underground floors, windowless floors, or the floors above the fourth floor, all of which not falling under any of preceding subparagraph 1;
3.
Things that store or handle special combustible materials of not less than 750 times the amount determined in the Appendix 4 as factories and storage facilities not falling under preceding subparagraphs 1 and 2; and
4.
Garages and parking lots installed on the roofs of buildings of which the floor area used for parking is not less than 200 square meters.
(3)
The fire fighting properties where sprinkler equipment shall be installed are as follows:
Provided
, That this shall not apply in the case of gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Viewing assembly and sports facilities of which the floor area of a stage (including equipment rooms and property rooms attached to a stage; hereinafter, the same shall apply) meets the standards as referred to in the following items or higher:
(a)
The stage of which the floor area is 300 square meters, in case where the stage is located on an underground floor, windowless floor, or the fourth floor or higher; and
(b)
The stage of which the floor area is 500 square meters, in case where the stage is located on any other floor;
2.
All floors for sales facilities of which the total floor area meets the standards as referred to in the following items or higher:
(a)
6,000 square meters for buildings of not more than three stories; and
(b)
5,000 square meters for buildings of not less than four stories;
3.
All floors for those that have floors used as hotels or motels for buildings of not less than 11 stories;
4.
The floors not less than the sixteenth floor for apartments of not less than 16 stories;
5.
Things that are not less than 1,500 square meters in total floor area that are rack-style storages (those mean storages with a shelf or a similar stuff and a transport equipment for receiving materials by an elevator) with the height of the ceiling being higher than 10 meters;
6.
Things that store or handle special combustible materials of not less than 1,000 times the amount determined in the Appendix 4 that are storage facilities not falling under subparagraph 5 or a factory;
7.
Things that are not less than 1,000 square meters in total floor area of underground streets (excluding tunnels);
8.
Floors not less than 1,000 square meters in total floor area that do not fall under subparagraphs 1 through 6 inclusive of underground floors, windowless floors, or the 4th floor and above the 4th floor of fire fighting properties (schools, apartments and freezing storages are excluded);
9.
11th floor and above the 11th floor for the buildings that have not less than 11 floors that are fire fighting properties and do not fall under subparagraphs 1 through 6 inclusive or subparagraph 8.;
10.
Boiler rooms or connecting passageways constructed in the fire fighting properties of subparagraphs 1 through 9 inclusive; and
11.
All floors that are those of not less than 5,000 square meters in total floor area of complex buildings:
Provided
, That in the case of a complex building of residence and commerce, each shall be distinguished and installed according to the standards of subparagraphs 2 and 4.
(4)
Fire fighting properties where water spraying fire extinguishing equipment shall be installed are as follows:
Provided
, That this shall not apply in the case of gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Things storing or handling special combustible materials of not less than 1,000 times the amount determined in the Appendix 4, that are factories and storages;
1-2. Airplane hangar;
2.
Things not less than 800 square meters in total floor area among parking buildings;
3.
Garages and parking lots established in a building (in case of those attached to an apartment, limited to an apartment house falling under any of subparagraphs of
Article 7
(1) of the Decree on the Management of Apartment Houses) of which the floor area used for parking is not less than 200 square meters;
3-2. Things not less than 200 square meters for the floor area of the place which always holds vehicles that are vehicle inspection centers or vehicle maintenance centers;
4.
Things which can park not less than 20 vehicles, that are parking facilities with machine equipment such as elevators not falling under subparagraphs 2 and 3; and
5.
Things not less than 300 square meters in floor area that are electricity rooms, power generator rooms, electricity substation rooms (electricity rooms, power generator rooms, electricity substation rooms only installing electric wires and cables not using combustible covering and electric machines such as current transformers or a current breaker not using combustible insulating oil) storage battery room, communications room and computer room (in case there are not less than two rooms installed within the same fireproof section, these shall be considered as one room for the calculation of the floor area):
Provided
, That those of the main control room installed with an indoor power control in a fireproof structure with installation of a two voltage facility and using low voltage of not more than 220 volts for the electric machines and with workers permanently stationed for 24 hours are excluded.
(5)
Fire fighting properties where outdoor fire hydrant equipment shall be installed are as follows:
Provided
, That this shall not apply in the case of gas facilities, underground exits, or tunnels among underground streets:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Things which the sum of the floor area of the first and second floor is not less than 9,000 square meters. In this case, if there are not less than two buildings in the same area, the buildings whose horizontal distance, from the middle line of outer walls mutually, is not more than three meters for the first floor and not more than five meters for the second floor, shall be considered as one building;
2.
Things not less than 1,000 square meters in total floor area that are designated cultural heritage; and
3.
Things storing or handling special combustible materials of not less than 750 times the amount determined in the Appendix 4 outside the building that are factories and storage facilities not falling under subparagraph 1:
Provided
, That those where sprinkling equipment has been installed for the purpose of suppressing the dispersement of dust under
Article 28 of the Clean Air Conservation Act
are excluded.
(6)
Fire fighting properties where power generated fire fighting pumps shall be installed are as follows:
Provided
, That this shall not apply in the case of gas facilities, underground exits, or tunnels among underground streets:
<Added by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Fire fighting properties where indoor fire hydrant equipment shall be installed; and
2.
Fire fighting properties where outdoor fire hydrant equipment shall be installed.
법령보기 화면
Article 29 (Alarm Equipment)
(1)
Fire fighting properties which are to be equipped with emergency alarm equipment shall be as follows:
Provided
, That this shall not apply in the case of gas facilities or underground exits:
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
1.
Fire fighting property of which the total floor area is not less than 400 square meters (excluding tunnels among underground streets), or the floor area of underground floors or windowless floors is not less than 150 square meters (in case of a performance hall, not less than 100 square meters); and
2.
Tunnels, among underground streets, which are not less than 500 meters in length.
(2)
Emergency broadcasting equipment shall be installed in fire fighting properties which are not less than 3,500 square meters in total floor area or with not less than 11 floors or with not less than 3 underground floors:
Provided
, That this shall not apply in the cases of gas facilities, underground exits, or tunnels among underground streets.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(3)
Fire fighting properties (limited to the building not fire resisting construction but buildings with the wallㆍfloor or ceiling whose whole or part material is made of incombustibles or quasi-incombustibles with wire net put in) where short-circuit alarm systems shall be installed are as follows:
Provided
, That this shall not apply in the case of gas facilities, underground exits, or tunnels among underground streets:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Those that are not less than 500 square meters in total floor area (not less than 1,000 square meters in the cases of business facilities, communications and photography facilities, education and research facilities and exhibition facilities); and
2.
Those exceeding 100 amperes in the contracted current capacity (in case electricity of a different kind of contract is being supplied to the same building, it means the greatest contracted current among them).
(4)
Fire fighting properties where automatic fire detection equipment shall be installed are as follows:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Neighborhood living facilities (except general baths), amusement facilities, lodging facilities, facilities for the old and the young, medical facilities and complex buildings that are not less than 600 square meters in total floor area;
2.
General baths, viewing assembly and sports facilities, communications and photography facilities, tourist resting facilities, underground streets (excluding tunnels), sales facilities, apartments (limited to those falling under any of the subparagraphs of
Article 7
(1) of the Decree on the Management of Apartment Houses) and dormitories, business facilities, transportation vehicle related facilities, exhibition facilities, factories and storage facilities all of which are not less than 1,000 square meters in total floor area;
3.
Educational research facilities, religious facilities, animal and plant related facilities, sanitation, etc. related facilities and correctional facilities that are not less than 2,000 square meters in total floor area;
4.
Factories and storage facilities not falling under subparagraph 2 which store or handle special combustible materials of not less than 500 times the amount designated in the Appendix 4; and
5.
Underground exits prescribed by the Ministerial Decree of Home Affairs.
(5)
Automatic prompt fire notification equipments shall be installed in sales facilities, lodging facilities, communications and photography facilities, exhibition facilities, factories and storage facilities having a floor of not less than 1,500 square meters in floor area.
법령보기 화면
Article 30 (Evacuation Equipment)
(1)
Evacuation equipment shall be installed in all the floors of the fire fighting property except the evacuation floor, second floor and the eleventh floor or above:
Provided
, That this shall not apply in the cases of gas facilities, underground exits, or tunnels among underground streets.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(2)
Life rescue equipments shall be installed in tourist hotels having not less than seven stories and in hospitals of at least five stories:
Provided
, That artificial resuscitation equipment in the case of hospitals are excluded.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(3)
Evacuation exit guiding lights, passageway guiding lights and guide signs shall be installed in all fire fighting properties (excluding tunnels among underground streets), and guest seat guiding lights shall be installed in dancing amusement restaurants, viewing assemblies and sports facilities:
Provided
, That in the case of underground exits, evacuation exit guiding lights and passageway guiding lights are excluded.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(4)
The fire fighting properties where emergency lights shall be installed are the following:
Provided
, That this shall not apply to garages, parking facilities, gas facilities, underground exits, or those similar to this that are prescribed by the Ministerial Decree of Home Affairs:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Buildings having not less than five stories and not less than 3,000 square meters in total floor area;
2.
The underground floor or windowless floor in the case of the fire fighting properties not falling under subparagraph 1 and the underground floor or the windowless floor being not less than 450 square meters in floor area; and
3.
Tunnels, among underground streets, which are not less than 500 meters in length.
법령보기 화면
Article 31 (Fire Fighting Water Equipment)
(1)
Fire fighting properties where waterworks fire fighting water equipment shall be installed are the following:
Provided
, That in the areas not having installed the waterworks prescribed by the Ministerial Decree of Home Affairs may this be replaced with a water hole the attached fire fighting water reservoir:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Those not less than 5,000 square meters in total floor area:
Provided
, That this shall not apply in the cases of gas facilities, underground exits, or tunnels among underground streets; and
2.
Those gas facilities having a sum of not less than 100 tons in storage capacity of the tank exposed above the ground.
(2)
Fire fighting water reservoirs shall be installed in the fire fighting properties (excluding apartments, gas facilities, and tunnels among underground streets) of the following subparagraphs:
Provided
, That this can be replaced by a fire fighting water reservoir in case the emergency water facility conforms to the facilities standard prescribed by the Ministerial Decree of Home Affairs as referred to in
Article 58 of the Building Act
:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Those having the sum of the floor area of the first and second floor of not less than 15,000 square meters. In this case, in a case where not less than two buildings exist in the same area, if the parallel distance from the middle line between the outer walls of this building for the first floor is not more than three meters, and not more than five meters for the second floor, this shall be considered as one building; and
2.
Those fire fighting properties not falling under the preceding subparagraph 1 and being not less than 11 stories in height.
법령보기 화면
Article 32 (Fire Fighting Activities Equipment)
(1)
Fire fighting properties where smokeproof equipments shall be installed are the following:
<Amended by Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Those viewing assemblies and sports facilities having a floor area of the stage area of not less than 200 square meters;
2.
Those neighborhood activities and recreation facilities, sales facilities, and overnight sleeping facilities having a floor area of the underground floors or the windowless floors of not less than 1,000 square meters;
3.
Those waiting rooms or resting rooms of cross-country bus terminals, railroad station buildings, airport facilities, marine transportation facilities having a floor area of the underground floors or the windowless floors of not less than 1,000 square meters;
4.
Those underground streets (excluding tunnels) having a total floor area not less than 1,000 square meters;
4-2. Tunnels, among underground streets, which are not less than 1,000 meters in length; and
5.
Special evacuation stairs and elevator areas of emergency elevators constructed in special areas (except side-corridor-type apartments).
(2)
Fire fighting properties where connecting water pipe equipment shall be installed are as follows:
Provided
, That this shall not apply in the cases of gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Buildings not less than five stories high having not less than 6,000 square meters in total floor area;
2.
Fire fighting properties not falling under subparagraph 1 being not less than 7 stories in height;
3.
Fire fighting properties not falling under subparagraphs 1 and 2 having underground floors of not less than three floors and the sum of the floor area of the underground floors being not less than 1,000 square meters; and
4.
Tunnels, among underground streets, which are not less than 2,000 meters in length.
(3)
Fire fighting properties where water sprinkling connecting equipment shall be installed are as follows:
Provided
, That underground exits are excluded, and in the case of subparagraphs 1 and 2, when the main structural parts consist of a fireproof structure, the areas of the bathing room, toilet room, electricity room, machine room (except the boiler room), communications machine room, elevator shaft, linen shoot and the pipe duct are excluded:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
1.
Those sales facilities having a floor area of not less than 1,000 square meters;
2.
Those underground floors having a sum of the floor area of not less than 150 square meters:
Provided
, That it is those underground floors of apartments (limited to those used only for evacuation facilities) that are not more than the size of citizen housing as referred to in the proviso clause of Article 30 (1) of the Ordinance of Housing Construction Promotion Act and underground floors of schools that are not less than 700 square meters;
3.
Tank facilities among the gas facilities that are not less than 30 tons in tank capacity exposed above the ground; and
4.
Connecting passageways attached in the fire fighting properties of subparagraphs 1 and 2.
(4)
The fire fighting properties where emergency plug equipments shall be installed are as follows:
Provided
, That this shall not apply in the cases of gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Eleventh floor or above for those buildings with at least eleven stories;
2.
All the underground floors for those having not less than three underground floors and the sum of the floor areas of the underground floor being not less than 1,000 square meters; and
3.
Tunnels, among underground streets, which are not less than 500 meters in length.
(5)
The fire fighting properties where wireless communications aid equipment shall be installed are as follows:
Provided
, That this shall not apply in the cases of gas facilities or underground exits:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Those underground streets having a total floor area of not less than 1,000 square meters;
2.
All the underground floors for those having the sum of the floor areas of the underground floors of not less than 3,000 square meters or having not less than three underground floors and the sum of the floor areas of the underground floors being not less than 1,000 square meters; and
3.
Tunnels, among underground streets, which are not less than 500 meters in length.
(6)
Combustion prevention equipment shall be installed in the underground exits prescribed by the Ministerial Decree of Home Affairs.
<Added by Presidential Decree No. 14334, Jul. 20, 1994>
Section 3 Installation Exemption, etc. of Fire Fighting Facilities
법령보기 화면
Article 33 (Exemption etc. of Fire Fighting Facilities Installation)
(1)
In case where the sprinkler equipment water spraying fire extinguishing equipment, outdoor fire hydrant equipment, or power generated fire fighting pump equipment are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to fire fighting properties where automatic fire extinguishers or indoor fire hydrant equipment shall be installed, the automatic fire extinguishers or indoor fire hydrant equipment do not have to be installed within partial area of the effective range of the equipment (including the stairs of the floors and the accessories room with the sprinkler equipment or water spraying fire extinguishing equipment installed that are prescribed by the Ministerial Decree of Home Affairs, and limited to the parts of the first floor and second floor for the outdoor fire hydrant equipment or power generated fire fighting pump equipment).
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14747, Aug. 10, 1995>
(2)
In case where water spraying fire extinguishing equipments are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where sprinkler equipment shall be installed, the sprinkler equipment may not have to be installed within the partial area of the effective range of the equipment.
(3)
In case where sprinkler equipments are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to garages or parking lots (including those falling under
Article 28
(4) 3-2) where the water spraying fire extinguishing equipments shall be installed, or to the fire fighting properties storing or handling special combustible materials of the Appendix 4,the water spraying fire extinguishing equipment may not have to be installed within the partial area of the effective range of the equipment.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(4)
In case where the sprinkler equipment, water spraying fire extinguishing equipment, or power generated fire fighting pump equipment are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where the outdoor fire hydrant equipments shall be installed, the outdoor fire hydrant equipment may not have to be installed within the partial area of the effective range of the equipment.
(5)
In case where the indoor fire hydrant equipment, outdoor fire hydrant equipment, sprinkler equipment or water spraying fire extinguishing equipment are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where power generated fire fighting pump equipment shall be installed, the power generated fire fighting pump equipment may not have to be installed within the partial area of the effective range of the equipment.
(6)
In case where the sprinkler equipment, water spraying fire extinguishing equipment, or foam fire fighting equipment (limited to those installed with a closed-type head having an operating time of within 60 seconds and a indicating temperature of not more than 75 degrees celsius) are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties (except the parts of the fire fighting properties prescribed by the Ministerial Decree of Home Affairs) where automatic fire detecting equipment shall be installed, the automatic fire detecting equipment may not have to be installed within the partial area of the effective range of the equipment.
(7)
In case where the automatic fire detecting equipments are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where an emergency alarm system shall be installed, the emergency alarm system may not have to be installed within the partial area of the effective range of the equipment.
(8)
In case where the automatic fire detecting equipment or emergency alarm system or any broadcasting equipment producing sounds better or equivalent to the emergency alarm system are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where emergency broadcasting equipment shall be installed, the emergency broadcasting equipment may not have to be installed within parts of the effective range of the equipment.
(9)
In case it is deemed that there is no interference to evacuation according to the situation of the location, structure, or equipment of the fire fighting properties where evacuation equipment shall be installed, the evacuation equipment may not have to be installed under the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(10)
In case indoor fire hydrant equipment, sprinkler equipment, or connecting sprinkler equipment constructed with connecting water pipes outdoors and water proof holes indoors are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where connecting water pipes equipment shall be installed, the connecting water pipes equipment may not have to be installed within the partial area of the effective range of the equipment.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(11)
In case sprinkler equipment or water spraying fire extinguishing equipment constructed with water holes are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where connecting sprinkler equipment shall be installed, the connecting sprinkler equipment may not have to be installed within the partial area of the effective range of the equipment.
(12)
In case an air conditioning equipment are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where smokeproof equipment shall be installed, the smokeproof equipment may not have to be installed.
(13)
In case evacuation exit guiding lights or passageway guiding lights are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where emergency lights shall be installed, the emergency lights may not have to be installed within the partial area of the effective range of the guiding lights.
(14)
In case where short circuit alarms or ground fault circuit interrupter equipment are installed as referred to in electricity related Acts and subordinate statutes to the fire fighting properties or to their parts, the short circuit alarms do not have to be installed within the partial area of the effective range of the equipment.
(15)
In case mobile communications internal line equipment are installed applicable to the standards prescribed by the Ministerial Decree of Home Affairs to the fire fighting properties where wireless communications aid equipment shall be installed, the wireless communications aid equipment may not have to be installed.
<Added by Presidential Decree No. 14747, Aug. 10, 1995>
(16)
In case where fire fighting water facilities are installed under the provisions as prescribed by the Ministerial Decree of Home Affairs around the area of the fire fighting properties where waterworks fire extinguishing water facilities shall be installed, the waterworks fire extinguishing water facilities do not have to be installed.
<Added by Presidential Decree No. 14747, Aug. 10, 1995>
법령보기 화면
Article 33-2 (Special Case for Applying Fire Fighting Facilities Standards of Building Extensions or Altering Purpose of Use)
(1)
In the case of building extensions to existing special areas as referred to in
Article 31 (2) of the Act
, the standards of the fire fighting facilities at the time of extending the building is applied to the entire special area including the existing parts:
Provided
, That this is exempted for the fire fighting facilities that shall be installed to the existing parts in case the existing parts and the extension parts are sectioned with fireproof floors and walls or with fireproof doors or automatic fireproof shutters applicable to the standards prescribed by the Ministerial Decree of Home Affairs.
(2)
In case there is an alteration to the purpose of use for the special area, the standards of the fire fighting facilities at the time of the alteration of the purpose of use is applied, limited to the parts being altered:
Provided
, That in a case where the parts of the previous purpose of use was installed applicable to the standards of the fire fighting facilities at the time the said parts was installed in the case of the higher fire hazard purpose of use prescribed and publicly noticed by the Ministry of Home Affairs being altered to the lower fire hazard purpose of use, standards of the fire fighting facilities at the time the parts of the previous purpose of use was installed is applied.
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 34 (Special Cases of Fire Fighting Facilities Application)
(1)
Among the special areas of the Appendix 1 with respect to the special areas prescribed by the Ministerial Decree of Home Affairs, the special case regarding the fire fighting facilities as referred to in
Articles 28
through
32
inclusive can be prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(2)
Under
Article 69 (2) of the Act
, the chief of fire station may order the installation of outdoor fire hydrant equipment, connecting water pipe equipment, connecting sprinkler equipment, or foam trailer with respect to the fire fighting properties within the fire precaution zone.
(3)
In case of those fire fighting properties, where fire fighting facilities shall be installed under
Article 28
(2) through (6) inclusive and
Articles 29
through
32
inclusive, having the main structural parts and finishing materials installed with incombustible materials and falling under any of the following subparagraphs, the said fire fighting facilities do not have to be installed:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
1.
A water purification plant or others used in a similar purpose as this;
2.
Work areas of pulp factories, washing or electricity charging work areas of beverage factories, or others used in a similar purpose as this; and
3.
Processing factories machine assembly factories foundry factories of building stones incombustible metals-incombustible building materials, etc., or storages not storing or handling combustible materials (except hazardous materials less than the designated quantity or the hazardous materials being stored or handled in manufacturer, etc. permitted under
Article 16 of the Act
).
(4)
In a case where water spraying equipments, etc. are installed as referred to in gas related Acts and subordinate statutes to the gas facilities and connecting water holes for fire engine use are attached to this equipments, the chief of fire station may order not to install the connecting sprinkler equipments.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994>
(5)
Among the fire fighting property not falling under paragraphs (1) through (3) inclusive, in the case the chief of fire station determines the situation of its location, structure and equipment warrants the danger of the eruption and burning of fire remarkably low even though the fire fighting facilities are not installed or the damage due to fire can be minimized due to fire, he does not have to apply either entire or the part of the provisions of Chapter 4, Section 2.
Section 5 Type Approval, etc. of Fire Fighting Machiery, Tools, etc.
법령보기 화면
Article 35 Deleted.<by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 36 (Fire Fighting Machinery and Tools, etc. Subject to Type Approval)
The fire fighting machinery and tools, etc. which are subject to the type approval by the Minister of Home Affairs pursuant to the provisions of
Article 50 (1) of the Act
shall be as follows:
1.
Manual and automatic fire extinguishers (except chemically reacting foam fire extinguishers), handy portable fire extinguishing tools and fire extinguisher pressurizing gas vessels using fire extinguishing agents (except those having received inspection under the
High-Pressure Gas Safety Control Act
);
2.
Fire extinguishing agents (except carbon dioxide fire extinguishing agents and chemically reacting foam fire extinguishing agents);
3.
Fire retardant agents:
Fire retardant liquids, fire retardant paints and fire retardant materials;
4.
Fire fighting pumps:
Power generated fire fighting pumps, mobile fire fighting pumps;
5.
Fire fighting pump vehicles (including ladder vehicles and refracting vehicles not equipped with power generated fire fighting pumps);
6.
Fire fighting suction pipes and fire fighting hoses;
7.
Connecting metal holes:
Connecting metal holes for the fire fighting hose, connecting metal holes for the suction pipes and mid-connecting metal holes;
8.
Indoor fire hydrant waterproof holes, outdoor fire hydrants, nozzle, water shooting gun;
9.
Among the automatic fire extinguishing equipment, the water-leakage indicating equipment, simultaneous opening valves, pressure chambers, watering heads, sprinkler heads, and gas cylinder selection valves;
10.
Water holes and waterproof holes;
11.
Metal evacuation ladders, escape hatches, escape chutes;
12.
Heat resistant uniforms, and breathing gear;
13.
Among the automatic fire detection equipment, the transmitters, receivers, connecters, sensors (including independent alarm sensors) and sound equipment (including alarm bells);
14.
Gas leakage alarms and short circuit alarms;
15.
Guiding lights and emergency lights (limited to those with a built-in reserve power); and
16.
Cabinet type automatic fire extinguishing machines.
[This Article Wholly Amended by Presidential Decree No. 15485, Sep. 27, 1997]
CHAPTER Ⅵ FIRE FIGHTING SYSTEM CONSTRUCTION BUSINESS, ETC.
법령보기 화면
Article 37 (Standards of Licensing)
(1)
The licence standards of the fire fighting safety construction as referred to in
Article 53 of the Act
for technology capability, capital funds (meaning asset evaluated amount in the case of individuals. Hereinafter, the same shall apply), facilities and equipment are the same as in the Appendix 5.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(2)
The capital funds as referred to in paragraph (1) shall each be separate capital funds according to the types of businesses and the types of the juristic persons as referred to in the Act or other Acts and subordinate statutes, and the evaluated amount of assets shall be the appraised and evaluated amount as referred to in the
Public Notice of Values and Appraisal of Lands, etc. Act
.
(3)
The Mayor or
Do
governor, if he deems it necessary, may order a company appraisal to be conducted by a company appraising agency with respect to its capital funds.
법령보기 화면
Article 38 (Contract Price Limit Assessment)
(1)
The contract price limit as referred to in
Article 59 of the Act
shall be the construction record of the past two years of the fire fighting system construction businessman:
Provided
, That the capital funds itself in case one year has not passed since the businessman received the license the construction business licence, and the calculated sum of the construction amounts for the past one year and the capital funds, in the case of the fire fighting system business with not less than one year and less than two years shall each be the contract price limit.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(2)
The construction record as referred to in paragraph (1) excludes the given contract for work portion and includes the received contract for work portion, and in the case where the fire fighting system construction business is transferred, acquired, or merged, the construction record prior to the transfer, acquisition, or merger is added.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(3)
The construction amount in applying the contract price limit for the fire fighting system construction businessman shall be calculated. based on the contract for work amount of one construction (in a case where one individual fire fighting system construction businessman divides a fire fighting facilities construction in the same land or building into not less than two constructions in the case of a contract for work or a given contract for work and the period of construction entirely or partially overlaps, this shall be considered as one construction. Hereinafter in this Article the same shall apply) that he has contracted or a given contract for work. In this case, in a case where the material is provided by the employer of the contractor (in the case of given contract for work, the contractor is included), the market price and the transportation fee of that material is included in the contract for work amount.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
(4)
In case not less than two fire fighting system construction businessmen simultaneously receive a contract for work for one fire fighting facilities construction, the added sum amount of the contract price limit of each of the fire fighting safety construction businessman shall be the limited contract price.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(5)
The effective period of the contract price limit shall be until the day before the next contract price limit is publicly noticed.
(6)
In order to meet the need of calculation of the contract price limit as referred to in paragraph (1), the fire fighting system construction businessman shall submit fire fighting system construction records to the Mayor/
Do
governor under the conditions as prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 39 (Special Cases Related to Application of Contract Price Limit)
For the purpose of the proviso of
Article 59
(1) of this Act, the term “other grounds prescribed by the Presidential Decree” means the fluctuation of the currency exchange rates as referred to in
Article 5 of the Foreign Exchange Control Act
.
법령보기 화면
Article 40 (Rescission of Contract for Work)
(1)
For the purpose of the provision of the preceding paragraph of
Article 61 (1) of the Act
, the term “grounds prescribed by the Presidential Decree” means those fire fighting system construction businesses that temporarily close or close business or discontinues the fire fighting system construction for not less than thirty days without due cause.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(2)
The employer of the contractor of the fire fighting system construction may, under the provisions of the latter part of
Article 61 (1) of the Act
, rescind the contract for work within 30 days after the receiving of notification by the fire fighting system construction businessman whose license is revoked or business is suspended or of the fact that grounds as referred to in paragraph (1) are created, or after the day this fact is known.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(3)
The fire fighting system construction businessman whose contract has been rescinded, shall transfer matters on the progress of construction, relevant blueprints, etc. to a new contractor of the fire fighting system construction.
<Added by Presidential Decree No. 15485, Sep. 27, 1997>
[This Article Wholly Amended by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 40-2 (Fire Fighting Construction Superintendence Objects)
(1)
For the purpose of the provisions of the main text of
Article 61-2 (1) of the Act
, the term “special areas of not less than the size as prescribed by the Presidential Decree” means the special areas having a total floor area of not less than 1,000 square meters (total floor area of 2,000 square meters for religious facilities) that shall receive a permit and consent of use inspection under
Article 4
(1):
Provided
, That special areas equipped only with respective fire fighting facilities falling under
Article 24
(1) 1 and (2) 1 through 3, 5 and 6, and (3), apartments (limited to apartments of not more than ten stories), schools, public work facilities (limited to the government buildings of the State or local government), freezing storages, animal and plant related facilities, sanitation, etc. related facilities, correctional facilities, among special areas as shown in the Appendix 1, and the special areas falling under the special cases of the application of fire fighting facilities under
Article 34
(1) and (3) through (5) inclusive (except in the case of applying the special cases with respect to parts of the fire fighting facilities) are excluded from the objects for the fire fighting construction superintendence.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
(2)
Under the proviso clause of
Article 61-2 (1) of the Act
, the State, local government, government-invested institution by
Framework Act on the Management of Government-Invested Institutions
, local governmentinvested public corporation or local government public corporation by
Local Public Enterprises Act
may designate a construction superintendent among public officials under his jurisdiction or workers who are persons having first class fire fighting equipment engineer or professional engineer of fire fighting equipment qualification. In this case, agreement with the chief of fire station shall be made in advance.
<Newly inserted by Presidential Decree No. 14747, Aug. 10, 1995>
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 40-3 (Objects Applicable to Replacement of Completion of Construction Inspection of Fire Fighting Facilities with Fire Fighting Construction Superintendence Report)
For the purpose of the provisions of the proviso of
Article 62 (2) of the Act
, the term “special areas prescribed by the Presidential Decree” means the special areas that are subject to the fire fighting construction superintendence under
Article 40-2
:
Provided
, That the special areas over which the affiliated public officials or workers are designated as construction superintendents under
Article 40-2
(2) shall be excluded.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995; Presidential Decree No. 15485, Sep. 27, 1997>
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 40-4 (Period and Method of Repairs of Defects in Fire Fighting System Construction)
(1)
The period of repairs of defects as referred to in
Article 61-3 (1) of the Act
are as the following subparagraphs:
Provided
, That in the case of apartment house, it is prescribed by the Decree on the Management of Apartment Houses:
1.
Guiding lights, guide signs, emergency lights, emergency broadcasting equipment and wireless communications aid equipment: one year; and
2.
Automatic fire extinguishers, indoor fire hydrant equipment, sprinkler equipment, water spraying fire extinguishing equipment, outdoor fire hydrant equipment, automatic fire detecting equipment, fire extinguishing water equipment, fire extinguishing activity equipment (except wireless communications aid equipment): two years.
(2)
In case where the fire fighting system construction businessman does not execute the repairs of defects or the persons concerned of the special areas deems the defect repair plan to be unreasonable and that the special area has a total floor area of not less than 100,000 square meters (except apartments), this shall be notified to the Minister of Home Affairs, and in the case of the total floor area being less than 100,000 square meters or the object for repairs of defects is an apartment, to the chief of fire station by the persons concerned.
(3)
The Minister of Home Affairs, receiving the notification under paragraph (2), shall request deliberation to the Central Fire Fighting Safety Technical Commission and the chief of fire station shall request deliberation to the Local Fire Fighting Safety Technical Commission with regard to the defect condition prescribed by the Ministerial Decree of Home Affairs.
(4)
In a case where the Minister of Home Affairs or the chief of fire station receives the notification of the deliberation results as referred to in paragraph (3), the results shall be notified to the persons concerned of the special areas or the fire fighting system construction businessman within ten days. In a case where the deliberation results proves the pending work to be defective, a period necessary for the repairs of defects shall be determined and orders for repairs of defects shall be given to the fire fighting system construction businessman.
(5)
In a case where the persons concerned of the special areas or the fire fighting system construction businessman receiving notification of the deliberation results or receiving defect repair orders by the chief of relevant fire station under paragraph (4) deems the deliberation results or the defect repair orders as unreasonable, he may request a redeliberation with respect to the defect conditions to the Minister of Home Affairs.
(6)
The Minister of Home Affairs receiving the request for a re-deliberation under paragraph (5) shall request a deliberation with respect to the defect conditions to the Central Fire Fighting Safety Technical Commission and according to the decision rendered by the commission, shall have the chief of fire station under paragraph (4) notify the re-deliberation results and have him order the repairs of defects.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 40-5 (Guarantee of Repairs of Defects)
(1)
The construction of the fire fighting system that shall guarantee the repairs of defects under
Article 61-3 (3) of the Act
shall be conducted by construction of the fire fighting system that shall make a new construction report under
Article 62 (2) of the Act
:
Provided
, That fire fighting system construction being not more than five million won in the contract amount (meaning the added amount in the case of the fire fighting system construction businessman dividing the fire fighting system construction within the same district into not less than two contracts) are excluded.
(2)
The fire fighting system construction businessman that shall guarantee repairs of defects under paragraph (1) shall deposit the guarantee certificate falling under any of the following subparagraphs to the persons concerned of the special areas (meaning the employer of the contractor in case where the builder of the building construction signs the contract for work with respect to the fire fighting system of the said special areas. Hereinafter, the same shall apply):
<Amended by Presidential Decree No. 15485, Sep. 27, 1997; Presidential Decree No. 15581, Dec. 31, 1997>
1.
The payment guarantee certificates issued by the Korea Development Bank, the Export-Import Bank of Korea, the Korea Long-Term Credit Bank as referred to in Long-Term Credit Bank Act, or a financial institution as referred to in
Article 3 of the Banking Act
;
2.
Securities under the provision of Article 21 of the Enforcement Decree of the Furtherance of the Capital Market Act;
3.
Insurance guarantee policies issued by insurance business proprietor under the
Insurance Business Act
;
4.
The guarantee certificates guaranteeing the payment of a credit guarantee fund as referred to in the
Credit Guarantee Fund Act
, a technology credit guarantee fund as referred to in Financial Assistance to New Technology Business Act, or debt payment issued by the Engineering Mutual Benefit Society as referred to in
Engineering Technology Promotion Act
;
5.
Time deposit certificates issued by the banks and financial institutions as referred to in subparagraph 1 or postal service organization;
6.
Profit securities issued by trust companies under the
Trust Business Act
;
7.
Profit securities issued by the trust companies under the Securities Investment
Trust Business Act
;
8.
Guarantee certificates for repair of defects issued by a construction-related mutual-aid association under the
Framework Act on the Construction Industry
;
9.
Guarantee certificates for repair of defects issued by an electrical construction mutual aid association under the Electrical Construction Mutual Aid Association Act;
10.
Guarantee certificates for repair of defects issued by an information and communication mutual-aid association under the
Information and Communication Work Business Act
; and
11.
Guarantee certificates for repair of defects issued by a housing project mutual-aid association under the
Housing Construction Promotion Act
.
(3)
The defect repair guaranteed amount as referred to in paragraph (2) shall be 5/100 of the guaranteed amount in a case where the fire fighting system concerned is the alarm system and 3/100 of the guaranteed amount in the case where it is all other systems:
Provided
, That in case other Acts prescribe differently with regard to the defect repair guaranteed amount, the other Acts and subordinate statutes shall prevail.
(4)
Deleted.
<by Presidential Decree No. 15485, Sep. 27, 1997>
(5)
The guarantee certificate, etc. of the repairs of defects with regard to the fire fighting facilities of the apartment notwithstanding the provisions of paragraph (2) shall be deposited with the employer of the contractor (the chief of fire station in case the employer of the contractor and the fire fighting system construction businessman are the same) of the said fire fighting facilities, and in case it is deposited with the chief of fire station when a tenant representative committee is organized, the chief of fire station shall transfer without delay the guarantee certificate, etc. to the tenant representative committee.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(6)
In a case where the fire fighting system construction businessman does not execute the defect repair order as referred to in the latter part of
Article 40-4
(4) or in the provision of paragraph (6) of the same Article, the persons concerned of the special areas or the tenant representative committee holding the guarantee money, etc. under the provisions of paragraphs (2) and (5) shall take the necessary measures according to the types of guarantee certificates for repair of defects, etc. as prescribed by the Ministry of Home Affairs.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 40-6 (Completion of Repairs of Defects)
(1)
The fire fighting system construction businessman shall notify the persons concerned of the special areas, of the scheduled completion date of the defect repair period prescribed by the Ordinance of the Minister of Home Affairs thirty days prior to the expiration of the defect repair period as referred to in
Article 40-4
(1).
(2)
The defect repair period ends with the expiration of the period as referred to in
Article 40-4
(1):
Provided
, That in case where the repairs of defects are in progress, it ends at the time of the completion of the said repairs of defects.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41 (New Construction Management of Fire Fighting System Construction)
The types and range of the fire fighting system construction that shall be constructed under the responsibility of the fire fighting system engineer under the provisions of
Article 63 (2) of the Act
are the same as in the Appendix 6.
CHAPTER Ⅵ-2 DESIGNING OF FIRE FIGHTING SYSTEM AND CONSTRUCTION SUPERINTENDENCE BUSINESS.
법령보기 화면
Article 41-2 (Objects for Registration of Fire Fighting System Designing and Fire Fighting Construction Superintendence Business)
For the purpose of
Article 65-2 (1) 1 and 2 of the Act
, the term “special areas of not less than the size prescribed by the Presidential Decree” means the special areas as referred to in
Article 40-2
.
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 41-3 (Types, etc. of Fire Fighting System Designing Business and Fire Fighting Construction Superintendence Business)
The types, registration standards and business operation range of the fire fighting system designing business and fire fighting construction superintendence business as referred to in
Article 65-2 (2) of the Act
shall be the same as in the Appendix 7.
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
법령보기 화면
Article 41-4 (Types and Method of Fire Fighting Construction Superintendence)
(1)
The types and method of the fire fighting construction superintendence as referred to in the preceding part of
Article 65-4 (3) of the Act
shall be the same as in the Appendix 8.
(2)
For the purpose of the latter part of
Article 65-4 (3) of the Act
, the term “fire fighting system construction of not less than the size prescribed by the Presidential Decree” means the construction of the fire fighting system installed in the special areas (except apartments) of not less than 30,000 square meters in total floor area.
<Amended by Presidential Decree No. 14747, Aug. 10, 1995>
(3)
For the purpose of the latter part of
Article 65-4 (3) of the Act
, the term “persons prescribed by the Presidential Decree” means the assistant technical laborers as referred to in the Appendix 7.
[This Article Added by Presidential Decree No. 14334, Jul. 20, 1994]
CHAPTER Ⅵ-3 FIRE FIGHTING SAFETY TECHNICAL COMMISSION
법령보기 화면
Article 41-5 (Organization of Fire Fighting Safety Technical Commission)
(1)
The organization of the Central Fire Fighting Safety Technical Commission as referred to in
Article 65-11 of the Act
shall be composed of nine commissioners including the chairman, and the Local Fire Fighting Safety Technical Commission shall be composed of not less than five and not more than seven commissioners including the chairman.
(2)
The Central Fire Fighting Safety Technical Commission can organize and operate subcommissions by different fields.
(3)
Among the commissioners of the Central Fire Fighting Safety Technical Commission and the Local Fire Fighting Safety Technical Commission (hereinafter referred to as “Fire Fighting Safety Technical Commission”), the term of the commissioners who are not public officials shall be two years:
Provided
, That the term of a commissioner filling a vacancy shall be the remaining period of his predecessor.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-6 (Appointment or Commission of Commissioners)
(1)
The commissioners of the Central Fire Fighting Safety Technical Commission shall have one person from among the fire fighting public officials under the jurisdiction of the Ministry of Home Affairs and among persons falling under any of the following subparagraphs appointed or commissioned by the Minister of Home Affairs :
1.
Persons having a masters degree or above in a fire fighting related degree;
2.
A professional fire fighting equipment engineer or a fire fighting system manager;
3.
Persons having worked for not less than five years in fire fighting related work at a fire fighting related company, juristic person, or organization; and
4.
Persons having not less than five years of work experience teaching or researching in fire fighting public officials educational institutions, or in educational institutions same or above the technical college level (limited to fire fighting related departments), or in fire fighting related research institutions.
(2)
The commissioners of the Local Fire Fighting Safety Technical Commission shall have one person from among the fire fighting public officials under the jurisdiction of the said City/
Do
and among persons falling under any of the subparagraphs of preceding paragraph (1) appointed or commissioned by the Mayor/
Do
governor.
(3)
The chairperson of the Central Fire Fighting Safety Technical Commission shall be commissioned from among the commissioners by the Minister of Home Affairs, and the chairperson of the Local Fire Fighting Safety Technical Commission shall be commissioned from the commissioners of the Commission by the Mayor/
Do
governor.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-7 (Official Duties of Chairperson and Commissioners)
(1)
The chairperson of the Fire Fighting Safety Technical Commission convenes meetings of the Fire Fighting Safety Technical Commission and shall be its chairperson.
(2)
In a case where the chairperson has been incapacitated, the commissioner designated by the chairperson in advance acts on behalf of the chairperson.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-8 (Investigation, etc. of Commission)
(1)
In a case where it is necessary for the purpose of executing work such as deliberating with respect to the defect conditions, etc., the Fire Fighting Safety Technical Commission may call the presence of the persons concerned, relevant witnesses, or appraiser to give statements or expert testimony or request the submission of necessary documents or materials, or may have the commissioners of the Fire Fighting Safety Technical Commission enter the area concerned to investigate or inspect the materials or documents.
(2)
The chief of fire station shall cooperate in the execution of necessary investigations or the inspection of documents of the Fire Fighting Safety Technical Commission.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-9 (Allowance for Commissioners)
An investigation research allowance may be payed to the commissioners of the Fire Fighting Safety Technical Commission within the range of the budget.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-10 (Enactment of Operation Rules)
(1)
The Central Fire Fighting Safety Technical Commission may enact the processing procedures, deliberation standards of the relevant works of the Fire Fighting Safety Technical Commission and other necessary matters for the operation of the commission pertaining to the operation rules.
(2)
In the enactment of the operation rules as referred to in paragraph (1), the Central Fire Fighting Safety Technical Commission shall have an approval from the Minister of Home Affairs in advance. The same shall also apply in a case where there is an alteration to this.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
법령보기 화면
Article 41-11 (Objects for Deliberation)
For the purpose of
Article 65-11 (1) 1 and 3 of the Act
, the term “not less than the size prescribed by the Presidential Decree” means not less than 100,000 square meters, and for the purpose of
Article 65-11 (2) 1 and 2 of the Act
, the term “less than the size prescribed by the Presidential Decree” means less than 100,000 square meters.
[This Article Added by Presidential Decree No. 14747, Aug. 10, 1995]
CHAPTER Ⅶ FIRE PRECAUTION ZONE, ETC.
법령보기 화면
Article 42 (Designation of Fire Precaution Zones)
The Mayor/
Do
governor, under
Article 69 (1) of the Act
, may designate areas falling under any of the following subparagraphs as a fire precaution zone:
1.
Market areas;
2.
Factory or storage massed areas;
3.
Wooden building massed areas;
4.
Fire fighting water supply, fire fighting system, or fire fighting passageway insufficiently equipped areas;
5.
Hazardous materials storage and handling facilities massed areas; and
6.
Areas with factories producing petrochemical products.
법령보기 화면
Article 43 (Fire Drill in Fire Precaution Zone)
(1)
Training plans for the fire drill within the fire precaution zone as referred to in
Article 69 (2) of the Act
shall be made and conducted not less than two times annually.
(2)
The fire drills as referred to in paragraph (1) are as follows:
1.
Fire notification training;
2.
Fire extinguishing training; and
3.
First aid and rescue training.
CHAPTER Ⅷ PRIVATE FIRE FIGHTING
법령보기 화면
Article 44 Deleted.<by Presidential Decree No. 15485, Sep. 27, 1997>
법령보기 화면
Article 45 (Expenses, etc., Concerning Assignment of Private Fire Fighters)
(1)
The special assigner shall bear the following expenses concerning the assignment of the private fire fighters:
1.
The salary and allowance payable to the private fire fighters;
2.
Uniform allowances for the private fire fighters;
3.
Education costs for the private fire fighters;
4.
Indemnity as referred to in paragraph (3) and severance pay as referred to in paragraph (4); and
5.
Other expenses necessary to the operation of the private fire fighters.
(2)
Deleted.
<by Presidential Decree No. 15485, Sep. 27, 1997>
(3)
In case the private fire fighter falls under any of the following subparagraphs, the indemnity is payed by the Minister of Labor under the same Act in case of the special assigner being insured by an insurance of the
Industrial Accident Compensation Insurance Act
, or by the special assigner under the
Labor Standards Act
in other cases:
1.
In case of injury, illness, or death due to the execution of official duties; and
2.
In case of retirement or death within two years after retirement, due to injury or illness while performing official duties.
(4)
In case where a private fire fighter retires, the special assigner shall pay the retirement allowance as referred to in the
Labor Standards Act
.
법령보기 화면
Article 46 (Dress Codes)
(1)
The private fire fighter shall wear the uniform while performing official duty.
(2)
Matters necessary for the uniform and dress codes of the private fire fighters shall be prescribed by the Minister of Home Affairs.
법령보기 화면
Article 47 (Education)
The special assigner shall make the person hired as a private fire fighter get the education necessary to execute official duties.
법령보기 화면
Article 48 (Official Duties, etc., of Private Fire Fighters)
(1)
The private fire fighter shall execute the following official duties under the guidance and supervision of the special assigner and the chief of fire station of the jurisdiction:
1.
Assisting the fire prevention manager business as referred to in
Article 9 (2) of the Act
;
2.
Assisting the hazardous materials safety manager business as referred to in
Article 20 (2) of the Act
;
3.
Taking measures to rescue persons and extinguish fires or prevent the spread of fires as referred to in
Article 72 (1) of the Act
; and
4.
Any duty that is ordered by the chief of fire station who deems it necessary for the purpose of prevention, precaution and suppression of fires.
(2)
Matters necessary for the operation and procedures of the assignment situation report, job education for service, and work supervision, etc. of the private fire fighters shall be prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
CHAPTER Ⅸ FIRST AID AND RESCUE BUSINESS
법령보기 화면
Article 49 (Organization and Operation, etc., of First Aid and Rescue Units)
(1)
Matters pertaining to the organization and operation of first aid and rescue units as referred to in
Articles 93 (5) and 94 (3) of the Act
shall be determined by the Ministerial Decree of Home Affairs depending on the size of population, types of the fire fighting property, outbreaks of fire and special characteristics of the area:
Provided
, That the matters relating to Emergency Medical Treatment Act may be determined by the Ministerial Decree of Home Affairs after consultation with the Minister of Health and Welfare.
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 14446, Dec. 23, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
(2)
The first aid unit member shall be appointed from among the fire fighting public officials falling under any of the following subparagraphs:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Persons who have received education pertaining to the first aid business prescribed by the Ministerial Decree of Home Affairs;
2.
Medical persons as referred to in
Article 2 (1) of the Medical Service Act
;
3.
Persons approved of the qualifications of a nursing aides under
Article 58 (1) of the Medical Service Act
; and
4.
Persons approved of the qualifications of an emergency rescue worker under Article 15 of Emergency Medical Treatment Act.
(3)
The rescue unit member shall be appointed from among the fire fighting public officials falling under any of the following subparagraphs:
<Added by Presidential Decree No. 15485, Sep. 27, 1997>
1.
Persons who have received education pertaining to the rescue business as determined by the Ministerial Decree of Home Affairs;
2.
Persons who hold certificates of qualifications related to life salvage; and
3.
Persons who have service experience of two years or more in a rescue-related field at the State, local government, public institution, or other similar institutions.
법령보기 화면
Article 50 (Assistance by Medical Service Facilities)
Matters pertaining to the assistance of the medical service facilities necessary to the execution of the first aid business as referred to in
Article 93 (2) of the Act
shall be determined in consultation between the Minister of Home Affairs and the Minister of Health and Welfare.
<Amended by Presidential Decree No. 14446, Dec. 23, 1994>
법령보기 화면
Article 50-2 (Permanent Station, etc. of First Aid Units)
In a case where the chief of fire headquarters or the chief of fire station deems it necessary, he may station permanently a part of the first aid units on areas such as the national expressways where emergency patients are very likely to be reported.
[This Article Wholly Amended by Presidential Decree No. 15485, Sep. 27, 1997]
법령보기 화면
Article 51 Deleted.<by Presidential Decree No. 15485, Sep. 27, 1997>
CHAPTER Ⅹ NATIONAL TREASURY ASSISTANCE
법령보기 화면
Article 52 (Objects for and Standard Amount of National Treasury Assistance)
(1)
Objects for national treasury assistance as referred to in
Article 96 of the Act
are as follows:
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
1.
The following fire fighting activity equipment and system:
(a)
Fire fighting vehicles;
(b)
Fire fighting helicopters and fire fighting boats; and
(c)
Communications equipment and computer system for fire fighting only;
2.
Fire fighting government office buildings.
(2)
The national treasury assistance standard amount according to size and types of fire fighting activity equipment and system of paragraph (1) shall be prescribed by the Ministerial Decree of Home Affairs.
<Amended by Presidential Decree No. 15485, Sep. 27, 1997>
(3)
The national treasury assistance shall be not less than 1/3 of the standard amount of paragraph (2) within the range of the budget.
법령보기 화면
Article 53 (Application for Assistance)
In a case where the Mayor/
Do
governor desires to receive national treasury assistance with respect to the cost necessary for the purchase or installation of the fire fighting activity equipment, tools and equipment in the Seoul Special Metropolitan City, Metropolitan Cities or Dos (hereinafter referred to as the “City/
Do
”), an assistance fund distribution application shall be made to the Minister of Home Affairs under the conditions as prescribed by the Ministerial Decree of Home Affairs.
법령보기 화면
Article 54 (Cancellation or Suspension, etc. of Assistance Distribution)
(1)
After the Minister of Home Affairs distributes the assistance to the City/
Do
, in a case where the grounds falling under any of the following subparagraphs have arisen, he may order the cancellation, suspension or the repayment of the whole or partial amount of the assistance:
1.
In a case where the fire fighting activity equipment and tools and systems have not been entirely or partially purchased or installed without due cause; and
2.
In a case where the assistance has been used for other purposes or used in violation of the assistance conditions.
(2)
In a case where the Minister of Home Affairs desires to cancel, suspend the distribution of the assistance or receive repayment of the distributed assistance under paragraph (1), he shall give the Mayor/
Do
governor the opportunity to submit a statement of opinion or material establishing a prima facie case.
법령보기 화면
Article 55 (Supervision)
The Minister of Home Affairs can order the submission of a report to the City/
Do
that received the assistance or have the relevant public officials under his jurisdiction inspect the fund assisted fire fighting activity equipment, tools and equipments.
CHAPTER XI KOREA FIRE SAFETY ASSOCIATION
법령보기 화면
Article 56 (Qualification of Members)
For the purpose of
Article 99 (1) 1 of the Act
, the term “persons prescribed by the Presidential Decree” means the persons falling under any of the following subparagraphs:
1.
Persons having received an installation permit for a manufacturer, etc., (except regular handling places for the purpose of heating) under
Article 16
(1);
2.
Persons having received a manufacturing business permit of fire fighting machinery and tools under
Article 44
(1); and
3.
Persons having received a fire fighting equipment construction business license under
Article 52
(1).
법령보기 화면
Article 56 Deleted. <by Presidential Decree No. 15485, Sep. 27, 1997> <<Enforcement Date: Mar. 8, 1999>>
법령보기 화면
Article 57 (Articles of Association)
The content of the Articles of the National Fire Safety Association as referred to in
Article 100 (1) of the Act
are as follows:
1.
Purpose;
2.
Name;
3.
Location of office;
4.
Matters related to business;
5.
Matters related to the acquisition or loss of membership;
6.
Matters related to membership fee;
7.
Matters related to asset and accounting;
8.
Matters related to staff officers and workers;
9.
Matters related to the organization and structure;
10.
Matters related to the general meeting and the board of directors; and
11.
Matters related to the alteration of the Articles of incorporation.
법령보기 화면
Article 58 (Establishment Registration Matters)
The establishment registration matters of the Association as referred to in
Article 100
(1) are as follows:
1.
Purpose;
2.
Name;
3.
Location of Office;
4.
Date of establishment approval;
5.
Name and address of staff officers; and
6.
Total amount of assets.
법령보기 화면
Article 59 (Staff Officers)
The number of staff officers, their terms and methods of appointment by the Association as referred to in
Article 100 (1) of the Act
are as follows:
1.
The number of staff officers shall be not more than thirteen directors, including one chairman and two auditors, and staff officers excluding three directors including the chairman and one auditor as non-permanent members;
2.
The term of the staff officers shall be three years (the term for staff officers filling vacancies shall be the remaining term of the predecessor), and a continual reappointment is forbidden. In such case, the term of a staff officer filling a vacancy shall not be included in the reappointment limitation; and
3.
Staff officers shall be appointed from among persons having professional knowledge and experience related to fire fighting under the conditions as prescribed by the Articles of association.
법령보기 화면
Article 60 (Supervision, etc.)
(1)
The Minister of Home Affairs shall supervise the Association under
Article 100 (1) of the Act
.
(2)
The Association shall report the following matters to the Minister of Home Affairs under the conditions as prescribed by the Ministerial Decree of Home Affairs:
1.
The main decision matters of the general meeting and the board of directors;
2.
Matters related to the status of members; and
3.
Other important matters related to the Association and its members.
(3)
The business plan and budget of the Association shall be approved by the Minister of Home Affairs under the conditions as prescribed by the Articles of association.
CHAPTER XII SUPPLEMENTARY PROVISIONS
법령보기 화면
Article 61 (Education with Regard to Fire Fighting Facilities Managers)
For the purpose of
Article 105 (1) of the Act
, the term “other persons prescribed by the Presidential Decree” means the following persons:
<Amended by Presidential Decree No. 14334, Jul. 20, 1994; Presidential Decree No. 15485, Sep. 27, 1997>
1.
Persons in charge of the safety performance test at a hazardous materials tank safety performance testing business company as referred to in
Article 18 of the Act
;
2.
Fire fighting system managers and check-up assistants as referred to in
Article 33 (2) 2 of the Act
;
3.
Technical workers, as shown in the Appendix 5, who are engaged in fire protection systems construction businesses as referred to in
Article 52 of the Act
; and
4.
Fire fighting equipment professional engineers, fire fighting equipment engineers, architects, construction machinery equipment professional engineers, air conditioning and freezing machinery professional engineers, construction electrical equipment professional engineers, who are working in the fire fighting facilities designing business or fire fighting construction superintendence business as referred to in
Article 65-2 (1) of the Act
or assistant technical laborers as referred to in the provision of the Appendix 7. In such case the architects, construction machinery equipment professional engineers, cooperative freezing machinery professional engineers and construction electrical equipment professional engineers are limited to the persons registered as the main technical workers of the third class fire fighting facilities designing business or the fire fighting construction superintendence business of the Appendix 7.
법령보기 화면
Article 62 (Delegation of Authority)
The authority of the Minister of Home Affairs as referred to in
Article 12 of the Act
(limited to a flame retardant performance test business of articles to be post-processed under the provisions of
Article 11
(5)) and the authority of the Mayor/
Do
governor as referred to in
Articles 16, 17, 19, 22, 24 and 25 of the Act
, and subparagraph 2 of
Article 106 of the Act
shall be delegated to the chief of fire station, under the provisions of
Article 108 (1) of the Act
.
[This Article Wholly Amended by Presidential Decree No. 15598, Dec. 31, 1997]
법령보기 화면
Article 63 (Consignment of Business)
The Minister of Home Affairs shall consign the fire retardant performance test business as referred to in
Article 12 (1) of the Act
(excluding a flame retardant performance test business of articles to be post-processed under the provisions of
Article 11
(5)), and the type approval, authorization and examination of the fire fighting machinery and tools, the change in such type approval, and the performance test business, as referred to in
Articles 50 (1) and (2), 50-2 (1), and 50-4 (1) of the Act
, to the Korea Fire Equipment Inspection Corporation as referred to in
Article 103 of the Act
, and the education business with respect to the fire safety manager, etc. as referred to in
Article 105 (1) of the Act
, to the Association, respectively, under
Article 108 (2) of the Act
.
[This Article Wholly by Presidential Decree No. 15485, Sep. 27, 1997]
법령보기 화면
Article 64 (Levy of Fine for Negligence)
(1)
In a case where the Mayor/
Do
governor, the chief of fire headquarters, or the chief of fire station (hereinafter referred to as “relevant government office” in this Article) levies a fine for negligence under
Article 119 (2) and (6) of the Act
, the facts of the violation, appeal method and appeal period shall be clearly expressed on the document after the investigation and confirmation of the said act of violation is done, and the payment of fine shall be made known to the person subject to the fine for negligence.
(2)
In a case where the relevant government office desires to levy a fine for negligence under paragraph (1), it shall determine a period of not less than ten days to give to the person subject to the fine for negligency measure an opportunity to present an oral or written explanation. In such case, in a case where there is no explanation within the designated period, he shall be considered as having no opinion.
(3)
In determining the monetary amount of the fine for negligence, the relevant government office shall consider the motive and the result of the said violation.
(4)
The collection procedures of the fine for negligence shall be prescribed by the Ministerial Decree of Home Affairs.
법령보기 화면
Article 65 Deleted.<by Presidential Decree No. 15485, Sep. 27, 1997>
ADDENDA
Article 1 (Enforcement Date)
This Decree shall enter into force on the date of its promulgation.
Article 2 (Transitional Measures with Respect to Fire Resistance Managers)
(1)
Among the special areas installed at the time of the enforcement of this Decree, the persons concerned of the fire fighting property falling under the special areas where new fire resistance managers shall be installed under the provision of
Article 6
, shall assign fire resistance managers until December 31, 1992.
(2)
Fire resistance managers appointed under the previous provisions at the time of the enforcement of this Decree shall be considered as fire resistance managers as referred to in
Article 9
, but among them the persons lacking the qualification standards of a fire resistance manager shall receive special supplementary education conducted by the Korea Fire Safety Association until June 30, 1993.
Article 3 (Transitional Measure Regarding Hazardous Materials Handling Places)
Type No. 1 sales handling places and Type No. 2 sales handling places among the sales handling places of hazardous materials at the time of the enforcement of this Decree shall be considered as the petroleum sales handling places as referred to in subparagraph 2 of
Article 15
, and among the regular handling places of hazardous materials, the regular handling places that store hazardous materials or that have installed facilities for the purpose of transferring the hazardous materials to a container or mobile tank storage facility shall be considered as storage handling facilities as referred to subparagraph 4 of
Article 15
.
Article 4 (Transitional Measures with Regard to Self-Fire Fighting Units of Hazardous Materials Storage Handling Places)
Among the hazardous materials manufacturer, etc., installed at the time when this Decree enters into force, the hazardous materials manufacturer, etc., where the self-fire fighting units shall be newly installed under
Article 23
(1) 3 shall install it until December 31, 1994.
Article 5 (Transitional Measures with Regard to Term of Korea Fire Safety Association Staff Officers)
The term of persons working as a staff officers of the Korea Fire Safety Association at the time when this Decree enters into force shall comply with the previous provisions despite the provisions of subparagraph 2 of
Article 59
, but may be reappointed only one time.
Article 6 (Transitional Measures with Regard to Administrative Dispositions)
The permits issued by the administrative agency under the previous provision, other actions of or various reports to the administrative agency, and other actions to the administrative agency at the time when this Decree enters into force shall be considered as actions of or to the administrative agency as referred to in the Decree correspondingly.
Article 7 (Relationship with Other Acts and Subordinate Statutes)
In case other Acts and subordinate statutes have quoted the provisions of the previous
Enforcement Decree of the Fire Services Act
at the time when this Decree enters into force where there are Articles falling under this Decree among that Act, it shall be considered as those quoted from Articles falling under that Act in replacement of the previous provisions.
ADDENDA<Presidential Decree No. 14334, Jul. 20, 1994>
Article 1 (Enforcement Date)
This Decree shall enter into force on the date of its promulgation:
Provided
, That the amended provisions
Articles 28
(1) 2,
38
(1),
40-2
,
40-3
,
41-2
through
41-4
inclusive, subparagraph 2 of
Article 61
, and the Appendix 5 through the Appendix 8 inclusive shall enter into force on December 28, 1994.
Article 2 (Transitional Measures with Regard to Graduates with Industrial Safety Related Major)
Persons who graduated from a four year college or above at an educational institution majoring in an industrial safety related department by December 31, 1994 shall be considered as a person having graduated from an industrial safety related department as referred to in
Article 9
(1) 7 and (2) 7 of the amended provisions.
Article 3 (Transitional Measures with Regard to Application of Fire Fighting Facilities Standard to Gas Facilities and Underground Exits)
With respect to the gas facilities and underground exits installed at the time when this Decree enters into force, the previous examples shall be followed, despite the amended provisions of
Articles 27
through
32
inclusive.
Article 4 (Transitional Measures with Regard to Fire Fighting System Construction Businessman)
Persons having received the fire fighting system construction business licence under the previous provision at the time when this Decree enters into force shall be considered as the first class fire fighting system construction businessman as referred to in the amended provision of the Appendix 5, but shall have the licence qualification as referred to in the amended provision of the Appendix 5 by December 31, 1996.
ADDENDA<Presidential Decree No. 14446, Dec. 23, 1994>
Article 1 (Enforcement Date)
This Decree shall enter into force on the date of its promulgation. (Proviso is Omitted)
Articles 2 and 3 Omitted.
ADDENDA<Presidential Decree No. 14747, Aug. 10, 1995>
(1)
(Enforcement Date) This Decree shall enter into force on the date of its promulgation:
Provided
, That the amended provisions of
Articles 9
(5), subparagraph 5 of
Article 35,
40-4
through
40-6
inclusive,
Articles 41-5
through
41-11
inclusive shall enter into force on January 1, 1996.
(2)
(Transitional Measures with Regard to Hazardous Materials Sales Handling Places) The petroleum sales handling places installed under the proviso of the previous subparagraph 2 (a) of
Article 15
at the time when this Decree enters into force shall be considered as a petroleum sales handling place applicable to this Decree, and the quantity of the hazardous materials capable of being stored in the said petroleum sales handling place shall follow the previous provision.
(3)
(Transitional Measures with regard to fire fighting system construction business) Among the persons having received the fire fighting system construction business licence under the previous provision at the time when this Decree enters into force, the first class fire fighting system construction business shall be considered as a professional fire fighting system construction business and the second class fire fighting system construction business shall be considered as a regular fire fighting system construction business, but shall meet the licence qualification as referred to in the amended provision of the Appendix 5 until December 31, 1996.
ADDENDA<Presidential Decree No. 15389, Jun. 11, 1997>
Article 1 (Enforcement Date)
This Decree shall enter into force on the date of its promulgation. (Proviso is Omitted)
Article 2 Omitted.
ADDENDA<Presidential Decree No. 15485, Sep. 27, 1997>
Article 1 (Enforcement Date)
This Decree shall enter into force on the date of its promulgation:
Provided
, That the amended provisions of
Articles 19-2
and
36
shall enter into force on March 8, 1998, and the amended provisions of
Article 56
, on March 8, 1999.
Article 2 (Transitional Measures concerning Provisions of Flame Retardant)
The amended provisions of
Article 11
shall not apply with respect to the special areas for which business permission, etc. is granted at the time when this Decree enters into force, and the articles subject to frame retardant which are used at such special areas, and the flame retardant performance test of post-processed articles as referred to in the amended provisions of
Article 62
shall enter into force on September 8, 1998.
Article 3 (Transitional Measures concerning General Handling Places)
The storage handling places which are permitted as provided in subparagraph 6 of
Article 15
at the time when this Decree enters into force, but which are newly treated as general handling places under the amended provisions of subparagraph 5 of
Article 15
, shall be considered to be permitted as general handling places under the provisions of this Decree. In that case, the competent permission authority shall deliver a renewed permit within three months after this Decree enters into force.
Article 4 (Transitional Measures concerning Leakage Inspection, etc. of Manufacturer, etc.)
Any person who, at the time when this Decree enters into force, installs an underground storage tank covering less than 20,000 liters in storage capacity, but fails to conduct the leakage inspection thereon shall, notwithstanding the amended provisions of
Article 19-3
(2), conduct the leakage inspection pursuant to the previous provisions by June 30, 1998, and an underground storage tank which is subject to the inspection under the amended provisions of
Article 19-3
(2) shall go through the inspection within six months from the date designated by the Ministerial Decree of Home Affairs.
Article 5 (Transitional Measures concerning Application of Fire Fighting Equipment)
With respect to fire fighting properties on which the consent of building permission, etc. and report on construction work are effected at the time when this Decree enters into force, the amended provisions of
Article 28
(1) 2 and (2) 1-2 and 4,
Article 29
(1) 2,
Article 30
(4) 3, and
Article 32
(1) 4-2, (2) 4, (4) 3 and (5) 3 shall not apply.
Article 6 (Transitional Measures concerning Term of Office of Commissioner of Fire Fighting Safety Technical Commission)
The term of office of a commissioner of the Fire Fighting Safety Technical Commission at the time when this Decree enters into force shall be governed pursuant to the previous provisions notwithstanding the amended provisions of
Article 41-5
(3).
Article 7 (Transitional Measures concerning Permission, etc. of Hazardous Materials Manufacturer, etc. pursuant to Amendment of Hazardous Materials Categories)
Any person who has installed hazardous materials manufacturer, etc. to manufacture, handle, and store an inflammable solid, yellow phosphor, and hydrazine under the amended provisions of the Appendix 3 at the time when this Decree enters into force, shall be considered to have obtained permission (including permission for change) or gone through the completion inspection, etc. pursuant to the provisions of this Decree:
Provided
, That such person shall meet facilities standards, etc. pursuant to this Decree or order issued by this Decree by March 31, 1998.
Article 8 (Transitional Measures concerning Fire Fighting Construction Superintendent)
Any person who has made the registration of a fire fighting construction superintendence business at the time when this Decree enters into force shall be equipped with facilities and equipment pursuant to the amended provisions of subparagraph 2 of the Appendix 7 by December 31, 1997.
ADDENDA<Presidential Decree No. 15581, Dec. 31, 1997>
Article 1 (Enforcement Date)
This Decree shall enter into force on January 1, 1998. (Proviso is Omitted.)
Articles 2 through 7 Omitted.
ADDENDUM<Presidential Decree No. 15598, Dec. 31, 1997>
This Decree shall enter into force on January 1, 1998.